Vacuum applications<br />
For applications under vacuum, Endress+Hauser recommends mounting the pressure transmitter below the<br />
lower diaphragm seal. This prevents a vacuum load of the diaphragm seal caused by the presence of filling oil<br />
in the capillaries.<br />
When the pressure transmitter is mounted above the lower diaphragm seal, the maximum height difference<br />
H1 in accordance with the following illustration must not be exceeded. The maximum height difference is<br />
dependent on the density of the filling oil and the smallest ever pressure that is permitted to occur at the<br />
diaphragm seal on the positive side (empty tank), see the following illustration, on the right.<br />
12.0<br />
Low temperature oil<br />
–<br />
+<br />
– +<br />
H1<br />
Height difference H1 [m]<br />
10.0<br />
8.0<br />
6.0<br />
4.0<br />
2.0<br />
Silicone oil<br />
Vegetable oil<br />
High temperature<br />
oil<br />
Inert oil<br />
0.0<br />
50 100 200 300 400 500 600 700 800 900 1000<br />
Pressure, diaphragm seal positive side [mbar abs ]<br />
P01-FMD7xxxx-11-xx-xx-xx-001<br />
Installation above the lower diaphragm seal<br />
P01-FMD7xxxx-05-xx-xx-en-002<br />
Diagram of maximum installation height above the lower diaphragm<br />
seal for vacuum applications dependent on the pressure at the<br />
diaphragm seal on the positive side<br />
Heat insulation – FMD<strong>77</strong><br />
The FMD<strong>77</strong> must only be insulated up to a certain height. The maximum permitted insulation height is<br />
indicated on the devices and applies to an insulation material with a heat conductivity 0.04 W/(m x K) and<br />
to the maximum permitted ambient and process temperature ( see table below). The data were determined<br />
under the most critical application "quiescent air".<br />
T A<br />
λ ≤ 0.04<br />
W<br />
mK •<br />
T P<br />
Maximum permitted insulation height<br />
P01-FMD<strong>77</strong>xxxx-11-xx-xx-xx-000<br />