<strong>Deltabar</strong> S<br />

Thermal change of the zero<br />

output and the output span –<br />

<strong>PMD70</strong>, <strong>FMD76</strong><br />

Measuring cell –10 to +60 °C (14 to 140 °F) –20 to –10 °C (-4 to 14 °F),<br />

+60 to +85 °C (140 to 185 °F)<br />

% of the set span<br />

25 mbar (0.3<strong>75</strong> psi) (0.35 x TD + 0.05) (0.3 x TD + 0.15)<br />

100 mbar<br />

(1.5 psi)<br />

(0.05 x TD + 0.05) (0.08 x TD + 0.07)<br />

Operating conditions (Installation)<br />

General installation<br />

instructions<br />

Measuring arrangement<br />

• The position-dependent zero point shift can be corrected directly at the device via operating keys, and also<br />

in hazardous areas in the case of devices with external operation. Diaphragm seals also shift the zero point,<br />

depending on the installation position ( ä 65 ff, "Installation instructions, diaphragm seal systems"<br />

section).<br />

• The housing of the <strong>Deltabar</strong> S can be rotated up to 380°. See ä 26, "Turning the housing" section.<br />

• Endress+Hauser offers a mounting bracket for installing the device on pipes or walls.<br />

See ä 24, "Wall and pipe-mounting" section.<br />

• When measuring in media containing solids, such as dirty liquids, installing separators and drain valves is<br />

useful for capturing and removing sediment.<br />

• Using a three-valve or five-valve manifold allows for easy commissioning, installation and maintenance<br />

without interrupting the process.<br />

• General recommendations for the pressure piping can be found in DIN 19210 "Methods for measurement<br />

of fluid flow; differential piping for flow measurement devices" or the corresponding national or international<br />

standards.<br />

• Install the pressure piping with a continuous gradient of at least 10%.<br />

• When routing the pressure piping outdoors, ensure sufficient anti-freeze protection, e.g. by using pipe heat<br />

tracing.<br />

• For FMD<strong>77</strong> and FMD<strong>78</strong>: ä 65 ff, "Installation instructions, diaphragm seal system" section.<br />

• Use flushing rings for flange and cell diaphragm seals if buildup or clogging can be expected at the diaphragm<br />

seal connection. The flushing ring can be fitted between the process connection and diaphragm seal. Material<br />

buildup in front of the process isolating diaphragm can be flushed away, and the pressure chamber vented,<br />

via the two lateral flushing holes.<br />

Flow measurement<br />

• The <strong>PMD70</strong> and PMD<strong>75</strong> are best suited to flow measurement.<br />

• Measuring arrangement for gases: Mount device above the measuring point.<br />

• Measuring arrangement for liquids and vapors: Mount device below the measuring point.<br />

• For flow measurement in vapors, mount the condensate traps at the same level as the tapping point and at<br />

the same distance from <strong>Deltabar</strong> S.<br />

Level measurement<br />

• <strong>PMD70</strong>, PMD<strong>75</strong>, <strong>FMD76</strong> and FMD<strong>77</strong> are best suited to level measurement in open tanks. All <strong>Deltabar</strong> S<br />

devices are suitable for level measurement in closed tanks.<br />

Measuring arrangement for level measurement in open tanks<br />

• <strong>PMD70</strong>, PMD<strong>75</strong>: Mount device below the lower measuring connection. The negative side is open to<br />

atmospheric pressure.<br />

• <strong>FMD76</strong>, FMD<strong>77</strong>: Mount device directly on the tank. The negative side is open to atmospheric pressure.<br />

Measuring arrangement for level measurement in closed tanks and closed tanks with superimposed vapor<br />

• <strong>PMD70</strong>, PMD<strong>75</strong>: Mount device below the lower measuring connection. Always connect the negative side<br />

above the maximum level via pressure piping.<br />

• <strong>FMD76</strong>, FMD<strong>77</strong>: Mount device directly on the tank. Always connect the negative side above the maximum<br />

level via pressure piping.<br />

• In the case of level measurement in closed tanks with superimposed vapor, a condensate trap ensures the<br />

pressure remains constant on the minus side.<br />

Endress+Hauser 23<br />