8.4 Wiring remote control voltage configurationThe CS can be remotely controlled either by an external voltage (20 to 60 VDC or120Vac), or by “free potential” contacts (internal power supply 30VDC from the CS, oradditional 120Vac source). This choice is made by the values at address 70 in the Jbus table.CONTROL INPUTS CONFIGURATIONInputs configuration Fig Jbus address B7 B6 B5 B4 B3 B2 B1 B0External voltage +20Vto +60V-- to 1 70 X 0 X X X X 0 0control the inputsContacts to control theinputs.2 70 X 0 X X X X 0 124V-- internal voltageExternal voltage 115V~to control the inputs3 70 X 0 X X X X 1 0Internal voltage 115V~to control the inputs4 70 X 0 X X X X 1 060 21362 CIRCUIT SELECTOR Installation & Maintenance Page 13 / 32