<strong>Deltabar</strong> S<br />

Vacuum applications<br />

For applications under vacuum, Endress+Hauser recommends mounting the pressure transmitter below the<br />

lower diaphragm seal. This prevents a vacuum load of the diaphragm seal caused by the presence of filling oil<br />

in the capillaries.<br />

When the pressure transmitter is mounted above the lower diaphragm seal, the maximum height difference<br />

H1 in accordance with the following illustration must not be exceeded. The maximum height difference is<br />

dependent on the density of the filling oil and the smallest ever pressure that is permitted to occur at the<br />

diaphragm seal on the positive side (empty tank), see the following illustration, on the right.<br />

12.0<br />

Low temperature oil<br />

–<br />

+<br />

– +<br />

H1<br />

Height difference H1 [m]<br />

10.0<br />

8.0<br />

6.0<br />

4.0<br />

2.0<br />

Silicone oil<br />

Vegetable oil<br />

High temperature<br />

oil<br />

Inert oil<br />

0.0<br />

50 100 200 300 400 500 600 700 800 900 1000<br />

Pressure, diaphragm seal positive side [mbar abs ]<br />

P01-FMD7xxxx-11-xx-xx-xx-001<br />

Installation above the lower diaphragm seal<br />

P01-FMD7xxxx-05-xx-xx-en-002<br />

Diagram of maximum installation height above the lower diaphragm<br />

seal for vacuum applications dependent on the pressure at the<br />

diaphragm seal on the positive side<br />

Heat insulation – FMD<strong>77</strong><br />

The FMD<strong>77</strong> must only be insulated up to a certain height. The maximum permitted insulation height is<br />

indicated on the devices and applies to an insulation material with a heat conductivity 0.04 W/(m x K) and<br />

to the maximum permitted ambient and process temperature ( see table below). The data were determined<br />

under the most critical application "quiescent air".<br />

T A<br />

λ ≤ 0.04<br />

W<br />

mK •<br />

T P<br />

Maximum permitted insulation height<br />

P01-FMD<strong>77</strong>xxxx-11-xx-xx-xx-000<br />

Endress+Hauser 67<br />