<strong>SIGUARD</strong> ® <strong>DSA</strong><br />

Situational awareness for dynamic stability<br />

as add-on control centre functionality<br />

www.siemens.com/siguard<br />

© Siemens AG 2012. All rights reserved.


Prof. Dr.-Ing. Rainer Krebs<br />

Principal Expert Power Technologies<br />

Head of Protection and Control System Studies<br />

Siemens AG, Infrastructure & Cities Sector<br />

IC SG SE PTI NC PCS, Erlangen, Germany<br />

Honorary Professor for System Protection and Control<br />

Otto-von-Guericke University Magdeburg, Germany<br />

German Member in working groups of: IEC, CIGRE, IEEE, DKE, T&D Europe<br />

Board Member of VDE Bavaria<br />

Page 2<br />

2013-06 R. Krebs<br />

© Siemens AG 2012. All rights reserved.<br />

IC SG SE PTI


Content<br />

• Challenges for Electrical Energy Supply Networks<br />

• The Solution: <strong>SIGUARD</strong> ®<br />

• The Dynamic Security Assessment <strong>SIGUARD</strong> ® <strong>DSA</strong><br />

• <strong>SIGUARD</strong> ® <strong>DSA</strong> Demonstrator<br />

• References<br />

Page 3<br />

2013-06 R. Krebs<br />

© Siemens AG 2012. All rights reserved.<br />

IC SG SE PTI


Content<br />

• Challenges for Electrical Energy Supply Networks<br />

• The Solution: <strong>SIGUARD</strong> ®<br />

• The Dynamic Security Assessment <strong>SIGUARD</strong> ® <strong>DSA</strong><br />

• <strong>SIGUARD</strong> ® <strong>DSA</strong> Demonstrator<br />

• References<br />

Page 4<br />

2013-06 R. Krebs<br />

© Siemens AG 2012. All rights reserved.<br />

IC SG SE PTI


Challenges for Electrical Energy Supply Networks<br />

Renewables<br />

• Bulk wind farms onshore and offshore are<br />

feeding transmission grids<br />

• Smaller wind farms and large PV plants are<br />

feeding distribution grids<br />

• Small roof PV plants feeding LV grid<br />

• Energy infeed is predictable, Power infeed is not<br />

predictable<br />

Energy trade<br />

• Energy market is deregulated<br />

The transmission grids with a clear<br />

„Power Transmission“ task<br />

are actually transformed into<br />

„Power Exchange“ platforms<br />

Transmission system expansion<br />

• Reduction of spinning reserve<br />

Power electronics equipments<br />

• Reduction of system inertia<br />

• High system dynamics<br />

Page 5<br />

2013-06 R. Krebs<br />

© Siemens AG 2012. All rights reserved.<br />

IC SG SE PTI


Challenges for Electrical Energy Supply Networks<br />

High System Dynamics<br />

Outage of 1100MW<br />

In the synchronous eastern grid of USA<br />

Travelling of a frequency wave acc. to the<br />

generator inertias with app. 600km/s<br />

Page 6<br />

2013-06 R. Krebs<br />

© Siemens AG 2012. All rights reserved.<br />

IC SG SE PTI


Challenges for Electrical Energy Supply Networks<br />

Involvement of Protection Relays in Blackouts<br />

In 80% of all blackouts relays are involved<br />

• Zone 3 trips of distance relays,<br />

often used for overload protection instead of<br />

thermal models in numerical relays<br />

• Missing load and power swing blocking<br />

• Uncoordinated protection / or overload<br />

settings across borders or between diff.<br />

utilities<br />

• Too low synchro-check settings<br />

• OC backup in parallel to distance or<br />

differential protection without delay<br />

• Development of primary system without<br />

adaption of relaying design and relay settings<br />

Source: udoleuschner.de: 400kV Mettlen-Lavorgo Line<br />

Area of tree flashover starting the 2003 Italy Blackout<br />

Page 7<br />

2013-06 R. Krebs<br />

© Siemens AG 2012. All rights reserved.<br />

IC SG SE PTI


Challenges for Electrical Energy Supply Networks<br />

Result in Blackouts<br />

>1,000,000 customer hours of disruption per event • Large number of blackouts per year<br />

in > 75% protection is involved (NERC)<br />

• Outages of large infrastructures<br />

• High outage costs<br />

• Death of humans<br />

Source: http://en.wikipedia.org/wiki/List_of_power_outages<br />

In the majority of cases:<br />

Blackouts of<br />

Probability<br />

Source: Prof. Arun Phadke, Virginia Tech Iniversity, USA<br />

Page 8<br />

2013-06 R. Krebs<br />

Electrical Systems<br />

are<br />

AVOIDABLE<br />

© Siemens AG 2012. All rights reserved.<br />

IC SG SE PTI


Content<br />

• Challenges for Electrical Energy Supply Networks<br />

• The Solution: <strong>SIGUARD</strong> ®<br />

• The Dynamic Security Assessment <strong>SIGUARD</strong> ® <strong>DSA</strong><br />

• <strong>SIGUARD</strong> ® <strong>DSA</strong> Demonstrator<br />

• References<br />

Page 9<br />

2013-06 R. Krebs<br />

© Siemens AG 2012. All rights reserved.<br />

IC SG SE PTI


<strong>SIGUARD</strong> ®<br />

The family of Power System Security Solutions<br />

<strong>SIGUARD</strong> is an innovative solution<br />

that helps ensure reliable power supply<br />

at all times.<br />

<strong>SIGUARD</strong> <strong>DSA</strong>: „Dynamic Security Assessment“<br />

for evaluation of the impact of contingencies on<br />

power system stability and it’s improvement<br />

<strong>SIGUARD</strong> PDP: „Phasor Data Processor“<br />

for acquisition, management and analysis of PMU<br />

measurements<br />

<strong>SIGUARD</strong> PSA: “Protection Security Assessment”<br />

for evaluation, auditing and improvement of the<br />

protection system<br />

Page 10<br />

2013-06 R. Krebs<br />

© Siemens AG 2012. All rights reserved.<br />

IC SG SE PTI


Content<br />

• Challenges for Electrical Energy Supply Networks<br />

• The Solution: <strong>SIGUARD</strong> ®<br />

• The Dynamic Security Assessment <strong>SIGUARD</strong> ® <strong>DSA</strong><br />

• <strong>SIGUARD</strong> ® <strong>DSA</strong> Demonstrator<br />

• References<br />

Page 11<br />

2013-06 R. Krebs<br />

© Siemens AG 2012. All rights reserved.<br />

IC SG SE PTI


<strong>SIGUARD</strong> ® <strong>DSA</strong><br />

Easy to Use: Continuous Procedure<br />

System State<br />

Dynamic Analysis<br />

Working point<br />

now<br />

forecasts<br />

time<br />

- Re-dispatch<br />

- tap-changer blocking<br />

- load shedding<br />

- ...<br />

Page 12<br />

Measures<br />

2013-06 R. Krebs<br />

Visualization<br />

© Siemens AG 2012. All rights reserved.<br />

IC SG SE PTI


<strong>SIGUARD</strong> ® <strong>DSA</strong><br />

Data Aggregation: Stability Indices and Grid Code Requirements<br />

Voltage Stability<br />

Small signal stability<br />

Angle<br />

Energy margin<br />

Maximum frequency deviation<br />

Frequency recovery time<br />

Frequency gradient<br />

Dynamic voltage<br />

Quasi-steady-state voltage<br />

Fault ride through<br />

Line power flow<br />

Load shedding<br />

Transformer power flow<br />

Nodal loading<br />

Results Scaling<br />

Page 13<br />

2013-06 R. Krebs<br />

0 … 1<br />

Voltage Stability Index (VSI)<br />

Small Signal Stability Index (SSSI)<br />

Angle Index (AI)<br />

Energy Margin Index (EMI)<br />

Maximum Frequency Deviation Index (MFDI)<br />

Frequency Recovery Time Index (FRTI)<br />

Frequency Gradient Index (FGI)<br />

Dynamic Voltage Index (DVI)<br />

Quasi-Steady-State Voltage Index (QSVI)<br />

Fault Ride Through Index (VRTI)<br />

Line Power flow Index (LPFI)<br />

Load Shedding Index (LSI)<br />

Transformer Power Flow Index (TPFI)<br />

Nodal Loading Index (NLI)<br />

© Siemens AG 2012. All rights reserved.<br />

IC SG SE PTI


<strong>SIGUARD</strong> ® <strong>DSA</strong><br />

Data Aggregation: Transient Generator Stability – Angle Index<br />

Angle Index (AI)<br />

AI<br />

⎡ ⎛ δ ci,max<br />

⎞⎤<br />

= min ⎢1, max<br />

⎥<br />

⎢ i=<br />

1... N ⎜<br />

G δ ⎟<br />

⎣ ⎝ c,max,<br />

adm ⎠⎥⎦<br />

80<br />

60<br />

Limit<br />

index range: 0…1<br />

Rotor angle<br />

40<br />

20<br />

0<br />

-20<br />

-40<br />

0 0.5 1 1.5 2 2.5 3<br />

Time<br />

Page 14<br />

2013-06 R. Krebs<br />

© Siemens AG 2012. All rights reserved.<br />

IC SG SE PTI


<strong>SIGUARD</strong> ® <strong>DSA</strong><br />

Data Aggregation: Ranking of Stability Indices and Grid Code Requirements<br />

Grid Code Compliance and<br />

Stability Signal Light<br />

1.0 INCOMPLIANT / INSECURE<br />

0.9<br />

0.8<br />

0.7<br />

c<br />

0.6<br />

0.5<br />

b<br />

0.4<br />

0.3<br />

0.2<br />

a<br />

0.1<br />

0.0<br />

COMPLIANT / SECURE<br />

Page 15<br />

2013-06 R. Krebs<br />

© Siemens AG 2012. All rights reserved.<br />

IC SG SE PTI


<strong>SIGUARD</strong> ® <strong>DSA</strong> - Data Aggregation<br />

Cockpit<br />

Page 16<br />

2013-06 R. Krebs<br />

© Siemens AG 2012. All rights reserved.<br />

IC SG SE PTI


<strong>SIGUARD</strong> ® <strong>DSA</strong><br />

Open Software Structure<br />

SCADA<br />

Snapshot<br />

Steady-State Network<br />

Interface<br />

Energy Trade,<br />

Renewable and<br />

Load Forecast<br />

Dynamic Network<br />

Database<br />

<strong>SIGUARD</strong> ® PDP<br />

PMU Data Stream<br />

Dynamic PMU<br />

Interface<br />

Contingencies &<br />

Measures<br />

Scenarios<br />

Automatic<br />

Contingencies &<br />

Measures<br />

Protection<br />

Database<br />

SETUP,<br />

CONFIGURATION<br />

Margins &<br />

Criteria<br />

Index Selection<br />

U<br />

Voltage<br />

Stability<br />

Margin Calculation<br />

Application Platform<br />

P<br />

Computation<br />

Engine<br />

σ<br />

5%<br />

Small Signal<br />

Stability<br />

Margin Calculation<br />

Ranking<br />

f<br />

δ<br />

fault<br />

Transient<br />

Stability<br />

Margin Calculation<br />

t<br />

PSS ® Suite<br />

Contingencies,<br />

Measures<br />

Interface<br />

Result<br />

Database<br />

SCADA<br />

<strong>SIGUARD</strong> PSA<br />

RDC<br />

SCADA<br />

<strong>SIGUARD</strong> ® PDP<br />

Monitoring<br />

Page 17<br />

2013-06 R. Krebs<br />

Visualization &<br />

Reporting<br />

© Siemens AG 2012. All rights reserved.<br />

IC SG SE PTI


<strong>SIGUARD</strong> ® <strong>DSA</strong><br />

Easy to Connect<br />

Integrated with<br />

Spectrum Power<br />

Standalone with<br />

any SCADA<br />

PSS PSS ® ® /E /E<br />

PSS ® /E<br />

PSS ® /E files<br />

Steady-state snapshopts<br />

Page 18<br />

2013-06 R. Krebs<br />

© Siemens AG 2012. All rights reserved.<br />

IC SG SE PTI


<strong>SIGUARD</strong> ® <strong>DSA</strong><br />

Typical Customized Setup<br />

Structural Elements<br />

• Main control center<br />

• Backup control center<br />

• Hot standby control center<br />

• Training center<br />

• End user network<br />

Data Security<br />

• Redundant computation servers<br />

• Redundant database servers<br />

• Different user rights<br />

Page 19<br />

2013-06 R. Krebs<br />

© Siemens AG 2012. All rights reserved.<br />

IC SG SE PTI


Content<br />

• Challenges for Electrical Energy Supply Networks<br />

• The Solution: <strong>SIGUARD</strong> ®<br />

• The Dynamic Security Assessment <strong>SIGUARD</strong> ® <strong>DSA</strong><br />

• <strong>SIGUARD</strong> ® <strong>DSA</strong> Demonstrator<br />

• References<br />

Page 20<br />

2013-06 R. Krebs<br />

© Siemens AG 2012. All rights reserved.<br />

IC SG SE PTI


<strong>SIGUARD</strong> ® <strong>DSA</strong> Online Visualization<br />

The Cockpit of the „Power System Navigator“<br />

post-contingency<br />

results distribution<br />

pre-contingency<br />

Page 22<br />

history<br />

2013-06 R. Krebs<br />

current<br />

working<br />

point<br />

forecast<br />

© Siemens AG 2012. All rights reserved.<br />

IC SG SE PTI


<strong>SIGUARD</strong> ® <strong>DSA</strong> Online Visualization<br />

The Contingencies Criticality Viewer<br />

Page 23<br />

2013-06 R. Krebs<br />

© Siemens AG 2012. All rights reserved.<br />

IC SG SE PTI


<strong>SIGUARD</strong> ® <strong>DSA</strong> Online Visualization<br />

The „Root-Cause Evaluator“<br />

Page 24<br />

2013-06 R. Krebs<br />

© Siemens AG 2012. All rights reserved.<br />

IC SG SE PTI


<strong>SIGUARD</strong> ® <strong>DSA</strong> Online Visualization<br />

The „Expert Viewer“<br />

Page 25<br />

2013-06 R. Krebs<br />

© Siemens AG 2012. All rights reserved.<br />

IC SG SE PTI


<strong>SIGUARD</strong> ® <strong>DSA</strong> Online Visualization<br />

The „Grid Viewer“<br />

• Schematic and geographical<br />

Grid representation<br />

• Contingency description<br />

• Results representation colored<br />

• Results representation by ISO-areas<br />

Page 26<br />

2013-06 R. Krebs<br />

© Siemens AG 2012. All rights reserved.<br />

IC SG SE PTI


Content<br />

• Challenges for Electrical Energy Supply Networks<br />

• The Solution: <strong>SIGUARD</strong> ®<br />

• The Dynamic Security Assessment <strong>SIGUARD</strong> ® <strong>DSA</strong><br />

• <strong>SIGUARD</strong> ® <strong>DSA</strong> Demonstrator<br />

• References<br />

Page 28<br />

2013-06 R. Krebs<br />

© Siemens AG 2012. All rights reserved.<br />

IC SG SE PTI


<strong>SIGUARD</strong> ® <strong>DSA</strong> - Dynamic Security Assessment<br />

Use Case: Customized solution for Seattle City Light (SCL), USA<br />

Challenges<br />

• NERC FAC-011-2 requires the „Secure Operation Limit (SOL)<br />

Determination“ done by ISOs/RTOs, here: WECC<br />

• WECC forwards this requirement to underlaying system operators<br />

• SCL realizes the requirement by use of <strong>SIGUARD</strong> <strong>DSA</strong><br />

<strong>SIGUARD</strong> <strong>DSA</strong> Solution<br />

• Analyzing the impact of system disturbances dynamically<br />

• Determining required SOL as defined by NERC<br />

for: Thermal, transient and voltage stability<br />

• Considering grid code constraints<br />

• Integrated control center solution with Spectrum Power<br />

Customer Benefits<br />

• Automatic information of WECC about SOL on daily basis<br />

• Reduced workload for control center personnel<br />

Status: Implementation<br />

Page 29<br />

2013-06 R. Krebs<br />

© Siemens AG 2012. All rights reserved.<br />

IC SG SE PTI


Thank you for your attention!<br />

Prof. Dr.-Ing. Rainer E. Krebs<br />

Head of Protection and Control System Studies<br />

Principal Expert for Power Technologies<br />

Phone: +49 9131 – 7 33515<br />

Fax: +49 9131 – 7 35017<br />

Mobile: +49 171 – 3026091<br />

E-mail: rainer.krebs@siemens.com<br />

Dr.-Ing. Chris-Oliver Heyde<br />

Consultant <strong>SIGUARD</strong> <strong>DSA</strong><br />

Phone: +49 9131 – 7 33875<br />

Fax: +49 9131 – 7 35017<br />

Mobile: +49 172 – 6678283<br />

E-mail: chris.heyde@siemens.com<br />

Siemens AG, IC SG SE PTI<br />

Freyeslebenstrasse 1<br />

91058 Erlangen<br />

Germany<br />

www.siemens.com/siguard<br />

Page 31<br />

2013-06 R. Krebs<br />

© Siemens AG 2012. All rights reserved.<br />

IC SG SE PTI