Figure 13: Motorized damperFigure 14: Top view of CO 2sensor (coin <strong>for</strong> scale)Additional Detail:a) DampersOutdoor air supply <strong>and</strong> exhaust/relief ducts shall have motorized dampers that automatically close whenthe spaces that they serve are not occupied. <strong>Building</strong>s less than three stories tall or in climate zones 1through 3 may use gravity dampers.Code SectionsIECCASHRAE2009: 503.2.4.4 2007: 6.4.3.4.3,6.4.3.4.1, 6.4.3.4.22012: 403.2.4.4 2010: 6.4.3.4.2, 6.4.3.4.1b) Ventilation fan <strong>controls</strong>Fans with motors greater or equal to three-quarter horsepower, must have <strong>controls</strong> that can shut off fanswhen not required. This control may be an occupancy sensor, timer, or other device.Code SectionsIECCASHRAE2009: NA 2007: 6.4.3.4.52012: NA 2010: 6.4.3.4.4Control Requirements <strong>for</strong> All Systems 19