Dimensions<br />
P104 Measurement Units<br />
This parameter sets the units you want to use for programming and display<br />
Option<br />
Description<br />
1 = metres (Default) All units of measure are METRES<br />
2 = cm All units of measure are CENTIMETRES<br />
3 = mm All units of measure are MILLIMETRES<br />
4 = feet All units of measure are FEET<br />
5 = inches All units of measure are INCHES<br />
P105 Empty Level<br />
This parameter is to be set to the maximum distance from the face of the<br />
transducer to the empty point, in P104 Measurement Units. Note this<br />
value affects span as well, (see important information below), so should be<br />
set before span.<br />
Important Information<br />
When using DUET, the empty distance is measured from the face of the<br />
lower transducer to the empty point in P104 Measurement Units.<br />
When using the dB Mach 3 the empty distance is measured from the end<br />
of the horn to the empty point in P104 Measurement Units.<br />
Important Information<br />
When changing the Empty Distance (P105) you can also recalculate the<br />
values for the Span so that it equals the empty distance (P105) minus Near<br />
Blanking (P107) and the Relay Setpoints, so that they remain at the same<br />
percentage values of the empty distance as they were before you changed<br />
the empty distance (P105). You will be asked the question “Recalculate<br />
Span?” if you choose yes (enter 1), then the span will be recalculated. Any<br />
other answer will leave the span at its original value. You will then be asked<br />
if you want to “Recalculate Setpoints?”, if you choose yes (enter 1), then all<br />
Relay Setpoints will be recalculated as a percentage of the new empty<br />
distance. Any other answer will leave the setpoints at their original values.<br />
Page 90