INSTRUCTION MANUALENGLISHChecking the chargeIf the system is properly charged superheating at the gaseous line should be 7- 8 °C , and subcooling at theliquid line access valve should be 4 – 6 ° C.To check whether or not the values indicated have been reached, under normal operating conditions at fullload, proceed as follows:superheatingallow the unit to function in a normal manner checking that high and low pressure readings in the relevantgauges are constant.Read the suction temperature just downstream the thermostatic valve’s bulb. The difference between thistemperature and saturation temperature read on the low pressure gauge must be within the described limits.subcoolingRead the temperature of the liquid in outlet from the condenser. The difference between the saturationtemperature seen on the high pressure gauge and that measured, must be within the described limits.17