13.07.2015 Views

VRIOGS 010.7 RevA - Public Transport Victoria

VRIOGS 010.7 RevA - Public Transport Victoria

VRIOGS 010.7 RevA - Public Transport Victoria

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

<strong>VRIOGS</strong> <strong>010.7</strong> Revision A 313. Under these circumstances the bonding design should still maintain a safevoltage level Vmax the value of which may depend on the possible durationof the surge. ARTC Standard PDS 10 – ‘Safe Limits of DC Voltages’ detailsthe factors which determine this level; the Traction System Engineer shouldprovide details of the DCCB time to cut off the fault current.7.3.7 Calculation1. Each section of fault current return should be calculated individually basedon the DCCB settings for the location. Based on the values in ARTCStandard PDS 10 with DCCB ranging from 2000 A to 8000 A and DCresistance of rail from 0.04 Ω/km to 0.033 Ω/km this gives a fault touchpotential voltage Vr of 100 V along a single rail at a distance ranging from312 m to 1.5 km from the negative busbar.2. The spacing between substations is generally about 3 km thus any spurshould be divided at the mid point giving a length of about 1.5 km andhence a maximum Vr at the end of the spur of 100 V to 500 V depending onthe current setting of the DCCB.3. The latter figure is above what may be considered acceptable based onCurve A within ARTC Standard PDS 10. Curve A indicates a maximumvoltage for ‘Long Term Threshold of Let-Go’ at 160 V. By placing a rail torail bond at the end of the spur (for double rail track circuits use animpedance bond without the neutral point connected) both rails would carrythe fault current thus halving the resistance of the spur and hence Vr to250 V. This figure may be considered acceptable for the duration of theDCCB operation.4. If the calculated rail voltage Vr is still considered unacceptable then thelength of the spur shall be subdivided into two or more shorter spurs byinserting IRJs as required.7.4 Other EquipmentAny cables to track connected equipment, including point machines and signal lampunits, should have no metallic shield or armour which could conduct fault current intothe equipment housings.7.5 Immunisation1. All signalling equipment within an Immunised Area shall be designed andconstructed with a suitable level of immunity to the potentially interferingcurrents produced by the electric traction system.2. Due to the high voltages and currents associated with electric tractionsupplies large circulating currents and earth return currents can be expected.These may couple to any conductive circuit within the signalling installation ormay be conducted to the equipment frames via the earthing systems installedfor personnel touch voltage and surge protection.3. Reference for information and treatment for immunization purposes referenceshould also be made to EN 50121-4:2006 Railway Applications-Electromagnetic Compatibility-Part 4: Emission and Immunity of the SignallingNOTE: This document is controlled only when viewed on the DOT Engineering Standards website.Any other copy of this document is uncontrolled, and the content may not be current.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!