IllustrationDescription5.3.1 PEAK LOPPING. A more advanced variation of the peaklopping system described above is to use a556 or an RS485 enabled 555 load controlmodule with an external device (such as a<strong>PLC</strong> and a kW transducer), variable PeakLopping can be achieved.The 556 or the <strong>PLC</strong> will monitor the siteload levels and vary the generators powerproduction. This can be used to ensure theset is used at it’s most economic load level,and prevents the system exporting power.NOTE: - It is recommended that ROCOF (Rate of change of frequency) or vector shiftdetection components are fitted when paralleling a generating set with the mains.Additional equipment of this type is normally specified by the local electricity SupplyCompany to protect against the generator feeding the mains grid in the case of a mainsfailure. If in doubt, you should refer to your local Electricity Supply Company for advice.16DSE Guide to Synchronising & Load Sharing PART 1 ISSUE5 18/3/04 AM