Rosemount 3051 Pressure Transmitter
Rosemount 3051 Pressure Transmitter - from AoteWell
Rosemount 3051 Pressure Transmitter - from AoteWell
- No tags were found...
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
www.rosemount.aotewell.com sales@aotewell.com AoteWell Sales team<br />
Product Data Sheet<br />
00813-0100-4001, Rev HA<br />
March 2008<br />
<strong>Rosemount</strong> <strong>3051</strong><br />
Total Performance<br />
For ±50 °F (28 °C) temperature changes, up to 1000 psi (6,9 MPa) line pressure (CD only), from 1:1 to 5:1 rangedown.<br />
Models<br />
<strong>3051</strong>C<br />
<strong>3051</strong>T<br />
Long Term Stability<br />
Models<br />
<strong>3051</strong>C<br />
Ranges 2-5<br />
Ranges 1-4<br />
Ranges 2-5<br />
<strong>3051</strong>CD Low/Draft Range<br />
Ranges 0-1<br />
<strong>3051</strong>T<br />
Ranges 1-4<br />
<strong>Rosemount</strong> <strong>3051</strong>H<br />
Ranges 2-3<br />
Ranges 4-5<br />
Total Performance<br />
±0.15% of span<br />
±0.15% of span<br />
Long Term Stability<br />
±0.125% of URL for 5 years<br />
±50 °F (28 °C) temperature changes, and up to 1000 psi (6,9 MPa) line pressure.<br />
±0.2% of URL for 1 year<br />
±0.125% of URL for 5 years<br />
±50 °F (28 °C) temperature changes, and up to 1000 psi (6,9 MPa) line pressure.<br />
±0.1% of URL for 1 year<br />
±0.2% of URL for 1 year<br />
Dynamic Performance<br />
Total Response Time (T d + T c ) (2) :<br />
<strong>3051</strong>C, Ranges 2-5:<br />
Range 1:<br />
Range 0:<br />
<strong>3051</strong>T:<br />
<strong>3051</strong>H/L:<br />
4 - 20 mA<br />
(HART protocol) (1)<br />
100 ms<br />
255 ms<br />
700 ms<br />
100 ms<br />
Consult factory<br />
Fieldbus<br />
protocol (3)<br />
152 ms<br />
307 ms<br />
752 ms<br />
152 ms<br />
Consult factory<br />
Dead Time (Td) 45 ms (nominal) 97 ms<br />
Update Rate 22 times per second 22 times per second<br />
(1) Dead time and update rate apply to all models and ranges; analog output only<br />
(2) Nominal total response time at 75 °F (24 °C) reference conditions.<br />
(3) <strong>Transmitter</strong> fieldbus output only, segment macro-cycle not included.<br />
Typical HART <strong>Transmitter</strong> Response Time<br />
<strong>Pressure</strong> Released<br />
100%<br />
36.8%<br />
<strong>Transmitter</strong> Output vs. Time<br />
T d<br />
T c<br />
T d = Dead Time<br />
T c = Time Constant<br />
Response Time = T d +T c<br />
63.2% of Total<br />
Step Change<br />
0%<br />
Time<br />
Line <strong>Pressure</strong> Effect per 1000 psi (6,9 MPa)<br />
For line pressures above 2000 psi (13,7 MPa) and Ranges 4-5, see user manual (<strong>Rosemount</strong> publication number 00809-0100-4001).<br />
Models<br />
Line <strong>Pressure</strong> Effect<br />
<strong>3051</strong>CD Zero Error (1)<br />
Range 0 ±0.125% of URL/100 psi (6,89 bar)<br />
Range 1 ±0.25% of URL/1000 psi (68,9 bar)<br />
Ranges 2-3 ±0.05% of URL/1000 psi (68,9 bar) for line pressures from 0 to 2000 psi (0 to 13,7 MPa)<br />
Span Error<br />
Range 0 ±0.15% of reading/100 psi (6,89 bar)<br />
Range 1 ±0.4% of reading/1000 psi (68,9 bar)<br />
Ranges 2-3 ±0.1% of reading/1000 psi (68,9 bar)<br />
<strong>3051</strong>HD Zero Error (1)<br />
All Ranges ±0.1% of URL/1000 psi (68,9 bar) for line pressures from 0 to 2000 psi (0 to 13,7 MPa)<br />
Span Error<br />
All Ranges ±0.1% of reading/1000 psi (68,9 bar)<br />
(1) Can be calibrated out at line pressure.<br />
5<br />