DeltaV Product Data SheetJanuary 2013 – Page 6M-<strong>series</strong> <strong>Intrinsically</strong> <strong>Safe</strong> I/O<strong>Intrinsically</strong> <strong>Safe</strong> Discrete I/O CardsSpecifications for DeltaV I.S. I/O DINumber of channels 16IsolationLocalBus to any channelBetween channelsI. S. Channel to non-I. S. LocalBusDetection level for OnDetection level for OffOutput ImpedanceLocalBus current (12 VDC nominal) per cardSwitching hysteresis60 VACNone250 VAC> 2.1 mA< 1.2 mA100 Ω @ >6 mA (wetting current)350 mA200 µA nominalApplicable specifications NAMUR, DIN 19234Voltage applied to sensor 7.0 to 9.0 V from 1 kΩ ± 10%Line fault detectionshort circuitopen circuit< 100Ω> 50 kΩMaximum input frequency in pulse counting mode 20 HzMinimum pulse width detectedOptional loop disconnect45 msNo