IntroductionGeneral descriptionEach unit is completely assembled, wired, evacuated, charged, tested, ready for installation. The maincomponents are air-cooled condensers with integral sub-cooler sections, accessible semi-hermetic single-screwcompressors, shell-and-tube evaporators, shell-and-tube water heat recovery condensers (optional), oilseparators, complete refrigerant piping and electrical panel (including control and power sections). Liquid linecomponents are shut-off valves, charging valves, filter-dryers, sight -glass/moisture indicators, electronic expansionvalves, liquid receivers (only with total heat recovery option). Other features are compressor heaters, evaporatorheater for low ambient water freeze protection, automatic pump-down during circuit shutdown and fully integratedmicroprocessor control system.The chiller uses R407C refrigerant and operates at positive pressures.Purpose of the manualThe manual allows the installer and the operator to perform correctly all the required operations for unit installationand maintenance without any damages to the chiller or to qualified personnel.Nomenclature<strong>McPower</strong> SE 276 . 2 ST 407<strong>McPower</strong>Air cooled screw chillerSEXEStandard EfficiencyHigh Efficiency228÷478 Unit size23 N° of compressorsSTCNLNXNXXNStandard versionWith Sound Proof CabinetLow noise versionExtra low noise versionSuper quiet407 Refrigerant HFC 407C508 C – <strong>06</strong>/04 A – pag. 3/44


Figure 8 - Typical heat recovery piping connection schemeEvaporator/Heat Recovery condenser Freeze ProtectionAll evaporators are equipped with electric heater thermostatically controlled that provide freeze protection downto -28°C. However, this should not be the only method of freeze protection. Unless the evaporator and heatrecovery condensers are flushed and drained as is described below in note 4, two or more of the remaining threerecommendations must be followed as part of the system design:1. Continuous circulation of water through the piping and the heat exchanger.2. Filling of glycol solution in the chilled water circuit.3. Additional insulation and heating of the exposed piping.4. Draining and flushing the chiller vessel with air during winter season.It is the responsibility of the installing contractor and/or on-site maintenance personnel to insure that this additionalprotection is provided. Routine checks should be made to insure adequate freeze protection is maintained.Failure to do so may result in damage to unit components. Freeze damage is not considered a warranty failure.Flow SwitchA water flow switch must be mounted in either the entering or leaving water line to insure an adequate water flowthrough the evaporator before starting the unit. This will safeguard against slugging the compressors on start -up. It<strong>McPower</strong> serves to shut down the unit in the event that water flow is interrupted to protect against evaporatorfreeze-up. Whenever the unit is equipped with the heat recovery condensers a water flow switch must be mountedin either the entering or leaving water line to insure an adequate water flow before switching the unit in “Heatrecovery mode”. It prevents against the unit shut -down for high condensing pressure.A flow switch is available from <strong>McQuay</strong> and it is a "paddle" type switch and adaptable to any pipe size from 5"(127mm) to 8" (203mm) nominal.Certain minimum flow rates are required to close the switch and are listed in Table 1.Flow direction marked on switchNPT flow switch connectionTee508 C – <strong>06</strong>/04 A – pag. 8/44


NOMINAL PIPESIZE INCHES (MM)5 (127) 3.76 (152) 5.08 (203) 8.8Table 1MINIMUM REQUIRED FLOWTO ACTIVATE SWITCH –LITERS PER SECONDSTable 1 – Operating limits – <strong>McPower</strong> SEUnit version ST LN XN XXNMax ambient temperature (1) °C 42 38 38 35Min ambient temperature °C +10 (2) +10 (2) +10 (2) -18 (3)Max entering evaporator water temperature °C +15 +15 +15 +15Min leaving evap. water temp.(without glycol) °C +4 +4 +4 +4Min leaving evap. water temp.(with glycol) °C -8 -8 -8 -8Max evaporator DT °C 6 6 6 6Min evaporator DT °C 4 4 4 4Note: (1) Max ambient temperature are referred to units working at full load. With higher temperatures the chillers willunloading(2) When air temperature is lower then +10°C you need the fan speed control device. It allows the unit working with airtemperature down to –18°C.(3) Fan speed control device is standard furnished on the XXN units.Table 2 – Operating limits – <strong>McPower</strong> XEUnit version ST LN XN XXNMax ambient temperature °C 46 42 42 40Min ambient temperature °C +10 (2) +10 (2) +10 (2) -18 (3)Max entering evaporator water temperature °C +15 +15 +15 +15Min leaving evap. water temp.(without glycol) °C +4 +4 +4 +4Min leaving evap. water temp.(with glycol) °C -8 -8 -8 -8Max evaporator DT °C 6 6 6 6Min evaporator DT °C 4 4 4 4Note: (1) Max ambient temperature are referred to units working at full load. With higher temperatures the chillers willunloading(2) When air temperature is lower then +10°C you need the fan speed control device. It allows the unit working with airtemperature down to –18°C.(3) Fan speed control device is standard furnished on the XXN units.508 C – <strong>06</strong>/04 A – pag. 9/44


Physical data <strong>McPower</strong> SE ST and SE CN with HFC 407C<strong>McPower</strong> unit size 228.2 255.2 276.2 300.2 320.2 340.3Cooling capacity (1) kW 767,4 849,5 916,1 996,2 1<strong>06</strong>0,1 <strong>11</strong>24,3Power input (1) kW 317,0 348,2 376,9 412,4 444,8 471,2COP 2,42 2,44 2,43 2,42 2,38 2,39<strong>McQuay</strong> singlescrew compressors N° 2 2 2 2 2 3Refrigerant circuits N° 2 2 2 2 2 3Oil charge l 28 28 28 28 28 28Min % of capacity reduction % 12,5 12,5 12,5 12,5 12,5 12,5Condenser fansN° of fans / Nominal power fan kW 12/2 13/2 14/2 15/2 16/2 18/2Fan speed rpm 860 860 860 860 860 860Diameter mm 800 800 800 800 800 800Total air flow m 3 /s 66,3 71,9 77,4 82,9 88,4 99,5EvaporatorEvaporator / Water volume N°/l 1 / 278 1 / 271 1 / 271 1 / 256 1 / 256 1 / 263Max operating pressure bar 10,5 10,5 10,5 10,5 10,5 10,5Water connections diameter mm 219 219 219 219 219 219Condenser coilCoil typeLanced fins – Internally spiral wound tubesWeight and dimensionStandard unit shipping weight for unit ST kg 5165 5425 5555 5795 5905 7990Standard unit operating weight for unit ST kg 5430 5710 5840 6070 6180 8270Standard unit shipping weight for unit CN kg 5405 5665 5795 6035 6145 8350Standard unit operating weight for unit CN kg 5670 5950 6080 6310 6420 8630Unit length mm 6210 7<strong>11</strong>0 7<strong>11</strong>0 8010 8010 9170Unit width mm 2230 2230 2230 2230 2230 2230Unit height mm 2520 2520 2520 2520 2520 2520<strong>McPower</strong> unit size 374.3 395.3 418.3 445.3 464.3 478.3Cooling capacity (1) kW 1246,8 1314,1 1384,7 1472,1 1536,9 1601,6Power input (1) kW 509,1 537,9 564,5 604,3 636,8 669,4COP 2,45 2,44 2,45 2,44 2,41 2,39<strong>McQuay</strong> singlescrew compressors N° 3 3 3 3 3 3Refrigerant circuits N° 3 3 3 3 3 3Oil charge l 28 28 28 28 28 28Min % of capacity reduction % 12,5 12,5 12,5 12,5 12,5 12,5Condenser fansN° of fans / Nominal power fan kW 19/2 20/2 22/2 22/2 23/2 24/2Fan speed rpm 860 860 860 860 860 860Diameter mm 800 800 800 800 800 800Total air flow m 3 /s 105 <strong>11</strong>0,6 124 121,6 127,2 132,7EvaporatorEvaporator / Water volume N°/l 1 / 432 1 / 432 1 / 432 1 / 419 1 / 419 1 / 419Max operating pressure bar 10,5 10,5 10,5 10,5 10,5 10,5Water connections diameter mm 273 273 273 273 273 273Condenser coilCoil typeLanced fins – Internally spiral wound tubesWeight and dimensionStandard unit shipping weight for unit ST kg 8305 8435 8890 8905 9155 9265Standard unit operating weight for unit ST kg 8775 8905 9360 9350 9600 9710Standard unit shipping weight for unit CN kg 8665 8795 9250 9265 9515 9625Standard unit operating weight for unit CN kg 9135 9265 9720 9710 9960 10070Unit length mm 10070 10070 10970 10970 <strong>11</strong>870 <strong>11</strong>870Unit width mm 2230 2230 2230 2230 2230 2230Unit height mm 2520 2520 2520 2520 2520 2520Note: (1) Nominal cooling capacity and power input are based on: 12 / 7 °C entering / leaving evaporator watertemperature; 35°C ambient temperature. The power input is for compressor only.508 C – <strong>06</strong>/04 A – pag. 10/44


Electrical data <strong>McPower</strong> SE ST and SE CN with HFC 407C<strong>McPower</strong> unit size 228.2 255.2 276.2 300.2 320.2 340.3Standard voltage (1)400 V – 3f – 50 HzNominal unit current (2) A 565 621 673 729 780 841Max compressor current (3) A 6<strong>06</strong> 660 7<strong>11</strong> 773 832 902Fans current A 48 52 56 60 64 72Max unit current (3) A 654 712 767 833 896 974Max unit inrush current (4) A 867 1<strong>06</strong>7 1088 <strong>11</strong><strong>11</strong> <strong>11</strong>33 1277Max unit current for wires sizing (5) A 494 546 598 753 908 741<strong>McPower</strong> unit size 374.3 395.3 418.3 445.3 464.3 478.3Standard voltage (1)400 V – 3f – 50 HzNominal unit current (2) A 907 959 1012 1070 <strong>11</strong>22 <strong>11</strong>73Max compressor current (3) A 966 1018 1<strong>06</strong>4 <strong>11</strong>34 <strong>11</strong>93 1251Fans current A 76 80 88 88 92 96Max unit current (3) A 1042 1098 <strong>11</strong>52 1222 1285 1347Max unit inrush current (4) A 1312 1341 1373 1402 1430 1459Max unit current for wires sizing (5) A 793 845 901 1052 1207 1362Notes: (1) Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.(2) Nominal current are based on: 12/7 °C entering/leaving evaporator water temperature and 35°C ambient temp.(3) Maximum current are based on: 14/9 °C entering/leaving evaporator water temperature and 44°C ambient temp.(4) Inrush current of biggest compressor + 75 % of nominal absorbed current of the other compressor + fans current.(5) Compressor FLA + fans current.508 C – <strong>06</strong>/04 A – pag. <strong>11</strong>/44


Electrical data <strong>McPower</strong> SE LN and SE XN with HFC 407CGrandezza unità <strong>McPower</strong> 228.2 255.2 276.2 300.2 320.2 340.3Standard voltage (1)400 V – 3f – 50 HzNominal unit current (2) A 599 654 705 766 823 890Max compressor current (3) A 620 675 726 792 852 921Fans current A 28 30 32 34 37 41Max unit current (3) A 648 705 758 826 889 962Max unit inrush current (4) A 869 1<strong>06</strong>8 1088 <strong>11</strong>13 <strong>11</strong>35 1281Max unit current for wires sizing (5) A 474 524 574 727 881 71032Grandezza unità <strong>McPower</strong> 374.3 395.3 418.3 445.3 464.3 478.3Standard voltage (1)400 V – 3f – 50 HzNominal unit current (2) A 957 1008 1053 <strong>11</strong>25 <strong>11</strong>82 1238Max compressor current (3) A 989 1040 1081 <strong>11</strong>61 1222 1282Fans current A 44 46 51 51 53 55Max unit current (3) A 1033 1086 <strong>11</strong>32 1212 1275 1337Max unit inrush current (4) A 1316 1343 1368 1404 1434 1464Max unit current for wires sizing (5) A 761 8<strong>11</strong> 864 1015 <strong>11</strong>68 1321Notes: (1) Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.(2) Nominal current are based on: 12/7 °C entering/leaving evaporator water temperature and 35°C ambient temp.(3) Maximum current are based on: 14/9 °C entering/leaving evaporator water temperature and 44°C ambient temp.(4) Inrush current of biggest compressor + 75 % of nominal absorbed current of the other compressor + fans current.(5) Compressor FLA + fans current.508 C – <strong>06</strong>/04 A – pag. 13/44


Physical data <strong>McPower</strong> SE XXN HFC 407C<strong>McPower</strong> unit size 228.2 255.2 276.2 300.2 320.2 340.3Cooling capacity (1) kW 687,9 759,9 820,5 889,5 946,6 10<strong>11</strong>,7Power input (1) kW 379,6 414,1 445,7 488,7 528,1 564,5COP 1,81 1,84 1,84 1,82 1,79 1,79<strong>McQuay</strong> singlescrew compressors N° 2 2 2 2 2 3Refrigerant circuits N° 2 2 2 2 2 3Oil charge l 28 28 28 28 28 28Min % of capacity reduction % 12,5 12,5 12,5 12,5 12,5 12,5Condenser fansN° of fans / Nominal power fan kW 12/0,77 13/0,77 14/0,77 15/0,77 16/0,77 18/0,77Fan speed rpm 500 500 500 500 500 500Diameter mm 800 800 800 800 800 800Total air flow m 3 /s 41,1 44,5 47,9 51,4 54,8 61,7EvaporatorEvaporator / Water volume N°/l 1 / 278 1 / 271 1 / 271 1 / 256 1 / 256 1 / 263Max operating pressure bar 10,5 10,5 10,5 10,5 10,5 10,5Water connections diameter mm 219 219 219 219 219 219Condenser coilCoil typeLanced fins – Internally spiral wound tubesWeight and dimensionStandard unit shipping weight kg 5405 5665 5795 6035 6145 8350Standard unit operating weight kg 5670 5950 6080 6310 6420 8630Unit length mm 6210 7<strong>11</strong>0 7<strong>11</strong>0 8010 8010 9170Unit width mm 2230 2230 2230 2230 2230 2230Unit height mm 2520 2520 2520 2520 2520 2520<strong>McPower</strong> unit size 374.3 395.3 418.3 445.3 464.3 478.3Cooling capacity (1) kW <strong>11</strong>13,95 <strong>11</strong>75 1250,7 1312,9 1370,6 1428,3Power input (1) kW 6<strong>06</strong>,5 638,4 659,4 715,4 755,1 794,7COP 1,84 1,84 1,9 1,84 1,82 1,8<strong>McQuay</strong> singlescrew compressors N° 3 3 3 3 3 3Refrigerant circuits N° 3 3 3 3 3 3Oil charge l 28 28 28 28 28 28Min % of capacity reduction % 12,5 12,5 12,5 12,5 12,5 12,5Condenser fansN° of fans / Nominal power fan kW 19/0,77 20/0,77 22/0,77 22/0,77 23/0,77 24/0,77Fan speed rpm 500 500 500 500 500 500Diameter mm 800 800 800 800 800 800Total air flow m 3 /s 65,1 68,5 77,4 75,4 78,8 82,2EvaporatorEvaporator / Water volume N°/l 1 / 432 1 / 432 1 / 432 1 / 419 1 / 419 1 / 419Max operating pressure bar 10,5 10,5 10,5 10,5 10,5 10,5Water connections diameter mm 273 273 273 273 273 273Condenser coilCoil typeLanced fins – Internally spiral wound tubesWeight and dimensionStandard unit shipping weight kg 8665 8795 9250 9265 9515 9625Standard unit operating weight kg 9135 9265 9720 9710 9960 10070Unit length mm 10070 10070 10970 10970 <strong>11</strong>870 <strong>11</strong>870Unit width mm 2230 2230 2230 2230 2230 2230Unit height mm 2520 2520 2520 2520 2520 2520Note: (1) Nominal cooling capacity and power input are based on: 12 / 7 °C entering / leaving evaporator water temperature;35°C ambient temperature. The power input is for compressor only..508 C – <strong>06</strong>/04 A – pag. 14/44


Electrical data <strong>McPower</strong> SE XXN HFC 407CGrandezza unità <strong>McPower</strong> 228.2 255.2 276.2 300.2 320.2 340.3Standard voltage (1)400 V – 3f – 50 HzNominal unit current (2) A 632 688 738 805 866 940Max compressor current (3) A 628 685 736 803 865 933Fans current A 18 20 21 23 24 27Max unit current (3) A 646 705 757 826 889 960Max unit inrush current (4) A 880 1079 1099 <strong>11</strong>25 <strong>11</strong>49 1302Max unit current for wires sizing (5) A 464 514 563 716 868 696Grandezza unità <strong>McPower</strong> 374.3 395.3 418.3 445.3 464.3 478.3Standard voltage (1)400 V – 3f – 50 HzNominal unit current (2) A 1008 1059 1095 <strong>11</strong>80 1242 1304Max compressor current (3) A 1003 1055 1090 <strong>11</strong>78 1240 1302Fans current A 29 30 33 33 35 36Max unit current (3) A 1032 1085 <strong>11</strong>23 12<strong>11</strong> 1275 1338Max unit inrush current (4) A 1337 1364 1385 1427 1460 1492Max unit current for wires sizing (5) A 746 795 846 997 <strong>11</strong>50 1302Notes: (1) Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.(2) Nominal current are based on: 12/7 °C entering/leaving evaporator water temperature and 35°C ambient temp.(3) Maximum current are based on: 14/9 °C entering/leaving evaporator water temperature and 44°C ambient temp.(4) Inrush current of biggest compressor + 75 % of nominal absorbed current of the other compressor + fans current.(5) Compressor FLA + fans current.508 C – <strong>06</strong>/04 A – pag. 15/44


Physical data <strong>McPower</strong> XE ST and XE CN with HFC 407C<strong>McPower</strong> unit size 228.2 255.2 276.2 300.2 320.2 340.3Cooling capacity (1) kW 829,1 926,4 998,0 1091,1 <strong>11</strong>60,9 1216,2Power input (1) kW 288,2 321,1 350,7 386,3 418,4 428,8COP 2,9 2,9 2,8 2,8 2,8 2,8<strong>McQuay</strong> singlescrew compressors N° 2 2 2 2 2 3Refrigerant circuits N° 2 2 2 2 2 3Oil charge l 28 28 28 28 28 28Min % of capacity reduction % 12,5 12,5 12,5 12,5 12,5 12,5Condenser fansN° of fans / Nominal power fan kW 16/2 17/2 18/2 19/2 20/2 24/2Fan speed rpm 860 860 860 860 860 860Diameter mm 800 800 800 800 800 800Total air flow m 3 /s 88,5 94 99,5 105 <strong>11</strong>0,6 132,7EvaporatorEvaporator / Water volume N°/l 1 / 271 1 / 256 1 / 256 1 / 270 1 / 270 1 / 278Max operating pressure bar 10,5 10,5 10,5 10,5 10,5 10,5Water connections diameter mm 219 219 219 219 219 219Condenser coilCoil typeLanced fins – Internally spiral wound tubesWeight and dimensionStandard unit shipping weight for unit ST kg 5900 6170 6290 6525 6645 9050Standard unit operating weight for unit ST kg 6185 6440 6560 6780 6900 9320Standard unit shipping weight for unit CN kg 6140 6410 6530 6765 6885 9410Standard unit operating weight for unit CN kg 6425 6680 6800 7020 7140 9680Unit length mm 8010 8910 8910 9810 9810 <strong>11</strong>870Unit width mm 2230 2230 2230 2230 2230 2230Unit height mm 2520 2520 2520 2520 2520 2520<strong>McPower</strong> unit size 374.3 395.3 418.3 445.3 464.3 478.3Cooling capacity (1) kW 1317,6 1385,4 1453,5 1548,3 1613,5 1678,7Power input (1) kW 461,9 490,7 519,3 555,2 586,5 617,8COP 2,9 2,8 2,8 2,8 2,8 2,7<strong>McQuay</strong> singlescrew compressors N° 3 3 3 3 3 3Refrigerant circuits N° 3 3 3 3 3 3Oil charge l 28 28 28 28 28 28Min % of capacity reduction % 12,5 12,5 12,5 12,5 12,5 12,5Condenser fansN° of fans / Nominal power fan kW 25/2 26/2 28/2 28/2 29/2 30/2Fan speed rpm 860 860 860 860 860 860Diameter mm 800 800 800 800 800 800Total air flow m 3 /s 138,2 143,7 157,8 154,8 160,3 165,8EvaporatorEvaporator / Water volume N°/l 1 / 432 1 / 432 1 / 432 1 / 419 1 / 419 1 / 419Max operating pressure bar 10,5 10,5 10,5 10,5 10,5 10,5Water connections diameter mm 273 273 273 273 273 273Condenser coilCoil typeLanced fins – Internally spiral wound tubesWeight and dimensionStandard unit shipping weight for unit ST kg 9505 9625 10<strong>06</strong>0 10075 10410 10470Standard unit operating weight for unit ST kg 9980 10100 10530 10520 10860 10920Standard unit shipping weight for unit CN kg 9865 9985 10420 10435 10770 10830Standard unit operating weight for unit CN kg 10340 10460 10890 10880 <strong>11</strong>220 <strong>11</strong>280Unit length mm 12770 12770 13670 13670 14570 14570Unit width mm 2230 2230 2230 2230 2230 2230Unit height mm 2520 2520 2520 2520 2520 2520Note: (1) Nominal cooling capacity and power input are based on: 12 / 7 °C entering / leaving evaporator water temperature;35°C ambient temperature. The power input is for compressor only.(2) Unit XE 464.3 and XE 478.3 are longer than 14000 mm so beware of special transportation required.508 C – <strong>06</strong>/04 A – pag. 16/44


Electrical data <strong>McPower</strong> XE ST and XE CN with HFC 407CGrandezza unità <strong>McPower</strong> 228.2 255.2 276.2 300.2 320.2 340.3Standard voltage (1)400 V – 3f – 50 HzNominal unit current (2) A 538 597 652 707 757 802Max compressor current (3) A 596 655 710 777 840 889Fans current A 64 68 72 76 80 96Max unit current (3) A 660 723 782 853 920 985Max unit inrush current (4) A 865 1<strong>06</strong>6 1089 <strong>11</strong><strong>11</strong> <strong>11</strong>32 1273Max unit current for wires sizing (5) A 510 562 614 769 924 765Grandezza unità <strong>McPower</strong> 374.3 395.3 418.3 445.3 464.3 478.3Standard voltage (1)400 V – 3f – 50 HzNominal unit current (2) A 861 915 972 1023 1078 <strong>11</strong>21Max compressor current (3) A 948 1003 1056 <strong>11</strong>24 <strong>11</strong>97 1245Fans current A 100 104 <strong>11</strong>2 <strong>11</strong>2 <strong>11</strong>2 120Max unit current (3) A 1048 <strong>11</strong>07 <strong>11</strong>68 1236 1309 1365Max unit inrush current (4) A 1305 1335 1369 1394 1424 1449Max unit current for wires sizing (5) A 817 869 925 1076 1227 1386Notes: (1) Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.(2) Nominal current are based on: 12/7 °C entering/leaving evaporator water temperature and 35°C ambient temp.(3) Maximum current are based on: 14/9 °C entering/leaving evaporator water temperature and 44°C ambient temp.(4) Inrush current of biggest compressor + 75 % of nominal absorbed current of the other compressor + fans current.(5) Compressor FLA + fans current.508 C – <strong>06</strong>/04 A – pag. 17/44


Physical data <strong>McPower</strong> XE LN and XE XN with HFC 407C<strong>McPower</strong> unit size 228.2 255.2 276.2 300.2 320.2 340.3Cooling capacity (1) kW 794,4 884,9 952,5 1038,5 <strong>11</strong>04,2 <strong>11</strong>67,1Power input (1) kW 3<strong>11</strong>,5 346,9 378,6 418,0 453,6 463,4COP 2,6 2,6 2,5 2,5 2,4 2,5<strong>McQuay</strong> singlescrew compressors N° 2 2 2 2 2 3Refrigerant circuits N° 2 2 2 2 2 3Oil charge l 28 28 28 28 28 28Min % of capacity reduction % 12,5 12,5 12,5 12,5 12,5 12,5Condenser fansN° of fans / Nominal power fan kW 16/1,25 17/1,25 18/1,25 19/1,25 20/1,25 24/1,25Fan speed rpm 680 680 680 680 680 680Diameter mm 800 800 800 800 800 800Total air flow m 3 /s 64,5 68,6 72,6 76,7 80,7 96,8EvaporatorEvaporator / Water volume N°/l 1 / 271 1 / 256 1 / 256 1 / 270 1 / 270 1 / 278Max operating pressure bar 10,5 10,5 10,5 10,5 10,5 10,5Water connections diameter mm 219 219 219 219 219 219Condenser coilCoil typeLanced fins – Internally spiral wound tubesWeight and dimensionStandard unit shipping weight for unit LN kg 5900 6170 6290 6525 6645 9050Standard unit operating weight for unit LN kg 6185 6440 6560 6780 6900 9320Standard unit shipping weight for unit XN kg 6140 6410 6530 6765 6885 9410Standard unit operating weight for unit XN kg 6425 6680 6800 7020 7140 9680Unit length mm 8010 8910 8910 9810 9810 <strong>11</strong>870Unit width mm 2230 2230 2230 2230 2230 2230Unit height mm 2520 2520 2520 2520 2520 2520<strong>McPower</strong> unit size 374.3 395.3 418.3 445.3 464.3 478.3Cooling capacity (1) kW 1261,4 1325,8 1394,0 1478,2 1525.7 1601,3Power input (1) kW 499,0 529,9 558,2 600,3 644,1 669,6COP 2,5 2,5 2,5 2,5 2,4 2,4<strong>McQuay</strong> singlescrew compressors N° 3 3 3 3 3 3Refrigerant circuits N° 3 3 3 3 3 3Oil charge l 28 28 28 28 28 28Min % of capacity reduction % 12,5 12,5 12,5 12,5 12,5 12,5Condenser fansN° of fans / Nominal power fan kW 25/1,25 26/1,25 28/1,25 28/1,25 29/1,25 30/1,25Fan speed rpm 680 680 680 680 680 680Diameter mm 800 800 800 800 800 800Total air flow m 3 /s 100,9 104,9 <strong>11</strong>5,6 <strong>11</strong>3 <strong>11</strong>3 121EvaporatorEvaporator / Water volume N°/l 1 / 432 1 / 432 1 / 432 1 / 419 1 / 419 1 / 419Max operating pressure bar 10,5 10,5 10,5 10,5 10,5 10,5Water connections diameter mm 273 273 273 273 273 273Condenser coilCoil typeLanced fins – Internally spiral wound tubesWeight and dimensionStandard unit shipping weight for unit LN kg 9505 9625 10<strong>06</strong>0 10075 10410 10470Standard unit operating weight for unit LN kg 9980 10100 10530 10520 10860 10920Standard unit shipping weight for unit XN kg 9865 9985 10420 10435 10770 10830Standard unit operating weight for unit XN kg 10340 10460 10890 10880 <strong>11</strong>220 <strong>11</strong>280Unit length mm 12770 12770 13670 13670 14570 14570Unit width mm 2230 2230 2230 2230 2230 2230Unit height mm 2520 2520 2520 2520 2520 2520Note: (1) Nominal cooling capacity and power input are based on: 12 / 7 °C entering / leaving evaporator water temperature;35°C ambient temperature. The power input is for compressor only.(2) Unit XE 464.3 and XE 478.3 are longer than 14000 mm so beware of special transportation required.508 C – <strong>06</strong>/04 A – pag. 18/44


Electrical data <strong>McPower</strong> XE LN and XE XN with HFC 407CGrandezza unità <strong>McPower</strong> 228.2 255.2 276.2 300.2 320.2 340.3Standard voltage (1)400 V – 3f – 50 HzNominal unit current (2) A 546 6<strong>06</strong> 661 721 775 813Max compressor current (3) A 594 656 712 782 845 886Fans current A 37 39 41 44 46 55Max unit current (3) A 631 695 753 826 891 941Max unit inrush current (4) A 854 1055 1077 <strong>11</strong>00 <strong>11</strong>22 1251Max unit current for wires sizing (5) A 483 533 583 737 890 724Grandezza unità <strong>McPower</strong> 374.3 395.3 418.3 445.3 464.3 478.3Standard voltage (1)400 V – 3f – 50 HzNominal unit current (2) A 874 928 979 1041 <strong>11</strong>07 <strong>11</strong>46Max compressor current (3) A 948 1003 1053 <strong>11</strong>27 12<strong>06</strong> 1252Fans current A 58 60 64 64 67 69Max unit current (3) A 10<strong>06</strong> 1<strong>06</strong>3 <strong>11</strong>17 <strong>11</strong>91 1273 1321Max unit inrush current (4) A 1283 1312 1340 1371 1404 1427Max unit current for wires sizing (5) A 775 825 877 1028 <strong>11</strong>82 1335Notes: (1) Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.(2) Nominal current are based on: 12/7 °C entering/leaving evaporator water temperature and 35°C ambient temp.(3) Maximum current are based on: 14/9 °C entering/leaving evaporator water temperature and 44°C ambient temp.(4) Inrush current of biggest compressor + 75 % of nominal absorbed current of the other compressor + fans current.(5) Compressor FLA + fans current.508 C – <strong>06</strong>/04 A – pag. 19/44


Physical data <strong>McPower</strong> XE XXN HFC 407C<strong>McPower</strong> unit size 228.2 255.2 276.2 300.2 320.2 340.3Cooling capacity (1) kW 768,8 854,4 919,2 1000,0 1<strong>06</strong>2,4 <strong>11</strong>30,7Power input (1) kW 329,6 366,7 400,1 442,4 480,6 490,4COP 2,3 2,3 2,3 2,3 2,2 2,3<strong>McQuay</strong> singlescrew compressors N° 2 2 2 2 2 3Refrigerant circuits N° 2 2 2 2 2 3Oil charge l 28 28 28 28 28 28Min % of capacity reduction % 12,5 12,5 12,5 12,5 12,5 12,5Condenser fansN° of fans / Nominal power fan kW 16/0,77 17/0,77 18/0,77 19/0,77 20/0,77 24/0,77Fan speed rpm 500 500 500 500 500 500Diameter mm 800 800 800 800 800 800Total air flow m 3 /s 54,8 58,2 61,7 65,1 68,5 82,2EvaporatorEvaporator / Water volume N°/l 1 / 271 1 / 256 1 / 256 1 / 270 1 / 270 1 / 278Max operating pressure bar 10,5 10,5 10,5 10,5 10,5 10,5Water connections diameter mm 219 219 219 219 219 219Condenser coilCoil typeLanced fins – Internally spiral wound tubesWeight and dimensionStandard unit shipping weight kg 6140 6410 6530 6765 6885 9410Standard unit operating weight kg 6425 6680 6800 7020 7140 9680Unit length mm 8010 8910 8910 9810 9810 <strong>11</strong>870Unit width mm 2230 2230 2230 2230 2230 2230Unit height mm 2520 2520 2520 2520 2520 2520<strong>McPower</strong> unit size 374.3 395.3 418.3 445.3 464.3 478.3Cooling capacity (1) kW 1220,0 1281,8 1351,4 1426,5 1469 1544,1Power input (1) kW 527,7 560,2 587,2 635,1 683,4 709,8COP 2,3 2,3 2,3 2,2 2,2 2,2<strong>McQuay</strong> singlescrew compressors N° 3 3 3 3 3 3Refrigerant circuits N° 3 3 3 3 3 3Oil charge l 28 28 28 28 28 28Min % of capacity reduction % 12,5 12,5 12,5 12,5 12,5 12,5Condenser fansN° of fans / Nominal power fan kW 25/0,77 26/0,77 28/0,77 28/0,77 29/0,77 30/0,77Fan speed rpm 500 500 500 500 500 500Diameter mm 800 800 800 800 800 800Total air flow m 3 /s 85,6 89,1 98,5 95,9 95,9 102,8EvaporatorEvaporator / Water volume N°/l 1 / 432 1 / 432 1 / 432 1 / 419 1 / 419 1 / 419Max operating pressure bar 10,5 10,5 10,5 10,5 10,5 10,5Water connections diameter mm 273 273 273 273 273 273Condenser coilCoil typeLanced fins – Internally spiral wound tubesWeight and dimensionStandard unit shipping weight kg 9865 9985 10420 10435 10770 10830Standard unit operating weight kg 10340 10460 10890 10880 <strong>11</strong>220 <strong>11</strong>280Unit length mm 12770 12770 13670 13670 14570 14570Unit width mm 2230 2230 2230 2230 2230 2230Unit height mm 2520 2520 2520 2520 2520 2520Note: (1) Nominal cooling capacity and power input are based on: 12 / 7 °C entering / leaving evaporator water temperature;35°C ambient temperature. The power input is for compressor only.(2) Unit XE 464.3 and XE 478.3 are longer than 14000 mm so beware of special transportation required.508 C – <strong>06</strong>/04 A – pag. 20/44


Electrical data <strong>McPower</strong> XE XXN HFC 407CGrandezza unità <strong>McPower</strong> 228.2 255.2 276.2 300.2 320.2 340.3Standard voltage (1)400 V – 3f – 50 HzNominal unit current (2) A 561 622 677 742 800 835Max compressor current (3) A 604 668 725 797 863 900Fans current A 24 26 27 29 30 36Max unit current (3) A 628 694 752 826 893 936Max unit inrush current (4) A 857 1058 1080 <strong>11</strong>05 <strong>11</strong>28 1258Max unit current for wires sizing (5) A 470 520 569 722 874 705Grandezza unità <strong>McPower</strong> 374.3 395.3 418.3 445.3 464.3 478.3Standard voltage (1)400 V – 3f – 50 HzNominal unit current (2) A 897 951 999 1<strong>06</strong>9 <strong>11</strong>40 <strong>11</strong>83Max compressor current (3) A 964 1020 1<strong>06</strong>7 <strong>11</strong>48 1231 1277Fans current A 38 39 42 42 42 45Max unit current (3) A 1002 1059 <strong>11</strong>09 <strong>11</strong>90 1273 1322Max unit inrush current (4) A 1290 1318 1345 1380 1415 1440Max unit current for wires sizing (5) A 755 804 855 10<strong>06</strong> <strong>11</strong>57 13<strong>11</strong>Notes: (1) Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.(2) Nominal current are based on: 12/7 °C entering/leaving evaporator water temperature and 35°C ambient temp.(3) Maximum current are based on: 14/9 °C entering/leaving evaporator water temperature and 44°C ambient temp.(4) Inrush current of biggest compressor + 75 % of nominal absorbed current of the other compressor + fans current.(5) Compressor FLA + fans current.508 C – <strong>06</strong>/04 A – pag. 21/44


Relief ValvesAs a safety precaution and to meet code requirements, each chiller is equipped with pressure relief valveslocated on the coil condenser , evaporator, heat recovery condenser( if supplied) and liquid receiver for thepurpose of relieving excessive refrigerant pressure (caused by equipment malfunctioning, fire etc.) to theatmosphere.Oil HeaterThe oil separator is equipped with an immersion electric heater that is installed in a tube tht it can beremoved without disturbing the oil or opening the refrigerant circuit.Evaporator water flow and pressure dropBalance the chilled water flow through the evaporator. The flow rates must fall between the minimum andmaximum values. Flow rates below the minimum values shown will result in laminar flow that will reduce efficiency,cause erratic operation of the electronic expansion valve and could cause low temperature cut -out. On the otherhand flow rates exceeding the maximum values shown can cause erosion , vibration and may cause the break onthe evaporator water connections and tubes. Measure the chilled water pressure drop through the evaporator atfield installed pressure taps. It is important not to include valve or strainer pressure drop in these readings.Variable chilled water flow through the evaporator while the compressors are operating is not recommended. Setpoints are based upon a constant flow and variable temperature.Heat Recovery Condenser water flow and pressure dropHeat recovery condensers are supplied without the headers connection on both water side, entering and leaving.These Headers must be provided by the installer locally , including the wells pockets for microprocessor controlsensors.Balance the hot water flow through the heat recovery condenser. The flow rates must fall between the minimumand maximum values. Flow rates below the minimum values shown will result in laminar flow that will reduceefficiency, cause erratic operation of the unit and could cause high pressure cut-out. On the other hand flow ratesexceeding the maximum values shown can cause erosion on the condenser water connections and tubes.Measure the hot water pressure drop through the condenser at field installed pressure taps. It is important not toinclude header, valve or strainer pressure drop in these readings. Variable hot water flow through the condenserwhile the compressors are operating is not recommended. Set points are based upon a constant flow and variabletemperature.Leaving ConnectionsInstaller must provide the Headersbetween the heat recoverycondenser to have only one supplywater connection and one returnwater connectionHeat Recovery CondensersEntering Connections508 C – <strong>06</strong>/04 A – pag. 22/44


Evaporator Pressure Drop – <strong>McPower</strong> 228.2 ‚ 478.3508 C – <strong>06</strong>/04 A – pag. 23/44


Partial Heat Recovery Exchanger (Plate Exchanger) Pressure Drop508 C – <strong>06</strong>/04 A – pag. 24/44


Total Heat Recovery Exchanger Pressure Drop – <strong>McPower</strong> 228.2‚478.3508 C – <strong>06</strong>/04 A – pag. 25/44


Prestart System ChecklistYes No N/AChilled waterPiping completeWater system filled, ventedPump installed,(rotation checked), strainers cleanedControls (3 way valves, face and bypass dampers, bypass valves, etc.) operableWater system operated and flow balanced to meet unit design requirementsHeat recovery CondensersPiping and headers completeWater system filled, ventedTemperature sensors installed in the water well pocketsPump installed,(rotation checked), strainers cleanedControls (3 way valves, face and bypass dampers, bypass valves, etc.) operableWater system operated and flow balanced to meet unit design requirementsElectricalPower leads connected to starterAll interlock wiring complete between control panel and complies with specificationPump starter and interlock wiredWiring complies with local codesMiscellaneousThermometers wells, thermometers, gauges, control wells, controls, etc., installedMinimum system load of 60% of machine capacity available for testing andAdjusting controlsNote: This check list must be completed and sent to the local <strong>McQuay</strong> service location two weeks prior to start-up.508 C – <strong>06</strong>/04 A – pag. 26/44


OperationOperator ResponsibilitiesIt is important that the operator become familiar with the equipment and the system before attempting tooperate the chiller. In addition to reading this manual, the operator should study the operating manualControl Panel Microtech II “C” Plus OM 101C (latest edition) and the electrical wiring diagram furnished withthe unit before starting, operating, or shutting it down.During the initial start up of the chiller the <strong>McQuay</strong> technician will be available to answer any questions andinstruct in the proper operating procedures.It is recommended that the operator maintain an operating log for each individual chiller unit. In addition, aseparate maintenance log should be kept of the periodic maintenance and servicing activities.If the operator encounters abnormal or unusual operating conditions, it is recommended that a <strong>McQuay</strong>service technician be consulted.Refrigeration CycleThe refrigerant gas, at low pressure, leaving the evaporator enters the screw compressor through the motor winding tocool it. The compressor compresses the refrigerant from low to high pressure and during this phase there is the oilinjection to cool, to lubricate and to seal the screw chamber. The effect of the oil injection is that to have a mixture of oiland refrigerant that enter the high efficiency oil separator where by a combined action of centrifugal force and lowvelocity , both elements are separated.While the gas is leaving from the top of oil separator, the oil slips down the receiver along the wall and goes back thecompressor injection port by the existing differential pressure between the suction and discharge side.After the oil separator, the high pressure and hot gas crosses the “four way-valve” and according to the unit operationmode, enters inside the air-cooled coil condenser (cooling mode) or heat recovery water condenser (heat recoverymode).In both heat exchangers the hot gas is cooled by the ambient air in the first case and by the water in the second casechanging the status from gas to liquid.The liquid refrigerant before leaving the condensing section is passing inside the sub-cooler where is cooled below thesaturation temperature, to compensate the pressure drops through the liquid line and to increasing the evaporatorcapacity.After the sub-cooler the liquid refrigerant enters in the liquid receiver, where the exceeding charge is accumulated duringthe “cooling mode” in order to compensate the different volume ( refrigerant side) between the coil condenser and theheat recovery condenser. The liquid refrigerant passes through the filter dryer, to eliminate eventual particle of humidity,and through the expansion valve where there are the lamination of the refrigerant.In that situation we have the refrigerant mixture of liquid and gas at low pressure entering the evaporator that absorbsthe heat load from chilled water to complete the evaporation and restart the cycle.508 C – <strong>06</strong>/04 A – pag. 27/44


Refrigerant circuit – <strong>McPower</strong>ST1WL1Y6EVAPORATORST2WL2Y6508 C – <strong>06</strong>/04 A – pag. 28/44


MicroTech II C Plus controlMicroTech II C Plus controller is installed as standard on all the units; it can be used to modify unit set points andcheck control parameters. A display illustrates the machine's operating status, programmable values and setpointse.g. temperatures, and pressures of fluids (water, refrigerant and air). Device controls optimize <strong>McQuay</strong>chillers energy efficiency and reliability characteristics. It uses sophisticated software with predictive logic to selectthe most energy efficient combination of compressor, EEXV and condenser fan to keep stable operating conditionsand optimize energy efficiency. The compressors are automatically rotated to ensure equal operating hours.MicroTech II protects critical components in response to external signals from its system sensors measuring:motor temperatures, refrigerant gas and oil pressures, correct phase sequence and evaporator.Control section - main features−−−−−−−−−−−−−−−−−−Management of the compressor capacity slide and fans modulation according to the distributedmultiprocessor logic systemChillers enabled to work in partial failure condition thanks to the distributed multiprocessor logic systemFull routine operation at condition of:- High ambient temperature value- High thermal load- High evaporator entering water temperature (start-up)Display of evaporator entering/leaving water temperatureDisplay of condensing-evaporating temperature and pressure, suction and discharge superheattemperature for each circuitLeaving water cooled temperature regulation. Temperature tolerance=0,1°CCompressors and evaporator/condenser pumps hours counterDisplay of Status Safety DevicesStart up numbers and compressors working hours equalizationExcellent management of compressors loadFans management according to condensing pressureAutomatic re-start in case of power supply interruption (adjustable)Soft LoadReturn ResetAOT ResetSet-point ResetDemand limit or Current limit (optional)Speedtrol control (optional)Safety for each refrigerant circuitHigh pressure (pressure switch)Low pressure (pressure switch)Compressor overloadCondensation fan Magneto-thermalHigh Discharge Temperature on the compressorPhase MonitorStar / Delta Transition FailedLow Delta Pressure between Suction and DischargeLow pressure ratioHigh oil pressure dropLow oil pressure508 C – <strong>06</strong>/04 A – pag. 29/44


System securityPhase monitorFreeze protectionA flow controller input (stops the unit)Remote on/off input without alarm signaling.Regulation typeProportional + integral + derivative regulation on the evaporator input probe.CondensationThe condensation can be carried out according to temperature or pressure. The fans can be managed accordingto ON/OFF mode or with a 0/10 V modulating signal.MicroTech II C Plus terminalThe MicroTech II C Plus terminal has following features:−4-lines by 20-character liquid crystal display back lighted− Key-pad consisting of 15 keys “ clear language display ”−−−−Memory to protect the dataGeneral faults alarm relay4-level password access to modify the settingService report displaying all running hours and general conditionsMicroPlant TM :Solution for tele-maintenance and supervisory systemsMicroTech II C Plus can be monitored locally or via modem by MicroPlant TM supervision program, that runs on PCsystems under Windows ’95 – ’98.MicroPlant TM is the best solution:−−−−−−To centralize all the information in just one local and/or remote PCTo check all the parameters for each unit connectedData logging of temperature - pressurePrintouts of alarms, parameters and graphsTo control several plants located in different geographical areas froma central stationTo manage the Service centersMicroPlant TM allows:−−−−Visualization of all working conditions for each controllerVisualization of their graphicsDisplay, print -out of the actual alarmsConnection between local and remote computer via telephone line(Modem)508 C – <strong>06</strong>/04 A – pag. 30/44


MicroTech II C Plus remote controlCompatibility with supervisory systems is becomingincreasingly important in HVAC. MicroTech II C Plus allowseasy interfacing with BMS (Building Management Systems),the external world that can be:− Full compatible Siemens, Johnson;− Every MODBUS compatible system;− ( Satchwell, Honeywell )− BacNet point to point, ECHELON FTT10− ( available on request )Heat Recovery Microprocessor ControlAll the units equipped with the heat recovery water condensers have an additional “microprocessor control” tomanage the heat recovery function of the unit .The microprocessor is installed inside the main control box below the Microtech key pad.(see the picture below)Microtech Key PadChiller OperationHEAT RECOVERYOPERATIONSwitch Selector “Q7”“0” Cooling Mode“1” Heat RecoveryModeHeat RecoveryMicroprocessorControlCarel type “ IR32”We use two different models of microprocessor control.IR32W units with two Heat recovery condensersIR32Z Units with three or four Heat recovery CondensersBoth models are equipped with the temperature sensors NTC, PT100 to control the entering watertemperature to the heat recovery condenser and metering the temperature of leaving hot water .Temperature sensors are supplied electrically connected to the microprocessor but not installed in the pipeswell pocket, the realization of that devices must done locally by the installer.508 C – <strong>06</strong>/04 A – pag. 31/44


The identification of the sensors are the following:“W10” to be installed at the entering of the condenser“W<strong>11</strong>” to be installed at the leaving of the condenserFunctionWhen the selector switch Q7 enable the heat recovery mode, if the sensor “W10” is measuring the hot watertemperature value below the set point allow the first step to switch the four-way valve from chiller to heatrecovery cycle. If the set point temperature is not achieved the microprocessor control insert all the othersteps available according to the number of refrigerant circuits. On the contrary if the water temperatureexceed the set point value the microprocessor control switch off the steps until the temperature is inside theband.Of course it is mandatory that the heat recovery condenser flow switch is on, otherwise the unit neverswitches on the heat recovery cycle.The Microprocessor control is normally settled , at the factory, to verify or change the set points see the usermanual supplied with the unit.Heat Recovery OperationThe unit supplied with the heat recovery condensers is equipped with an additional microprocessor (TC10 seeelectrical wiring diagram) with two, three or four steps to control the hot water temperature, according to thenumber of the heat exchangers installed on the unit(one step for each compressor). For reference how to set thismicroprocessor see the Specific manual supplied with the unit. The heat recovery mode is available only if there isthe request of cooling load and the capacity is depending from the number of the compressors running and theunloading position of them.To run the unit in heat recovery mode follow the items listed below:1) Verify the installation of the water flow switch done by the installer and check the electrical connection atM3.426 and M3.427 terminal blocks inside the electrical panel2) Verify the installation of the microprocessor sensor in the pocket well of the water return common header (done by the installer)3) Check the set point of the return water temperature on the display of the microprocessor “TC10” (Carel IR32).Do not exceed the max water temperature allowed (see the operating limits) to avoid the shut -down the unitfor high pressure.4) Switch the water pump on5) Switch “ON” the selector “Q7” that allow the unit to run in heat recovery mode. If the microprocessor TC10 isasking for hot water, the 4 ways-valve change the refrigerant circuit from the condenser coil to the heatrecovery condenser (first step) and insert the other circuits until the return hot water is matching the set point.In that condition the fan motors of the respective condenser coil are switched “OFF”. Vice-versa, when themicroprocessor is reducing the steps, the 4 ways-valve change the refrigerant circuit from the heat recoverycondenser to the condenser coil and switching on the respective fan motors.6) In case of lack of water in the heat recovery condenser the unit is automatically switched on cooling modeonly.Standard controlsHigh pressure controlThe high pressure switch will shut -down the compressor when the discharge pressure exceeds the setting pointvalue.Phase/voltage monitorThe phase/voltage monitor is a device which provides protection against three-phase electrical motor loss due topower failure conditions, phase loss, and phase reversal. Whenever any of these conditions occur, a contactopens to the microprocessor which then de-energizes all inputs. When proper power is restored, contacts closeand microprocessor enables compressors for operation. When three-phase power has been applied, the outputrelay should close and the "run light" should come on. If the output relay does not close, perform the followingtests:1. Check the voltages between L1-L2, L1-L3 and L2-L3 (L1, L2, L3 are the three phases). These voltages shouldbe approximately equal and within + 10% of the rated three-phase line-to-line voltage.2. If these voltages are extremely low or widely unbalanced check the power system to determine the cause of theproblem.508 C – <strong>06</strong>/04 A – pag. 32/44


3. If the voltages are good, using a phase tester, verify that phases are in A, B, C sequence for L1, L2 and L3.Correct rotation is required for compressor operation. If required to do so by phase sequence, turn off the powerand interchange any two of the supply power leads at the disconnect main switch. This may be necessary as thephase voltage monitor is sensitive to phase reversal. Turn on the power. The output relay should now close afterthe appropriate delay.Heat Recovery Microprocessor Set-upThe unit supplied with the heat recovery condensers is equipped with an additional microprocessor (TC10 seeelectrical wiring diagram) with two, three or four steps to control the hot water temperature, according to thenumber of the heat exchangers installed on the unit(one step for each compressor). For reference how to set thismicroprocessor see the Specific manual supplied with the unit.We report below the most important set -up values, for references see the microprocessor manual.ITEM Description Set PointSt1 Inlet water temperature set point Max 50St2N/ACO Operating Mode 1P1 Differential Set point 2P2N/AC4 Authority 0.5C5 1C6 0C7 3C8 5C9 0C10 0C<strong>11</strong> 0C12 20”C13 1C14 0C15 0C16 100C17 5C18 0C19 0C21 30C22 43C23N/AC24N/AP25 8P26 55P27 2P28 20C29 4C30N/AC31 0C32 1C33 0C50 4C51 0508 C – <strong>06</strong>/04 A – pag. 33/44


System MaintenanceGeneralTo ensure proper operation at peak capacity and to avoid damage to package components, a program of periodicinspections should be set up and followed. The following items are intended as a guide and are to be used duringinspection and must be combined with sound coming from compressor and electrical practices to ensure troublefreeperformance. The liquid line sightglass indicator on all circuits must be checked to be sure the glass is full andclear. If the indicator shows that a wet condition exists and/or there are bubbles in the glass, even with a fullrefrigerant charge, the filter-drier element must be changed.Compressor maintenanceThe screw Frame 4 compressor does not required frequent maintenance. However, vibration test is an excellentcheck for proper mechanical operation. Compressor vibration is an indicator of the requirement for maintenanceand contributes to a decrease in unit performance and efficiency. It is recommended that the compressor bechecked with a vibration analyser at or shortly after start-up and again on an annual basis. When performing thetest the load should be maintained as closely as possible to the load of the original test. The vibration analyser testprovides a fingerprint of the compressor and when performed routinely can give a warning of impending problems.The compressor is supplied with a cartridge oil filter. It is a good policy to replace this filter anytime the compressoris opened for servicing.Electrical controlWarning: Electric shock hazard. Turn off all electrical power supplies before continuing with following service.Caution: It is necessary to de-energise the complete electrical panel, including crankcase heater, before doingany servicing inside.Prior to attempting any service on the control centre it is advisable to study the wiring diagram so that youunderstand the operation system of the water chiller. Electrical components do not require particular maintenanceother than a monthly tightening of cables.Warning: The warranty becomes void if the wiring connection to the unit is not in accordance with thespecification. A blown fuse or tripped protector indicates a short ground or overload.Before replacing the fuse or restarting the compressor, the problem must be found and corrected. It is important tohave a qualified electrician to service this panel. Unqualified tampering with the controls can cause seriousdamage to equipment and void the warranty.Refrigerant sight-glassThe refrigerant sight-glasses should be observed periodically (a weekly observation should be adequate). A clearliquid sight-glass indicates the right refrigerant charge in the system to insure proper feed through the expansionvalve. Bubbling refrigerant in the sight-glass, during stable run conditions, indicates that the system may be shortof refrigerant charge. Refrigerant gas flashing in the sight-glass could also indicate an excessive pressure drop inthe liquid line, possibly due to a clogged filter-drier or a restriction elsewhere in the liquid line. If sub-cooling is lowadd charge to clear the sight -glass. If sub-cooling is normal and flashing is visible in the sight -glass replace thefilter-drier. An element inside the sight -glass indicates the moisture condition corresponding to a given elementcolour. If the sight-glass does not indicate a dry condition after about 3 hours of operation, the unit should bepumped down and the filter-dryers changed.The following table is a guide to determinate the dry or wet condition of the system:COLOURGreen (Sky Blue)Yellow (Pink)MEANSDryWetFilter-dryersA replacement of the filter-drier is recommended during scheduled service maintenance of the unit when bubblesoccur in the sight-glass with normal sub-cooling temperature. The filter-drier should also be changed if the508 C – <strong>06</strong>/04 A – pag. 34/44


moisture indicator in the sight -glass indicates excess moisture by the wet system colour indicators. During the firstfew months of operation the filter-drier replacement may be necessary if you have bubbles in liquid line asexplained before. Any residual particles from the unit working process, compressor and miscellaneouscomponents are swept by the refrigerant into the liquid line and are caught by the filter-drier.To change the filter drier, close the manual liquid line shutoff valve, pump the unit down by opening the switchesQ1, Q2 (ON/OFF switches compressors) in “off” position.Move the ON/OFF switch unit Q0 to the “off” position.Close the suction line valve. Remove and replace the filter-drier. Evacuate the liquid line through the manualshutoff valve removing non-condensable that may have entered during filter replacement.Open the suction line valve; open the manual liquid line of shutoff valve. A leak check is recommended beforereturning the unit to operation.Electronic expansion valve<strong>McPower</strong> air-cooled chiller is equipped with the most advanced electronic expansion valve to achieve precisecontrol of refrigerant mass flow. As today’s system requires improved energy efficiency, tighter temperaturecontrol, wider range of operating conditions and incorporate new features like remote monitoring and diagnostics,the application of electronic expansion valves becomes mandatory. <strong>McPower</strong> electronic expansion valve proposesfeatures that makes it unique: short opening and closing time, high resolution, positive shut-off function toeliminate use of additional solenoid valve, highly linear flow capacity, continuous modulation of mass flow withoutstress in the refrigerant circuit and corrosion resistance stainless steel body.EvaporatorThe units are supplied with new optimised counter-flow evaporator, single refrigerant pass. It is direct expansion (2evaporators for units with 4 compressors) with refrigerant inside the tubes and water outside (shell side) withcarbon steel tube sheets, with straight copper tubes that are spirally wound internally for higher efficiencies,expanded on the tube plates. The external shell, is linked with an electrical heater to prevent freezing to -28 Cambient temperature, energised by a thermostat and is covered with a closed cell insulation material. Eachevaporator has 2 or 3 refrigerant circuits one for each compressor. Each evaporator is manufactured inaccordance to PED approval. Normally no service work is required on the evaporator.Heat Recovery CondensersCondensers are shell and clearable, through-tube types. Standard configuration is 2 passes. The unit hasindependent exchangers, one per circuit completely assembled. Each heat recovery condenser has a carbon steeland seamless, integrally finned high efficiency copper tubes, roll expanded into heavy carbon steel tube sheets.Water heads are removable and include vent and drain plugs. Condensers are equipped spring loaded reliefvalves.Condenser is designed to comply with PED. Waterside working pressure is designed for 10.5 bar. Standardconfiguration on water connection side is 2 passes.The installer has to supply the water header connection for all heat recovery condensers installed on the unit, bothat the entering and leaving water connections and provide the flow switch. All the heat recovery condenser mustbe connected together in parallel. At the entering water pipe, must be installed the temperature sensor, suppliedspare with the unit, to control the heat recovery cycle.Condenser coil fansThe condenser fans are helical types with wing-profile blades to achieve a better performance. The direct couplingwith the electrical motor reducing vibrations caused by the functioning. The three-phase type motors are suppliedas standard with IP54 protection (Insulation class F); they are protected against overloading and short circuits bycircuit breakers located inside the electrical control panel.Air-cooled condenser (Condensing coil)The condensing coils are constructed with internally enhanced seamless copper tubes arranged in a staggeredrow pattern and mechanically expanded into <strong>McQuay</strong> lanced and rippled aluminum condenser fins with full fincollars. An integral sub-cooler circuit provides sub-cooling to effectively eliminate liquid flashing and increases incooling capacity without increasing the power input.No maintenance is ordinary required except the occasional removal of dirt and debris from the outside surface ofthe fins. <strong>McQuay</strong> recommends the use of foaming coil cleaners available at air conditioning supply outlets. Usecaution when selecting such cleaners as some may contain potentially harmful chemical. Care should be taken notto damage the fins during cleaning.508 C – <strong>06</strong>/04 A – pag. 35/44


Lubricating oilsBesides lubricating the bearing and other moving parts, the oil has the equally important task of sealing theclearances between the rotors and other potential leakage paths thereby improving pumping efficiency; the oil alsoassists in dissipating the heat of compression. The amount of oil injected is therefore well in excess of thatrequired for lubrication alone. To reduce the oil circulation in the refrigerant circuit, the oil separator is installed onthe compressor discharge lineLubricating oil approved for use with <strong>McQuay</strong> Screw compressor is POE Emkarate RL68H.The oil pressure transducer monitors the oil injection pressure on the compressor. If the oil pressure value is belowthe setting point inside the microprocessor control the compressor stops.The oil pressure is generated by discharge pressure, a minimum discharge pressure must be maintained; thisminimum pressure increases, as the suction pressure increases in order to maintain the pressure differencerequired.Crankcase and oil separator heatersThe function of the Oil separator heaters is to prevent oil dilution with refrigerant during compressor shutdown,which would cause foaming and consequent reduction in lubricating oil flow to the moving parts. Electric heatersare energised every time the compressors shuts-down.Warning: Verify if the heaters have been energised at least 12 hours, prior the start -up.RefrigerantRefrigerant chargingMcPowe air cooled screw chillers are shipped factory charged with a full operating charge of refrigerant but theremay be times that a unit must be recharged at the jobsite. Follow these recommendations when field charging.Refer to the unit operating charge found in the physical data tables on pages from 9 to15 according to the versionof the unit, chiller or heat recovery . The optimum charge is the charge which allows the unit to run with no flashingin the liquid line at all operating conditions. When the liquid line temperature does not drop with the addition of 2,0-4,0 Kg of charge and the discharge pressure goes up 20-35 kPa then the sub-cooler is nearly full and propercharge has been reached. Unit can be charged at any steady load condition, at any outdoor ambient temperature.Unit must be allowed to run 5 minutes or longer so that the condenser fan staging is stabilized at normal operatingdischarge pressure. For best results charge the unit with 2 or more condenser fans operating per refrigerant.In case of moisture is noticed in the system, through the moisture indicator, the system must be evacuated toeliminate the cause of trouble. After the trouble solved, the system must be dried by making an almost perfectvacuum. For this purpose, a displacement vacuum pump should be used.When the system has been opened for extensive repairs, as for an overhaul, it is advisable to use the method ofthe evacuation as follows:1. Evacuate the refrigerant system by the vacuum pump reaching the value of 200 Pa (1,5 mm Hg).2. Break the vacuum with nitrogen until the atmospheric pressure is reached.3. Repeat operation 1 and 2 for two times.4. Evacuate the refrigerant system reaching the value of 66,5 Pa.The dry nitrogen, used to break the vacuum will absorb any moisture and air left in the system, and they will bealmost completely removed by the three evacuations. If burnt oil or sludge are found in the refrigerant circuit(caused by the compressor motor burn-out), before the vacuum operation it will be necessary to carefully clean thesystem using the filter dryer clean-out method; which basically involves the use of special filter dryers including asuitable desiccant in both the liquid and suction lines.Excessive refrigerant losses can also cause leak of oil from the system. Check the oil level during operation andensure that oil is visible in the top sight-glass of the oil separator.1. If the unit is slightly undercharged the unit will show bubbles in the sight-glass. Recharge the unit.2. If the unit is moderately undercharged the unit will most likely trip on freeze protection. Recharge the unit asdescribed in the charging procedure below.Procedure to charge a moderately undercharged <strong>McPower</strong> unit1. If a unit is low on refrigerant you must first determine the cause before attempting to recharge the unit. Locateand repair any refrigerant leak. Evidence of oil is a good indicator of leakage however, oil may not be visible atall leaks. Liquid leak detector fluids work well to show bubbles at medium size leaks but electronic leak detectormay be needed to locate small leaks.508 C – <strong>06</strong>/04 A – pag. 36/44


2. Add the charge to the system through the valve on evaporator entering pipe between the expansion valve andthe evaporator head. Follow the procedure reported on “Refrigerant charging”.3. The charge can be added at any load condition.Charging the refrigerant1. Connect the refrigerant bottle with a filling pipe to the filling valve on the evaporator head. Before firmlytightening the refrigerant bottle valve, open it and force the air out from the filling pipe. Tighten the chargingvalve connection and fill the refrigerant.2. When the refrigerant stops to enter the system, start the compressor and complete the refrigerant charge.3. If you do not know how much refrigerant has to be added, shut off the bottle valve every 5 minutes and continueto charge the refrigerant until the sight glass is clear and free from bubbles.Note: Do not discharge the refrigerant into the atmosphere. To recover it, use empty, clean and dry bottles. Theliquid refrigerant recovery can be made through the valve provided on the condenser coil sub-cooler outlet. Tofacilitate the recovery of refrigerant, put the bottle inside a container full of ice; avoid excessive filling of the bottle(70÷80% max).Preventive maintenance scheduleOperationRef. No.TYPE OF OPERATIONWeekly1 Reading and recording of suction pressure x2 Reading and recording of discharge pressure x3 Reading and recording of supply voltage x4 Reading and recording of current intensity x5Check refrigerant charge and possible moisture in thecircuit refrigerant through the liquid sight glassSCHEDULESix-MonthlyMonthly6 Check the suction temperature and the superheating x7 Check setting and operation of safety devices x8 Check setting and proper operation of control devices x9 Inspect the condenser for possible scaling or damages xStart-up and shut-downxYearlyStart-up−−−−Verify that all shut-off valves are open.Prior to starting the unit, open the water circulation pump(s) and regulate the flow through the evaporatorand through the heat recovery condensers (if supplied) in accordance to the setting conditions of the unit.If in the water system is not available the flow meter, the practice suggests to fix the water flow as firststep by reaching the differential pressure drops values at the entering/leaving connections of the heatexchangers as reported on the diagram pressure drops. The final set up will be done, when the unit isrunning, adjusting the water flow to reach the water "∆Τ” at full load.Verify that the evaporator inlet and outlet water temperature sensors indicate the same temperature or thedifference between them and the thermometer does not exceed 0,1°C.Verify that the inlet water temperature sensors of the heat recovery condenser (if supplied) has beeninstalled in a well pocket on the common pipe and indicate the same temperature or the differencebetween it and the thermometer does not exceed 0,1°C.− Verify that the flow switch(es) is(are) connected to the electrical panel at the terminal blocks M3.8 – M3.23for the evaporator and M3.426 – M3.427 for heat recovery condensers ( if supplied)−−Verify the electrical power connection to the electrical panel and put in “OFF” position all the switches.Switch “ON” the main switch isolator “Q10” and the selector “Q12” . In this way the electric heaters of thecompressors and the oil separators are energised.Check if the software installed on the microprocessor is corresponding to the unit type and the set pointare correct. See the Microtech II “C” Plus operating manual 101C for instruction508 C – <strong>06</strong>/04 A – pag. 37/44


−−−Turn the selector switch Q0 in position ” Local ”. For normal unit operation condition, if the unit is handledby remote place switch Q0 in position “remote”.Push the “on/off” button on the keypad and wait for the green light on.Before turn the Q1 selector to ON position, check that the Q10 and Q12 has been switched ON at least12 hours before. The controller , if there is a cooling load demand, will start the correspondingcompressor. Repeat the sequence for Q2,Q3, Q4 selectors according to the number of compressorsinstalled.Operational Shut-down−−Push the “On/Off” button on the keypad, or by remote switch, to de-energise the unit, green light becomeoff, all the compressors will carry out its pump-down cycle and then stop.Switch off the water pumpsSeasonal Shut-down−−−−−−−−−Turn the Q1 selector to Off position. The compressor will carry out its pump-down cycle and then stop.Repeat the sequence for all the selectors Q2, (Q3 and Q4) to stop all the other compressors.Switch the “Q0” selector from “Local” to off position.Push the “On/Off” button on the keypad to de-energise the unit, green light become off.Open the circuit breaker Q12 to stop the auxiliary circuit.Open the main switch Q10 to remove the power supplier to the unit. In this condition the oil electric heateris off. When you restart the unit before switching on the compressors wait at least 12 hours to heat the oil.Close the shut-off valves of the refrigerant circuits.Switch off the water pumpsEmpty the water heat exchangers or fill them with glycol for freeze protection.Maintenance Shut-down−−−−−−−−−Turn the Q1 selector to Off position. The compressor will carry out its pump-down cycle and then stop.Repeat the sequence for all the selectors Q2, (Q3 and Q4) to stop all the other compressors.Switch the “Q0” selector from “Local” to off position.Push the “On/Off” button on the keypad to de-energise the unit, green light become off.Open the circuit breaker Q12 to stop the auxiliary circuit.Open the main switch Q10 to remove the power supplier to the unit. In this condition the oil electric heateris off. When you restart the unit before switching on the compressors wait at least 12 hours to heat the oil.Close the shut-off valves of the refrigerant circuits.Switch off the water pumpsService the unit accordingly to the programIn warranty return material procedureMaterial may not be returned except by permission of <strong>McQuay</strong>Service department. A "Return Goods" tag will beincluded with the returned material to expedite handling at our factory. Return of the parts does not constitute anorder for replacement. Therefore, a purchase order must be entered through our nearest Sales Representative.The order should include part name, part number, model number and serial number of the unit involved. After<strong>McQuay</strong> inspection of the returned part, if the failure is due to faulty material or workmanship, credit will be issuedon the customer's purchase order. All defective parts shall be returned to <strong>McQuay</strong> factory, transportation chargesprepaid.Service & replacement partsAlways report the model number, acknowledgement number and the unit serial number stamped on thenameplate, whenever ordering maintenance service or replacement parts.When order the replacement parts, state the installing date of the machine and the date of the failure. For an exactdefinition of the replacement part requested, make reference to the relative code number or, failing that, attach adescription of the part being requested.508 C – <strong>06</strong>/04 A – pag. 38/44


Troubleshooting chartPROBLEM POSSIBLE CAUSES POSSIBLE CORRECTIVE STEPS1. Main power switch open.2. Unit system switch open.Compressor willnot runCompressorOverload RelayTripped orCircuit BreakerTrip or FusesBlownCompressornoisy orvibratingCompressor willnot load orunload3. Circuit switch in pump-down position.4. Evaporator flow switch not closed.5. Circuit breakers open.6. Fuse blown or circuit breakers tripped.7. Unit phase voltage monitor not satisfied.8. Compressor overload tripped.9. Defective compressor contactor or contactorcoil.10. System shut down by safety devices.<strong>11</strong>. No cooling required.12. Motor electrical trouble.13. Loose wiring.1. Low voltage during high load condition.2. Loose power wiring.3. Power line fault causing unbalancedvoltage.4. Defective or grounded wiring in the motor.5. High discharge pressure.1. Compressor internal problem2. Oil injection not adequate.1. Defective capacity control.2. Unloader mechanism defective.3. Control solenoids defective.1. Close switch.2. Check unit status on Control Panel. Closeswitch.3. Check circuit status on Control Panel. Closeswitch.4. Check unit status on Control Panel. Closeswitch.5. Close circuit breakers.6. Check electrical circuits and motor windingsfor shorts or grounds.Investigate for possible overloading.Check for loose or corroded connections.Reset breakers or replace fuses after faultis corrected.7. Check unit power wiring to unit for correctphasing. Check voltage.8. Overloads are manual reset. Reset overloadat button on overload.Clear alarm on Microprocessor.9. Check wiring. Repair or replace contactor.10. Determine type and cause of shutdownand correct problem before attempting torestart.<strong>11</strong>. Check control settings. Wait until unit callsfor cooling.12. See 6, 7, 8 above.13. Check circuits for voltage at requiredpoints. Tighten all power wiring terminals.1. Check supply voltage for excessive voltagedrop.2. Check and tighten all connections.3. Check supply voltage.4. Check motor and Replace if defective.5. See Corrective steps for high dischargepressure.1. Contact <strong>McQuay</strong>2. Contact <strong>McQuay</strong>.1. See capacity control section.2. Replace.3. Replace.508 C – <strong>06</strong>/04 A – pag. 39/44


Troubleshooting chartPROBLEM POSSIBLE CAUSES POSSIBLE CORRECTIVE STEPS1. Discharge shutoff valve partially closed.2. Non condensable in the system.High dischargepressureLow dischargepressureLow suctionpressureHigh suctionpressureUnit doesn’tswitch in HeatRecoveryoperationMode3. Fans not running.4. Fan control out of adjustment.5. Heat recovery condensers dirty6. System overcharged with refrigerant.7. Duty condenser coil.8. Air re-circulation from outlet into unit coils.9. Air restriction into unit.1. Wind effect at low ambient.2. Condenser fan control not correct.3. Low suction pressure.4. Compressor operating unloaded.1. Inadequate refrigerant charge quantity.2. Evaporator dirty.3. Clogged liquid line filter-drier.4. Expansion valve malfunctioning.5. Insufficient water flow to evaporator.6. Water temperature leaving evaporator is toolow.7. Evaporator head ring gasket slippage.1. Excessive load - high water temperature.2. Compressor unloaders open.3. Superheat is too low.1. “Q7” selector switch doesn’t work2. No Heating load required3. Flow switch not operating4. 4-way Solenoid valve not working5. “W10” sensor element not fixed in the well pocket6. “W10” sensor element gives wrong signal7. “TC10” Microprocessor control doesn’t work1. Open shutoff valve.2. Purge the non condensable from thecondenser coil after shutdown.3. Check fan fuses and electrical circuits.4. Check that unit set-up in Microprocessormatches the unit model number. CheckMicroprocessor condenser pressuresensor for proper operation.5. Clean the condenser tubes by mechanicalor chemical tools6. Check for excessive sub-cooling. Removethe excess charge.7. Clean the condenser coil.8. Remove the cause of re-circulation.9. Remove obstructions near unit.1. Protect unit against excessive wind intovertical coils.2. Check that unit set-up in Microprocessormatches the unit model number.3. See Corrective Steps for low suctionpressure.4. See Corrective Steps for failure to load.1. Check liquid line sight-glass. Check unit forleaks.2. Clean chemically.3. Replace4. Check expansion valve superheat and valveopening position. Replace valve only itcertain valve is not working.5. Check water pressure drop across theevaporator and Adjust the flow.6. Adjust water temperature to higher value.7. Low suction pressure and low superheatboth present may indicate an internalproblem. Consult factory.1. Reduce load or add additional equipment.2. See Corrective Steps below for failure ofcompressor to load.3. Check superheat on Microprocessor display.Check suction line sensor installation andsensor.1. Replace the selector switch2. Add additional equipment.3. Check water pump4. Check the solenoid valve and if the 4-wayvalve is blocked. Replace the wrongcomponents5. Fix the element in the well pocket properly6. Replace the element7. Check the supply connections or replace it508 C – <strong>06</strong>/04 A – pag. 40/44


508 C – <strong>06</strong>/04 A – pag. 41/44