TM 5-<strong>6115</strong>-631-14&PFigure 4-2.Installing Power PlantWARNINGDo not operate generator sets until power plant is properly grounded(paragraph 4-2, b.). Serious injury or death by electrocution can result fromoperating an ungrounded power plant.CAUTIONTo avoid damage to equipment, make certain of voltage, frequency, andphase requirements of load being connected to generator set.(6) Refer to data plate on load terminal board cover and to TM5-<strong>6115</strong>-584-12. Connect powerplant to system or equipment to be powered.b. Grounding. Check that generator sets are grounded to GROUND TERMINAL stud on trailerbody. Using ground wire supplied, connect power plant to a suitable ground as described below. Thefollowing sources of a good ground are listed in order of preference.NOTEAs a substitute for the supplied ground wire, any copper wire of at least No. 6AWG maybe used.4-4