4 APPLICATION PROFILEIFC 3004.2.2 Status valueThe meanings of the status byte (unsigned integer) are described in the following tables.Quality Quality substatus LimitsGr Gr QS QS QS QS Qu Qu2 7 2 6 2 5 2 4 2 3 2 2 2 1 2 00 0 = bad0 1 = uncertain1 0 = good (Non Cascade)1 1 = good (Cascade) - not supportedStatus = badQuality Quality substatus LimitsGr Gr QS QS QS QS Qu Qu2 7 2 6 2 5 2 4 2 3 2 2 2 1 2 00 0 0 0 0 0 = non-specific0 0 0 0 0 1 = configuration error0 0 0 0 1 0 = not connected0 0 0 0 1 1 = device failure0 0 0 1 0 0 = sensor failure0 0 0 1 0 1 = no communication (last usable value)0 0 0 1 1 0 = no communication (no usable value)0 0 0 1 1 1 = out of serviceStatus = uncertainQuality Quality substatus LimitsGr Gr QS QS QS QS Qu Qu2 7 2 6 2 5 2 4 2 3 2 2 2 1 2 00 1 0 0 0 0 = non-specific0 1 0 0 0 1 = last usable value0 1 0 0 1 0 = substitute-set0 1 0 0 1 1 = initial value0 1 0 1 0 0 = sensor conversion not accurate0 1 0 1 0 1 = engineering unit violation (unit not in the valid set)0 1 0 1 1 0 = sub-normal0 1 0 1 1 1 = configuration error0 1 1 0 0 0 = simulated value26www.krohne.com02/2011 - 4001086601 - AD IFC 300 PROFIBUS R01 en