41.0 GENERAL GUIDELINES <strong>FOR</strong> ELECTRICAL <strong>INSTALLATION</strong> :<br />

41.1 a) The specifications detail the broad guide lines for erection, testing and<br />

commissioning of electrical equipment. The work shall however, at all<br />

times be carried out strictly as per the instructions of RCDF and in<br />

accordance with latest IER.<br />

b) The installation would also comprise for the supply laying and inter<br />

connecting, cables form the battery limits of the power supply to the<br />

various switchboards controls and electrical equipments.<br />

c) The cable of electric power should be of PVC armoured type approved<br />

from ISI unless otherwise specified and with sufficient cross section<br />

depending on the feeder.<br />

d) The cable for control and flexible connection should be unarmoured type<br />

with copper conductors. Wherever required, multicore copper cable should<br />

be used.<br />

e) Wherever necessary drip proof junction boxes and isolators, cable carrying<br />

trays, necessary clamps etc. shall be provided.<br />

f) Necessary isolators of appropriate sizes are to be provided near the motors<br />

as per IER. All the involved supply included within the scope of electrical<br />

installation and erection should be approved type and make and conform to<br />

ISI standard.<br />

g) Detailed electrical diagrams and cable layout should be prepared by the<br />

erector according to the specifications and the same should be approved by<br />

RCDF before the execution.<br />

41.2 Electrical installation work shall comply with all currently applicable statues,<br />

regulations and safety codes in the locality where the equipment will be<br />

installed. Nothing in this specifications shall be construed to relieve erector of<br />

his responsibility.<br />

41.3 Unless otherwise specified installation work shall comply with the<br />

requirements of latest additions of applicable Indian standards.<br />

41.4 In accordance with the specific installation instructions, as shown on<br />

manufacturer‟s drawings or as directed by Site Engineer of RCDF, the erector<br />

shall unload, erect, install wire test and put into commercial use all the<br />

electrical equipment included in the contract. Equipment shall be installed in<br />

neat workman like manner so that if is in level and plumb, properly aligned and<br />

(Signed & sealed by the tenderer<br />

in token of acceptance of above)<br />