Micropilot M<br />
Terminal assignment 4…20 mA with HART<br />
The 2-wire cable is connected to the screw<br />
terminals (wire diameter 0.5…2.5mm) in the<br />
terminal compartment.<br />
Use 2-wire twisted pair cable with screen for<br />
the connection.<br />
Protective circuitry against reverse polarity,<br />
RFI, and over-voltage peaks is built into the<br />
device (refer to TI 241F »basics for EMCtests«).<br />
L00-<strong>FMR</strong>2xxxx-04-00-00-en-002<br />
Terminal assignment PROFIBUS-PA<br />
The digital communication signal is transmitted<br />
to the bus via a 2-wire connection. The bus also<br />
provides the auxiliary energy.<br />
Please use 2-wire twisted pair cable with<br />
screen.<br />
Hints regarding architecture and grounding of<br />
the network can be found in BA 198F<br />
»projecting hints PROFIBUS-PA« and the<br />
specification for PROFIBUS-PA.<br />
L00-<strong>FMR</strong>2xxxx-04-00-00-en-003<br />
Terminal assignment Foundation Fieldbus<br />
The digital communication signal is transmitted<br />
to the bus via a 2-wire connection. The bus<br />
also provides the auxiliary energy.<br />
Please use 2-wire twisted pair cable with<br />
screen. Further cable specifications can be<br />
found in the FF specification or the<br />
IEC 61158-2.<br />
Further hints regarding architecture and<br />
grounding of the network can be found at the<br />
Internet address »http://www.fieldbus.org«.<br />
L00-<strong>FMR</strong>2xxxx-04-00-00-en-007<br />
10 Endress+Hauser<br />