United Kingdom regulations stipulate that a concentration of at least 0.2 mglitre free residual<br />

chlorine should exist at all outlets, and that water storage tanks should be cleaned at least<br />

annually with 50 mg/litre for at least four hours (Department of Transport, 1986), which is<br />

often accomplished by supplementary chlorination in the storage tanks and in distribution.<br />

Since it is often difficult to maintain cold water at less than 25 ºC on ships, supplementary<br />

chlorination is required to maintain disinfectant residual throughout the system; a level of<br />

free chlorine will contribute to the control of Legionella in such circumstances (WHO, 2004).<br />

Water flow in the distribution system should also be maintained during periods of reduced<br />

activity.<br />

Disinfection — control measures<br />

A study of 62 hotels in the Balearic Islands, Spain (Crespi et al., 1998) investigated the use of<br />

continuous hyperchlorination at 1–2 parts per million (ppm) of free residual chlorine in the<br />

cold water, and intermittent thermal treatment in the hot water. Samples positive for Legionella<br />

dropped from a level of 32.4–31.3%, after the first year of application, to 20% after three years<br />

and to 6% after five years. Another study evaluated the systematic purging of the hot and<br />

cold-water pipes in two hotels with water chlorinated at 1–1.5 ppm of free residual chlorine<br />

(Moreno et al., 1997). Negative cultures were not obtained in the two hotels until five and seven<br />

months respectively after the treatment, highlighting the recalcitrant nature of legionellae<br />

and the need for repeated and diligent disinfection.<br />

Temperature — control measures<br />

Some buildings may not be able to raise their hot-water temperature sufficiently to control<br />

Legionella growth; therefore, an on-line treatment such as chlorine or copper/silver ionization<br />

should be considered. Chapter 4 has more information on control measures relating to<br />

temperature in distribution systems.<br />

Design, operation and maintenance — control measures<br />

The control of Legionella in water distribution systems in hotels is difficult, and requires the<br />

continuous and effective maintenance of preventive measures.<br />

Hotel personnel responsible for the maintenance of hotel water systems must be educated<br />

and qualified to perform these duties. The importance of training and education has been<br />

recognized in a large number of published preventive guides. Data from the application of<br />

training programmes are very encouraging, and suggest that education may be important in<br />

preventing legionellosis in the tourist sector (Crespi & Ferra, 2002).<br />

<strong>LEGIONELLA</strong> AND THE PREVENTION OF LEGIONELLOSIS