DeltaV Product Data SheetJanuary 2013 – Page 3M-<strong>series</strong> <strong>Intrinsically</strong> <strong>Safe</strong> I/OHardware SpecificationsCommon Environmental Specifications for all I/O InterfacesCategorySpecificationsOperating temperatureStorage temperatureRelative humidityAirborne contaminants-40 to 70 °C(-40 to 158 °F)-40 to 85 °C(-40 to 185 °F)5 to 95% , non-condensingISA-S71.04-1985 Airborne Contaminants Class G3Conformal coatingProtection rating IP 20, NEMA 12Hazardous area/location*I/O InterfacesShockField circuitsVibrationCENELEC Zone 2 IIC T4 hazardous areaClass I, Div 2, Groups A. B, C, D T4 hazardous locations.CENELEC Zone 0, IIC hazardous area or Class 1, Div 1, GroupsA,B,C,D hazardous locations10 g ½-sine wave for 11 ms1 mm peak-to-peak from5 to 16 Hz;0.5 g from16 to 150 HzH 10.7 cm (4.2 in.)DimensionsW 4.1 cm (1.6 in.)Depth 10.5 cm (4.1 in.)*Refer to Zone 0 installation instructions (12P1990) for information on installing in hazardous areas.