7-12 <strong>Bosch</strong> <strong>Rexroth</strong> AG | Electric Drives and Controls <strong>Rexroth</strong> IndraControl VCP 25 | R911299720 / 02Interfaces7.2.1.1 Pin AssignmentFig. 7-16:9-pin D-SUB male and female connector stripConnector in the small operator terminal: 9-pin D-SUB male andfemale connector strip (assignment for male and female connector stripis the same).Pin Designation Function1 nc Not Connected2 CAN_L CAN_L Bus Line (Dominant LOW)3 CAN_GND CAN Ground4 nc Not Connected5 nc Not Connected6 CAN_GND CAN Ground7 CAN_H CAN_H Bus Line (Dominant HIGH)8 nc Not Connected9 nc Not ConnectedFig. 7-17: Pin assignment DeviceNetAll signal lines are looped through from X2.1 to X2.2. The connectingcables should be connected to every pin, including the reserved pins.In this way, the cables can still be used in case of future bus specificationextensions.The D-SUB connector strips must be shielded sufficiently. See chapter„Shielding D-SUB Connectors“ on page 7-23.7.2.1.2 CableA DeviceNet-certified cable must be used.CabletypeLoop resistanceSurgeimpedanceCapacitance perunit length2 x 1.1 mm < 22.6 Ohm/km 120 Ohm < 39.4 pf/m2 x 0.6 mm < 91.8 Ohm/km 120 Ohm < 39.4 pf/mFig. 7-18: Data line DeviceNet