c) VAV fan pressure reset strategyIf direct digital control of individual zone boxes reports to central control panel, then a static pressurereset strategy must be included in the <strong>controls</strong>. Reset must to be based on the zone requiring thehighest supply pressure.Code SectionsIECCASHRAE2009: 503.4.2 2007: 6.5.3.2.32012: 403.4.2.2 2010: 6.5.3.2.3Humidity ControlWhere humidifiers or dehumidifiers are provided, the system must control their operation to preventsimultaneous humidification <strong>and</strong> dehumidification <strong>and</strong> to shut off the components when they are not required.Plan ReviewSuggested Compliance Check(s):• If the system has a humidifier with a preheat jacket, then confirm on the mechanical floorplan that a valve is shown on the hot water supply line feeding the preheat jacket.• Verify that control of the preheat valve is described as a note oneither the mechanical schedule or mechanical plans.*• Verify that the control sequence specifies a means to preventsimultaneous humidification <strong>and</strong> dehumidification.** If the building is equipped with a building automation system (BAS), then these capabilities will most likely beprovided by the BAS. The BAS specifications or manual should indicate that the required capabilities are present.<strong>Building</strong> InspectionSuggested Compliance Check(s):• Where applicable, verify that an automatic valve has been installed on humidifier preheat jackets.• Verify that simultaneous humidification <strong>and</strong> dehumidification has been prevented inaccordance with the approach defined in the approved mechanical design.Additional Detail:a) Humidifier shutoffHumidifiers with preheating jackets mounted in the airstream shall be provided with an automatic valve toshut off preheat when humidification is not required.32 Control Requirements <strong>for</strong> Complex Systems

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!