TEMPERATUREElectronics of the unit should be protected with shelter against development oftoo high temperature by direct sunshine.SunshadeDisplay unitconnec torWIRING• Power must be switched off before wiring the unit.• This instrument use electronic components that may be damaged by staticelectricity thus apply precautions commonly used e.g. touching a properlygrounded point before removing cover of the enclosure• After removal of the cover of the housing and taking out the display module(if any), the screw terminals can be accessed. Suggested cable core crosssection 0.5 ... 1.5 mm 2 . The unit has first to be grounded by the inner orouter grounding screw.• After connecting the cable and unit programmed proper sealing and closingshould be ensured.<strong>Co</strong>nnector formeas. of loop current1 2U- U+1/2” NPTM20x1,51 2 3 4 5 6GND4...20 mA loop currentand supply voltage (HART)2 3I-I+1/2” NPTM20x1,54.2. CHECKING OF THE LOOP CURRENTAfter removal of the cover of the housing and taking out the display module (if any), voltage measuring instrument should be connected to the test connector.Setting range to <strong>200</strong> mV the loop current can be measured with an accuracy of ~ 0.5%.12/36 ♦ BKI 03 ATEX 043X ♦ cbr2052a0600p_01