65<br />

49.2 Piping (SS) (if mentioned in Purchase Order)<br />

The scope includes the installation and inter connection of a set of SS Pipes<br />

and fittings, including cocks, valves, Tees, flanges, unions, bends, reducers,<br />

liners and other necessary fittings SMS/IDF standards, for inter connecting all<br />

the equipment listed. Necessary pipe supports shall be also installed by the<br />

Erector.<br />

49.3 Pipe fittings at connection points<br />

All the required fittings that would be needed in the piping at all the tapping,<br />

termination, connection and intermediate points must be installed by the<br />

Erector.<br />

49.4 The erector shall prepare and submit the piping layout drawing, details of<br />

supports, details of tapping, termination interconnection etc. for approval. All<br />

the piping work shall be carried out strictly in accordance with the approved<br />

drawings/details. The respective milk flow diagram to which the piping layout<br />

correspondence must also be furnished by the erector.<br />

50.0 Insulation (if mentioned in Purchase Order)<br />

50.1 Insulation of chilled water, Glycol pipelines & ammonia suction line :<br />

All the chilled water pipelines shall be insulated as specified with 50 mm/75<br />

mm thick expanded polystyrene (50 mm for pipe 100 mm dia or less size) and<br />

all the Glycol pipeline should be installed with 75 mm thick expanded<br />

polystyrene in suitable pipe sections. The insulation shall be carried out in the<br />

following manner.<br />

1) The surface of the pipe to be insulated should be properly cleaned.<br />

2) Hot bitumen should be applied uniformly @ 1.5 kg. per sq. mm. on the surface<br />

of the pipe.<br />

3) A similar layer of bitumen should be applied on the inner surface and on the<br />

edges of the insulation section.<br />

4) The sections should then be stuck to the coated pipe with joints staggered.<br />

Adjacent sections should be tightly pressed together.<br />

5) All joints should be properly sealed with bitumen.<br />

6) A thick vapour seal of hot bitumen @ 2.5 kg per sq. mm. should be applied<br />

uniformly on the outer surface of the pipe sections and allowed to dry.<br />

(Signed & sealed by the tenderer<br />

in token of acceptance of above)<br />