SDECircular Smoke and Fire Damper20/SDE/0000/1107/EN• Construction based on EN1366-2-certified firedamper FDE (E120, ES90, EIS15).• SITAC (Sweden) approval as E120 ‘Brandgasspjäll’.• Possibility of use as an EI60/EI120 damper withadditional duct insulation (National Building Code,Sweden).• Installation in separating concrete or masonry wallsand ceilings and lightweight plasterboard walls.• Installation in circular ducts with diameter 100 to500 mm.• Manufactured in accordance with the ISO 9001quality standard.• External quality control management by VTT, theTechnical Research Centre of Finland.• Damper casing complying with the tightnessrequirements for Class C, EN 1751.• Inlet and outlet spigots with integral rubber gaskets.• Suitability for use in ducts with a maximum pressureof 3300 Pa.<strong>Product</strong> models and Accessories• Damper is equipped with electric spring-returnactuator.• Actuator has a visual position indicator.• Damper Power-Off position is closed.MATERIALPARTMATERIALCasingGalvanised steelBladeGalvanised steelBlade gasketsCeramic clothInstallation frameGalvanised steelClosing springsStainless steelDuct gaskets1C-polyurethane hybridSDE - Circular Smoke and Fire Damper141


DIMENSIONSWhen the damper is installed on a concrete ormasonry wall or ceiling, the size of the installationL620/SDE/0000/1107/ENhole is ØD + 50 mm.Ø DL3L1L2L3NS ØD L L1 L2 L3100 99 145 105 40 180125 124 145 105 40 205160 159 145 105 40 240200 199 145 105 40 280250 249 145 105 40 330315 314 145 105 40 395400 399 245 135 110 550500 499 245 135 110 630ACCESSORIES AND PRODUCT MODELSACCESSORY CODE DESCRIPTIONMesh on one sideN1Mesh on both sidesN2Microswitch MS Closed position indication, enclosure class IP 65ActuatorsBelimo BLF24 HI, operating voltage AC/DC 24 V(contains a microswitch), B7Belimo BLF230 HI, operating voltage AC 230 V(contains a microswitch), B8SDE - Circular Smoke and Fire Damper142


FunctionThe SDE is a motorised circular smoke damper thatprevents fire and smoke from spreading in ventilationducts. If the power in the motorised actuatoris switched off by the system, the blade closesautomatically (Fail-safe Closed).The smoke damper is made of fireproof materials,with a non-combustible ceramic blade gasket. Oncethe damper has closed, the blade and sealing closethe duct tightly, effectively preventing the spreading offire and smoke.InstallationDetailed installation instructions, as well as aninstaller’s installation certificate form, are suppliedwith each product. See also the section ‘Documents /Installation Instructions’.Installation on concrete or masonry walls120/SDE/0000/1107/ENThe SDE smoke damper shall be connected to theMSH control and testing system. The MSH systemenables the use of smoke detectors in ductworkor room spaces. The SDE smoke damper may beconnected to common building automation systemsalso.1 Screw and fixing plugØD1<strong>Product</strong> size + about 50 mmWhen the smoke damper is installed on a concrete ormasonry wall or ceiling between fire compartments,there are no restrictions on the damper position or airflow direction.An opening always is left in the separating element forthe smoke damper, and the product subsequently isgrouted into this. The size of the installation opening isD+50 mm.To make installation easier, all products come with aninstallation flange, which is used to attach the smokedamper to the concrete surface with screws beforegrouting.The damper and actuator shall be protected duringinstallation with, e.g., a plastic cover.The damper shall be cleaned after installation.The correct operation of the smoke damper must beensured before and after grouting.SDE - Circular Smoke and Fire Damper143


Installation on lightweight plasterboard wallsElectric actuator wiring diagram~+AC 24 VDC 24 V!Connect viasafety isolatingtransformer!20/SDE/0000/1107/ENS1 S2 S3S4 S5 S61 2< 5°< 80° BLF24-HI51432N L1230 VACS1 S2 S3S4 S5 S61 2ØD1 <strong>Product</strong> size + about 5 mm1 Fireproof sealing mass2 Steel frame3 Plasterboard4 Mineral wool5 Screw< 5°< 80° BLF230-HIWhen the smoke damper is installed on a lightweightplasterboard wall between fire compartments, a smallopening for the smoke damper must be left in theplasterboard walls.There are no restrictions on the damper position or airflow direction.An installation frame shall be installed around theopening.To make installation easier, the smoke damper comeswith an installation flange, which is used to fasten thedamper to, e.g., the steel frame of the panel wall.The space between the smoke damper and theplasterboard wall is grouted with fire preventionmastic. During installation, the smoke damper andactuator shall be protected with, e.g., a plastic cover.The correct operation of the smoke damper shall beensured after installation.Insulation to comply with thermal insulationcriterion (I)The SDE unit may be applied as an EI30...120 damperthrough the use of additional ductwork fire insulationin accordance with the appropriate national buildingcode.SDE - Circular Smoke and Fire Damper144


ServicingNo regular maintenance is required for the product.Regular testing with the MSH control and testingsystem is recommended.Upon failure during testing of the smoke evacuationdamper, maintenance service shall be ordered from anauthorised <strong>Halton</strong> representative to ensure appropriateoperation of the product.Suggested specificationsCircular smoke damper with electric spring-returnactuator and position indicator (Construction basedon certified fire damper FDE; E120; EN 1366-2). ThePower-Off damper position shall be closed.The casing and blades of the smoke and fire dampershall be made of galvanised steel.The closing blade shall be equipped with a noncombustibleceramic blade gasket.The smoke and fire damper casing shall have inlet andoutlet spigots with integral rubber gaskets and complywith the tightness requirements for Class C, EN 1751.The smoke and fire damper shall be approved bothfor installation in separating concrete or masonrywalls and ceilings and for installation on lightweightplasterboard walls.20/SDE/0000/1107/EN<strong>Product</strong> codeSDE-DD = Diameter of duct connection100, 125, 160, 200, 250, 315, 400, 500Specifics and accessoriesRE = Release typeB7 BLF24 HI (Damper closed when power off, no fuse)B8 BLF230 HI (Damper closed when power off, no fuse)MA = MaterialCS Galvanised steelAC = AccessoriesN1 Safety mesh, 1 side, installed in actuator sideN2 Safety mesh, 2 sidesCode exampleSDE D-100, B1=MA, MA=CS, AC=N1SDE - Circular Smoke and Fire Damper145