19CHAPTER 4EARTHING1. SCOPE:This specification is intended to cover the requirements of supply, installation, testing and commissioningofa) Pipe earthingb) Plate earthingc) Strip earthing2. STANDARDS:Earthing installations shall conform to the Indian Electricity Rules - 1956. as amended from time to timeand IS 3043-1989 “code of practice for earthling” with latest amendments.3. Earth electrode arrangement:3.1 Pipe electrode-:3.1.1 Electrode shall be made of CI pipe having a clean surface and not covered with paint. Enamel or poorlyconducting material. Galvanized pipe shall not be smaller than 100 mm ID. Earthing with pipe electrodeshall be done as per the details indicated in IS: 3043/87.3.1.2 Electrode shall be made of GI pipe having 40mm ID with ‘C’ class GI pipe.3.1.3 Electrodes shall be embeded below permanent moisture level3.1.4 The length of pipe electrodes shall not be less than 2.5 m. if rock is encountered, pipes shall be driven to adepth of not less than 1.5 m with 2 nos. of pipes of electrodes with a gap of 2mts. and inter connected.Pipe shall be in one piece and deeply driven.3.1.5 To reduce the depth of burial of an electrode without increasing the resistance, a number of rods or pipesmay have to be connected together in parallel. The distance between two electrodes in such a case shallnot be less than twice the length of the electrode. The earthing lead shall be connected by means of a-through bolt, nuts and washers and cable socket.3.2 Plate electrode:For plate electrodes, minimum dimensions of the electrode shall be as under.3.2.1 GI plate electrode 600 x600 x 6 mm thick3.2.2 Copper plate electrode 600 x 600 x 3 mm thick3.2.3 The electrode shall be buried in ground, with its face vertical and top not less than 2.5 M from the surfaceof the ground.3.2.4 Earthing using plate electrode shall be done as per details indicated in drawing.3.2.5 Plate electrodes shall have galvanized iron water pipe, buried vertically and adjacent to the electrode. Oneend of pipe shall be atleast 5 cm above the surface of the ground and need not be more than 10 cm. Theinternal diameter of the pipe shall be at least 19 mm. The length of pipe under the earth’s surface shall be
20such that it shall be able to reach the center of the plate. The earthing lead shall be securely bolted theplate with two bolts, nuts, check nuts and washers.3.3. Strip or conductor electrodes:3.3.1 Strip electrode shall not be smaller than 25 x 3 mm. if of copper and 25 x 6 mm. if of galvanized iron andsteel. If round conductors are used as earth electrodes, their cross sectional area shall not be smaller than 3sq.mm if of copper and 6 sq.mn if galvanized iron and steel.4. General:3.3.2 Conductor shall be buried in trenches not less than 0.5 m deep.i) All materials used for connecting the earth lead with electrode shall be of GI in case of GI pipe and GIplate electrodes, and of tinned brass in case of copper plate electrode. The earthing lead shall be securelyconnected at the other end to the main board.ii) The earthing lead from electrode onwards shall be suitably protected against mechanical injury by routingthe earth wire / strip through a suitable size of GI pipe.iii) All medium voltage equipments shall be earthed by two separate and distinct connections with the earth.In the case of high and extra high voltages, the neutral points shall be earthed by not less than twoseparate and distinct connections with the earth, each having its own electrode at the generating station orsubstation.iv) All materials, fittings etc. used in earthing shall conform to Indian standard specifications wherever theyexist. In the case of materials for which Indian standard specifications do not exist, such materials shall beapproved by the Engineer-in-Charge.v) The earth electrode shall be kept free from paint, enamel and grease.vi) It shall be ensured that similar material for respective earth electrodes and earth conductors are used.vii)viii)ix)Earth electrode shall not be installed in proximity to a metal fence.Copper GI strip shall be connected to the respective earth electrodes either by brazing or weldingrespectively. The Copper GI strip shall be jointed only either by brazing or by riveting at the end of overlapping portions The over lap shall not be less than 50 mmEarthing clamps used for supporting earth strips shall be made of such materials so as to avoid bimetallicaction between strip and clamps.5. Testing:The earth resistance of each electrode shall be measured by using a reliable and calibrated earth meggerand the value shall be as per IS/IE rules
- Page 59 and 60: 5813.1.a3 Preparation of Surface:Th
- Page 61 and 62: 6014.1.2 Preparation of surface:Pre
- Page 63 and 64: 62solution generously with brush. A
- Page 65 and 66: 64The Gypsum boards used for false
- Page 67 and 68: 661.4.1 Straining posts shall be pr
- Page 69 and 70: 687 Aluminum glazing section Hindal
- Page 71 and 72: 70SPECIFICATIONSPLUMBING AND SANITA
- Page 73 and 74: 722.6 For all pipes, work shall be
- Page 75 and 76: 743.6 As far as possible no GI pipe
- Page 77 and 78: 76Following measures shall be adopt
- Page 79 and 80: 781.15 ANGLE VALVEAngle valve shall
- Page 81 and 82: 803.16 Cast iron gratings shall be
- Page 83 and 84: 82a) The contractor shall at all ti
- Page 85 and 86: 844.5.1 LEADING IN C.I. PIPESThe le
- Page 87 and 88: 865.2.4 TRENCH FILLING OF G.I. PIPE
- Page 89 and 90: 88e) Location of all manholes, catc
- Page 91 and 92: 90Sr.No. MATERIALS APPROVED MAKE/AG
- Page 93 and 94: 2TECHNICAL CONDITIONS1.1 These spec
- Page 95 and 96: 411. Qualified Competent Supervisio
- Page 97 and 98: 6Ceiling rose: a) A ceiling rose or
- Page 99 and 100: 8The consuming device circuit shall
- Page 101 and 102: 10A cover plate at the top of the v
- Page 103 and 104: 12Mechanical operation indicators s
- Page 105 and 106: 1411. Indicating lamps and push but
- Page 107 and 108: 16CHAPTER 31. Scope:LAYING OF CABLE
- Page 109: 183.5.4 Provision shall be made to
- Page 113 and 114: 22ii) Tappings : OFF load tap chang
- Page 115 and 116: 245.3.2 Installation: The transform
- Page 117 and 118: 26A vertical air termination shall
- Page 119 and 120: 286. Testing:On the completion of t
- Page 121 and 122: 30l. Light Switches/Sockets/Fan Reg
- Page 123 and 124: 2TECHNICAL SPECIFICATIONSA) AIR COO
- Page 125 and 126: 47.0 CONEENSATE & DRAIN PIPING:7.1
- Page 127 and 128: 6B) AIR DISTRIBUTION SYSTEM:1.0 GEN
- Page 129 and 130: 8ii.iii.iv.All necessary allowances
- Page 131 and 132: 10ACTUATOR:In case of motorised smo
- Page 133 and 134: 12D) THERMAL/ACOUSTIC INSULATION. G
- Page 135 and 136: 14BASIS OF DESIGNAC REQUIRED FOROFF
- Page 137 and 138: 162.0 INSULATIONManufacturer Materi
- Page 139 and 140: 0G) LIST OF APPROVED MAKES:The foll
- Page 141 and 142: 1IV. TECHNICAL SPECIFICATIONSFORINT
- Page 143 and 144: 316. Unless otherwise provided spec
- Page 145 and 146: 52.9 ROUGH CARPENTRYMaterialAll fra
- Page 147 and 148: 7All joinery to be varnished/spirit
- Page 149 and 150: 9b) After the first coat has fully
- Page 151 and 152: 11b) The Contractor should furnish
- Page 153: 13holes, loose or dead knots or oth
- Page 156 and 157: 2S.N. MATERIAL TEST FIELD/LABORATOR
- Page 158 and 159: 4S.N. MATERIAL TEST FIELD/LABORATOR
19CHAPTER 4EARTHING1. SCOPE:This specification is intended to cover the requirements of supply, installation, testing and commissioningofa) Pipe earthingb) Plate earthingc) Strip earthing2. STANDARDS:Earthing installations shall conform to the <strong>India</strong>n Electricity Rules - 1956. as amended from time to timeand IS 3043-1989 “code of practice for earthling” with latest amendments.3. Earth electrode arrangement:3.1 Pipe electrode-:3.1.1 Electrode shall be made of CI pipe having a clean surface and not covered with paint. Enamel or poorlyconducting material. Galvanized pipe shall not be smaller than 100 mm ID. Earthing with pipe electrodeshall be done as per the details indicated in IS: 3043/87.3.1.2 Electrode shall be made of GI pipe having 40mm ID with ‘C’ class GI pipe.3.1.3 Electrodes shall be embeded below permanent moisture level3.1.4 The length of pipe electrodes shall not be less than 2.5 m. if rock is encountered, pipes shall be driven to adepth of not less than 1.5 m with 2 nos. of pipes of electrodes with a gap of 2mts. and inter connected.Pipe shall be in one piece and deeply driven.3.1.5 To reduce the depth of burial of an electrode without increasing the resistance, a number of rods or pipesmay have to be connected together in parallel. The distance between two electrodes in such a case shallnot be less than twice the length of the electrode. The earthing lead shall be connected by means of a-through bolt, nuts and washers and cable socket.3.2 Plate electrode:For plate electrodes, minimum dimensions of the electrode shall be as under.3.2.1 GI plate electrode 600 x600 x 6 mm thick3.2.2 Copper plate electrode 600 x 600 x 3 mm thick3.2.3 The electrode shall be buried in ground, with its face vertical and top not less than 2.5 M from the surfaceof the ground.3.2.4 Earthing using plate electrode shall be done as per details indicated in drawing.3.2.5 Plate electrodes shall have galvanized iron water pipe, buried vertically and adjacent to the electrode. Oneend of pipe shall be atleast 5 cm above the surface of the ground and need not be more than 10 cm. Theinternal diameter of the pipe shall be at least 19 mm. The length of pipe under the earth’s surface shall be