42.0 Cable Installation :<br />

57<br />

42.1 Erector shall install, test and commission the suitable cables. Cables shall be<br />

laid directly buried in earth on cable racks, in built up trenches, on cable trays<br />

and supports, in conduits, and ducts or bare on walls, ceiling etc. as follows :<br />

a) Outside the building premises :<br />

The scope of installation of underground cables includes digging necessary<br />

trenches, laying of the cables in the trench, covering them with sand and<br />

bricks and then refilling the trenches. Necessary cable markers at<br />

appropriate points to indicate the path of under ground cable should also be<br />

supplied and installed by the erector.<br />

b) With in the building :<br />

Under ground cables will be laid in GI light duty class pipes of not less<br />

than 37 mm. dia.<br />

c) Cables above ground :<br />

Cables above the ground shall be fixed either on wall or in cable trays of<br />

slotted angle with necessary clamps, bolts etc. as directed by RCDF.<br />

d) The main cables inside the building should be laid in hume pipes wherever<br />

provided by RCDF. At the places where hume pipes have not provided the<br />

main cables shall be laid as per 40.1 (c).<br />

42.2 Installation and testing of proper insulated cables shall be in accordance with<br />

Indian Standard Code of Practice IS:1255.<br />

42.3 Inspection on receipt unloading, storage and handling of cables shall be in<br />

accordance with IS:1255 and other Indian Standards Code of Practice.<br />

42.4 Sharp bending and kinking of cables shall be avoided. The bending radius for<br />

various types of cables shall not be less than those specified below unless<br />

specifically approved by the Site Engineer of RCDF.<br />

Type of Cable<br />

Minimum bending radius<br />

Voltage grade Single Multi Core<br />

Core Unarmoured Armoured<br />

Paper insulated upto 11 kv 25 D* 20 D 15 D<br />

Paper insulated upto 22 kv 32 D 25 D 20 D<br />

Paper insulated upto 33 kv 38 D 32 D 25 D<br />

(Signed & sealed by the tenderer<br />

in token of acceptance of above)<br />