CONSTRUCTION OF GENERATOR CAPABILITY A CURVES

construction of generator ca atcs ca atcs capability curves

construction of generator ca atcs ca atcs capability curves

SHOW MORE
SHOW LESS
  • No tags were found...

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

DETERMINATION <strong>OF</strong> <strong>GENERATOR</strong>S<br />

POTIER REACTANCE<br />

• The obtained values (dependences) of Potier reactance<br />

x p =f(Q<br />

G ,U G )≈ f(Q G,cosφ=0 ) should be used for design of generator<br />

capability curve.<br />

• The specified rule was verified on the example of generator<br />

GTHW360 (360 MW) for regimes around the nominal (P G ≈P Gn and<br />

Q G ≈Q Gn ), )iebycomparisonof:<br />

i.e. of:<br />

• measured values (I f ,meas), and<br />

• calculated values (I f,calc ), on the basis of Potier reactances (x P ) for Q G,cosφ=0<br />

And, it is obtained<br />

I f,calc =I f,meas ±0.4%<br />

G,cosφ=0 ≈Q Gn .