286. Testing:On the completion of the installation of lightning protection system the following tests shall he carriedout.i) Continuity testThe continuity of all conductors and the efficiency of all bonds and joints shall be checked.ii)Resistance tests:The resistance of the lightning protection system completes with air terminations but without the earthconnection shall be measured and its value shall not exceed 1 ohms.iii)Earth resistance test:The earth resistance shall be measured and it should not exceed 10 ohms.