8.3 Introduction of Step <strong>Instruction</strong>s: STP, FROM, TO and STPEND● STP Sx : S0≦Sx≦S7 (Displayed in WinProladder)orSTP Sx:S0≦Sx≦S7 (Displayed in FP-07)This instruction is the initial step instruction from where the step control of each machine process can be derived. Up to 8initial steps can be used in the FBs series, i.e. a PLC can make up to 8 process controls simultaneously. Each stepprocess can operate independently or generate results for the reference of other processes.【Example 1】 Go to the initial step S0 after each start (ON)WinProladderFP-07M1924STP S0M1924TO S0STP S0ORGTOSTPM1924S0S0【Example 2】 Each time the device is start to run or the manual button is pressed or the device is malfunction, then thedevice automatically enters the initial step S0 to standby.WinProladderFP-07M1924STP S0X0 M0M1924X0M0STP S0TO S0StandbyProcessProgramORG M1924OR X0OR M0TO S0STP S0Standby process program【Description】X0: Manual Button, M0: Abnormal Contact.8-5