Deltabar S PMD70/75 FMD76/77/78
Deltabar S, PMD70, PMD75, FMD76, FMD77, FMD78 - from AoteWell
Deltabar S, PMD70, PMD75, FMD76, FMD77, FMD78 - from AoteWell
- No tags were found...
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
www.aotewell.com www.fa-market.com info@aotewell.com<br />
<strong>Deltabar</strong> S<br />
Pressure on the negative side of the differential pressure transmitter (p – ) when the tank is empty (min. level)<br />
p – = p + p = Hv • ρ • g + H1 • ρ • g + p<br />
Hv H1<br />
Fl Fl i<br />
kg<br />
= 1.8 m • 0.96 • 9.81<br />
m kg<br />
+ 0.3 m • 0.96 • 9.81<br />
m<br />
+ p<br />
dm 3 s dm 3 s i<br />
= 197.<strong>77</strong> mbar + pi<br />
Pressure on the positive side of the differential pressure transmitter (p + ) when the tank is empty (min. level)<br />
p<br />
+<br />
= p + p = Hu • ρ • g + H1 • ρ • g + p<br />
Hu H1 M<br />
Fl i<br />
kg<br />
= 0.2 m • 1 • 9.81<br />
m kg<br />
+ 0.3 m • 0.96 • 9.81<br />
m<br />
+ p<br />
dm 3 s dm 3 s i<br />
= 47.87 mbar + pi<br />
Differential pressure at the transmitter (p Transmitter ) when the tank is empty<br />
Result:<br />
If the tank were full, a differential pressure of –51.80 mbar (-0.762 psi) would be present at the differential pressure<br />
transmitter. When the tank is empty, a differential pressure of –149.90 mbar (2.2485 psi) is present. Therefore, a 500 mbar<br />
(7.5 psi) measuring cell is required for this application.<br />
Capillary<br />
In order to obtain more precise measurement results and to avoid a defect in the device, mount the capillaries<br />
as follows:<br />
• vibration-free (in order to avoid additional pressure fluctuations)<br />
• not in the vicinity of heating or cooling lines<br />
• insulate if the ambient temperature is below or above the reference temperature<br />
• with a bending radius of 100 mm (3.94 in).<br />