Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
TM 5-<strong>6115</strong>-631-14&PFigure 5-5. Power Plant Markings.Section Ill. GENERATOR SET5-7. Generator Set Replacement. (See figures 5-6 and 5-7.) Power Plant AN/MJQ-16 has twogenerator sets. Replacement procedures are identical for both.a. Removal.. (1) Remove fitted cover (paragraph 3-11, a.(1)).(2) Remove six bow assemblies (paragraph 3-11, b.(1)).(3) Disconnect all power cable and ground wires (1, figure 5-6) from generator set (2).NOTEThe beveled washers (4) may have been welded in place.(4) Remove four screws (3) and four beveled washers (4), securing generator set (2), tomounting rails (5) on trailer bed (6).5-9