TENDER DOCUMENT FOR SUPPLY INSTALLATION & COMMISSIONING OF DAIRY EQUIPMENTS
Tender ID No. - Rajasthan Co-operative Dairy Federation Limited
Tender ID No. - Rajasthan Co-operative Dairy Federation Limited
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
66<br />
1) The surface of the pipe to be insulated should be properly cleaned.<br />
2) Hot bitumen should be applied uniformly @ 1.5 kg. per sq. mm. on the surface<br />
of the pipe.<br />
3) A similar layer of bitumen should be applied on the inner surface and on the<br />
edges of the insulation section.<br />
4) The sections should then be stuck to the coated pipe with joints staggered.<br />
Adjacent sections should be tightly pressed together.<br />
5) All joints should be properly sealed with bitumen.<br />
6) A thick vapour seal of hot bitumen @ 2.5 kg per sq. mm. should be applied<br />
uniformly on the outer surface of the pipe sections and allowed to dry.<br />
7) The chilled water and Glycol lines, after insulation must then be covered with<br />
22 gauge aluminium sheet with proper grooves and overlaps and secured in<br />
position with 12 mm. self tapping Parker screws.<br />
8) In case the insulation sweats or the specified/required insulation properties are<br />
not attained, the entire insulation in such region shall be redone with fresh<br />
material, entirely by the erector at his own cost.<br />
50.2 Insulation of Steam condensate & Hot water pipe lines :<br />
All the steam and hot water pipes shall be insulated with 50 mm. thick mineral<br />
wool or equivalent. The insulation shall be carried out in the following manner:<br />
1) Cleaning of surface to be insulated. Applying a coat of red oxide primer and<br />
fixing glass wool/mineral wool of suitable thickness tightly to the pipe, butting<br />
all joints to be tied with lacking wire.<br />
2) The insulation should be covered with GI wire netting.<br />
3) The steam and hot water lines, after insulation must be covered with 22 gauge<br />
aluminium sheet with proper grooves and overlaps and secured in position with<br />
12 mm. self tapping Parker screws.<br />
4) In case the insulation does not have the desired insulation properties, the entire<br />
insulation will have to be redone at the erector‟s cost to give the desired results.<br />
5) In case of condensate return piping, all the steps mentioned above shall be<br />
executed except that the thickness of insulation shall be 30 mm.<br />
50.3 Insulation of chilled water tank (if specified in the Purchase Order) :<br />
a) The surface is cleaned with the help of brushes to remove any loose particles.<br />
(Signed & sealed by the tenderer<br />
in token of acceptance of above)<br />
(RCDF)<br />