4) The supply of outside air is reduced to the design minimumwhen one of the following conditions applies:• Outside air temperature exceeds:• 75°F in climate zones 1B, 2B, 3B, 3C, 4B, 4C, 5B, 5C, 6B, 7, or 8• 70°F in climate zones 5A, 6A, or 7A• 65°F in any other climate zone• The climate specific shut off condition is reached, as determined by anotherapproved approach from the code sections referenced in section c below.5) The economizer will reduce outside air to the minimum requirement when outsideair no longer provides cooling or when the system is in a heating mode.* If the building is equipped with a building automation system (BAS), then these capabilities will most likely beprovided by the BAS. The BAS specifications or manual should indicate that the required capabilities are present.Figure 19: Economizer control strategy shown in a control sequenceModulating Economizer• Controls position of a damper based on the Control State, Outside Air Temperature (OAT), <strong>and</strong> CoolingDem<strong>and</strong>.• Economizer available if:○○○○Cooling mode <strong>and</strong> fan onEcon. low limit temp SP < OAT < Econ. temp SP• When available, economizer:○○Locks out other cooling when Cooling Dem<strong>and</strong> < 25%○○Modulates from minimum to maximum position as Cooling Dem<strong>and</strong> increases from 0% to 25%<strong>Building</strong> InspectionSuggested Compliance Check(s):• Review the mechanical plans <strong>and</strong> verify that economizers have been providedon air h<strong>and</strong>lers as shown in the approved mechanical design.• Confirm that economizer operation is controlled as specified in the approvedmechanical design. This will often mean confirming that a building automationsystem has been installed <strong>and</strong> connected to the economizer.Control Requirements <strong>for</strong> Complex Systems 27

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!