hVac controls guide for Plans examiners and Building inspectors
hVac controls guide for Plans examiners and Building inspectors hVac controls guide for Plans examiners and Building inspectors
c) Demand control ventilationA control strategy that varies the minimum ventilation outdoor air based on occupancy is required forlarge, densely occupied spaces. This usually applies to spaces 500 square feet and larger that havean occupant load greater than or equal to 40 people per 1,000 square feet (IECC 2012 expanded theapplicability by reducing the threshold occupant load to 25 people per 1000 square feet). Typically,ventilation is controlled by varying the outdoor air intake based on the measured level of carbon dioxidewithin a space.Code SectionsIECCASHRAE2009: 503.2.5.1 2007: 6.4.3.92012: 403.2.5.1 2010: 6.4.3.9d) Heat recovery ventilation bypassIf a heat recovery ventilator (HRV) is installed, this HRV must not inhibit the operation of the economizer. Thiscan be accomplished through controls which allow the HRV to be bypassed when the economizer is working.Code SectionsIECCASHRAE2009: 503.2.6 2007: 6.5.6.12012: 403.2.6 2010: 6.5.6.1Heat Pump Supplemental HeaterIf the building has heat pumps with supplemental electric heaters, those supplemental heaters should notbe engaged until the heat pump’s heating capacity is exceeded. ASHRAE 90.1 exempts heat pumps that areregulated under the National Appliance Energy Conservation Act (those with a cooling capacity less than65,000 Btu/h) from this requirement.Plan ReviewSuggested Compliance Check(s):• Verify that the mechanical schedule or control sequence specifies that supplementalresistance heating cannot operate when the heat pump can meet the heating load. This maybe accomplished by specifying a multi-stage electronic thermostat programmed to initiatethe supplemental heater when the heat pump cannot meet the setpoint (figure 15).Figure 15: Sample heat pump control sequence showing auxiliary heat engaged as second stageMode Call for Action Signal to Heat Pump Delivered ActionHeat None H Reversing valve in heat positionStage 1 heat H, H1 Heat using compressorStage 2 heat H, H1, H2 Heat using compressor and auxiliary heater20 Control Requirements for All Systems
Building InspectionSuggested Compliance Check(s):• Check that the type of thermostat or building automation system specifiedin the approved mechanical submittal is installed and operating.Additional Detail:Code SectionsIECCASHRAE2009: 503.2.4.1.1 2007: 6.4.3.52012: 403.2.4.1.1 2010: 6.4.3.5Control Requirements for All Systems 21
- Page 2 and 3: ContentsIntroduction ..............
- Page 5 and 6: Commercial buildingControl requirem
- Page 7 and 8: Prescriptive requirementsfor Comple
- Page 9 and 10: Code Requirements andCompliance Che
- Page 11 and 12: Control Requirements for All System
- Page 13 and 14: Figure 4: Sample control sequence s
- Page 15 and 16: d) Automatic setback and shutdown c
- Page 17 and 18: Figure 9: VSD installed on a supply
- Page 19: Figure 13: Motorized damperFigure 1
- Page 23 and 24: 4) The supply of outside air is red
- Page 25 and 26: ) Control strategyEconomizers must
- Page 27 and 28: 4) The supply of outside air is red
- Page 29 and 30: must be positioned well down the du
- Page 31 and 32: Figure 23: BAS screen shot indicati
- Page 33 and 34: Code SectionsIECCASHRAE2009: NA 200
- Page 35 and 36: Figure 27: Illustrated control sequ
- Page 37 and 38: Code SectionsIECCASHRAE2009: 503.4.
- Page 39: Building InspectionSuggested Compli
- Page 42 and 43: Building InspectionSuggested Compli
- Page 44 and 45: Figure 38: Sample control sequence
- Page 46: Building Technology ProgramThe U.S.
c) Dem<strong>and</strong> control ventilationA control strategy that varies the minimum ventilation outdoor air based on occupancy is required <strong>for</strong>large, densely occupied spaces. This usually applies to spaces 500 square feet <strong>and</strong> larger that havean occupant load greater than or equal to 40 people per 1,000 square feet (IECC 2012 exp<strong>and</strong>ed theapplicability by reducing the threshold occupant load to 25 people per 1000 square feet). Typically,ventilation is controlled by varying the outdoor air intake based on the measured level of carbon dioxidewithin a space.Code SectionsIECCASHRAE2009: 503.2.5.1 2007: 6.4.3.92012: 403.2.5.1 2010: 6.4.3.9d) Heat recovery ventilation bypassIf a heat recovery ventilator (HRV) is installed, this HRV must not inhibit the operation of the economizer. Thiscan be accomplished through <strong>controls</strong> which allow the HRV to be bypassed when the economizer is working.Code SectionsIECCASHRAE2009: 503.2.6 2007: 6.5.6.12012: 403.2.6 2010: 6.5.6.1Heat Pump Supplemental HeaterIf the building has heat pumps with supplemental electric heaters, those supplemental heaters should notbe engaged until the heat pump’s heating capacity is exceeded. ASHRAE 90.1 exempts heat pumps that areregulated under the National Appliance Energy Conservation Act (those with a cooling capacity less than65,000 Btu/h) from this requirement.Plan ReviewSuggested Compliance Check(s):• Verify that the mechanical schedule or control sequence specifies that supplementalresistance heating cannot operate when the heat pump can meet the heating load. This maybe accomplished by specifying a multi-stage electronic thermostat programmed to initiatethe supplemental heater when the heat pump cannot meet the setpoint (figure 15).Figure 15: Sample heat pump control sequence showing auxiliary heat engaged as second stageMode Call <strong>for</strong> Action Signal to Heat Pump Delivered ActionHeat None H Reversing valve in heat positionStage 1 heat H, H1 Heat using compressorStage 2 heat H, H1, H2 Heat using compressor <strong>and</strong> auxiliary heater20 Control Requirements <strong>for</strong> All Systems