135. Switch Fuse Units:5.1 GeneralThe switch fuse units shall be of the load break, heavy duty, cubicle type conforming to the requirementsIS and of AC 23 duty.The switch fuse units shall he capable of withstanding the thermal and electromagnetic stresses caused byshort circuits for the time of operation of the associated fuse links.The switch fuse units shall be double break and have quick make break mechanism, designed to ensurepositive operation.All switch fuse contacts shall be silver plated at the current transfer surfaces.The unit shall he provided with a front operating handle. The ON and OFF positions of the switch handleshall be clearly marked.5 2 Interlocks and SafetyInterlocks shall be provided so as to prevent opening of the unit door when the switch is in the ONposition and also to prevent closing of the switch with the door not properly secured. It should however bepossible for a competent person to operate the switch shall be suitable for locking with switch in the OFFposition by means of a padlock.The interior arrangement of the switch fuse unit shall be such that all ‘live’ parts are shrouded,5.3 HRC Fuses:The switch fuse units shall be fitted with High rupturing capacity cartridge fuse links with ISI marking fora rupturing capacity of not less than 50 KA at 415 volts. The fuse links shall be mounted in a draw outcarriage thus ensuring positive isolation of contacts during fuse replacements.6. Current Transformers.Current transformers shall comply with the requirements of relevant latest amendment IS. They shall haveratios, outputs and accuracy as specified in the schedule.7. Indicating / Integrating Meters:All indicating instruments shall he of flush mounted industrial pattern conforming to the relevant latestamended IS. The instrument shall have non-reflecting bezels, clearly, divided and indelibly marked scales.And shall be provided with zero adjusting devices in the front. Integrating instruments shall be of flushmounted switchboard pattern complying with the requirements of relevant latest IS.8. Relays: Circuit breakers shall be provided with integrally mounted relays as specified in theschedule.The relay shall have a set of three phase characteristics, which shall be adjustable over a wide range, toprovide discrimination between multiplicities of devices. The relay shall be able to provide over currentand earth fault protection. Also UV and Shunt trip Relays are to be provided.9. Control switches/Selector switches: Control switches/Selector switches shall be of the heavy-duty rotarytype, with plates clearly marked to show the operating position. They shall be of semi-flush mounted typewith only the front plate and the operating handle projected.10. Contactors : Contactors shall be 3 pole /4 pole load break AC 23 duty with auxiliary contacts,fixed & moving contacts copper tinned, silver coated, interier type ,ounting base frame din rail channel.
1411. Indicating lamps and push buttons:Indicating lamps shall be of the LED type of low watt consumption, provided with series resistors wherenecessary and with translucent lamp covers. Bulbs and lenses shall be easily replaceable from the front.Push buttons shall be of the momentary contact, push to actuate type fitted with self-reset contacts andprovided with plates marked with its junctions.12. Cable terminations:Cable entries and terminals shall be provided in the switchboard to suit the number, type and size ofaluminium conductor power cables and copper conductor control cables as indicated in the schematicdiagram.Provision shall be made for top or bottom entry of cables as required Generous size of cabling chambersshall be provided, with the position of cable glands and terminals such the cables can be easily and safelyterminated.Barriers or shrouds shall be provided to permit safe working at the terminals of one circuit withoutaccidentally touching that of another live circuit.Cable riser shall be adequately supported to withstand the effects of rated short circuit currents withoutdamage and without causing secondary faults.Cable sockets shall be of copper and of the crimping type/soldering as required.13. Control wiring: A1l control wiring shall be carried out with 1100/650 V grade multistandard Copperflexible wire conforming to relevant IS having stranded: copper conductors of minimum 2.5 sq. mmsection for CT Wiring and 1.5sq mm for Control/indicating Instruments.Wiring shall be neatly bunched, adequately supported and properly routed to allow easy access andmaintenance.Wires shall be identified by numbered ferrules at each end. The ferrules shall be of the ring type of nondeterioratingmaterial. They shall be firmly located on each wire so as to prevent free movement.All control circuit fuses shall be mounted in front of the panel and shall be easily accessible.14. Terminal blocks and labels:15. Tests:Terminal block shall be of 500 volts grade of the stud type. Insulating barriers shall be provided betweenadjacent terminals.Terminal block shall have minimum current rating of 10 amps and shall be shrouded. Provisions shall bemade for label inscriptions.Labels shall be made of anodized aluminium, with white engraving on black background. They shall beproperly secured with fasteners. Danger plate of size and descriptions as recommended in the relevant ISshall be provided on the PCC./PDB/MCC.i) The power control centre shall be completely assembled, wired, adjusted and tested for operation undersimulated conditions to ensure correctness of wiring and interlocking and proper functioning of allcomponents.ii) Each power control centre and components shall be subjected to standard routine tests as per applicableclauses of relevant standards.
- Page 53 and 54: 52The tiles shall generally conform
- Page 55 and 56: 54Plaster as herein specified shall
- Page 57 and 58: 5612.9.5 FLOATING COAT OF NEAT CEME
- Page 59 and 60: 5813.1.a3 Preparation of Surface:Th
- Page 61 and 62: 6014.1.2 Preparation of surface:Pre
- Page 63 and 64: 62solution generously with brush. A
- Page 65 and 66: 64The Gypsum boards used for false
- Page 67 and 68: 661.4.1 Straining posts shall be pr
- Page 69 and 70: 687 Aluminum glazing section Hindal
- Page 71 and 72: 70SPECIFICATIONSPLUMBING AND SANITA
- Page 73 and 74: 722.6 For all pipes, work shall be
- Page 75 and 76: 743.6 As far as possible no GI pipe
- Page 77 and 78: 76Following measures shall be adopt
- Page 79 and 80: 781.15 ANGLE VALVEAngle valve shall
- Page 81 and 82: 803.16 Cast iron gratings shall be
- Page 83 and 84: 82a) The contractor shall at all ti
- Page 85 and 86: 844.5.1 LEADING IN C.I. PIPESThe le
- Page 87 and 88: 865.2.4 TRENCH FILLING OF G.I. PIPE
- Page 89 and 90: 88e) Location of all manholes, catc
- Page 91 and 92: 90Sr.No. MATERIALS APPROVED MAKE/AG
- Page 93 and 94: 2TECHNICAL CONDITIONS1.1 These spec
- Page 95 and 96: 411. Qualified Competent Supervisio
- Page 97 and 98: 6Ceiling rose: a) A ceiling rose or
- Page 99 and 100: 8The consuming device circuit shall
- Page 101 and 102: 10A cover plate at the top of the v
- Page 103: 12Mechanical operation indicators s
- Page 107 and 108: 16CHAPTER 31. Scope:LAYING OF CABLE
- Page 109 and 110: 183.5.4 Provision shall be made to
- Page 111 and 112: 20such that it shall be able to rea
- Page 113 and 114: 22ii) Tappings : OFF load tap chang
- Page 115 and 116: 245.3.2 Installation: The transform
- Page 117 and 118: 26A vertical air termination shall
- Page 119 and 120: 286. Testing:On the completion of t
- Page 121 and 122: 30l. Light Switches/Sockets/Fan Reg
- Page 123 and 124: 2TECHNICAL SPECIFICATIONSA) AIR COO
- Page 125 and 126: 47.0 CONEENSATE & DRAIN PIPING:7.1
- Page 127 and 128: 6B) AIR DISTRIBUTION SYSTEM:1.0 GEN
- Page 129 and 130: 8ii.iii.iv.All necessary allowances
- Page 131 and 132: 10ACTUATOR:In case of motorised smo
- Page 133 and 134: 12D) THERMAL/ACOUSTIC INSULATION. G
- Page 135 and 136: 14BASIS OF DESIGNAC REQUIRED FOROFF
- Page 137 and 138: 162.0 INSULATIONManufacturer Materi
- Page 139 and 140: 0G) LIST OF APPROVED MAKES:The foll
- Page 141 and 142: 1IV. TECHNICAL SPECIFICATIONSFORINT
- Page 143 and 144: 316. Unless otherwise provided spec
- Page 145 and 146: 52.9 ROUGH CARPENTRYMaterialAll fra
- Page 147 and 148: 7All joinery to be varnished/spirit
- Page 149 and 150: 9b) After the first coat has fully
- Page 151 and 152: 11b) The Contractor should furnish
- Page 153: 13holes, loose or dead knots or oth
135. Switch Fuse Units:5.1 GeneralThe switch fuse units shall be of the load break, heavy duty, cubicle type conforming to the requirementsIS and of AC 23 duty.The switch fuse units shall he capable of withstanding the thermal and electromagnetic stresses caused byshort circuits for the time of operation of the associated fuse links.The switch fuse units shall be double break and have quick make break mechanism, designed to ensurepositive operation.All switch fuse contacts shall be silver plated at the current transfer surfaces.The unit shall he provided with a front operating handle. The ON and OFF positions of the switch handleshall be clearly marked.5 2 Interlocks and SafetyInterlocks shall be provided so as to prevent opening of the unit door when the switch is in the ONposition and also to prevent closing of the switch with the door not properly secured. It should however bepossible for a competent person to operate the switch shall be suitable for locking with switch in the OFFposition by means of a padlock.The interior arrangement of the switch fuse unit shall be such that all ‘live’ parts are shrouded,5.3 HRC Fuses:The switch fuse units shall be fitted with High rupturing capacity cartridge fuse links with ISI marking fora rupturing capacity of not less than 50 KA at 415 volts. The fuse links shall be mounted in a draw outcarriage thus ensuring positive isolation of contacts during fuse replacements.6. Current Transformers.Current transformers shall comply with the requirements of relevant latest amendment IS. They shall haveratios, outputs and accuracy as specified in the schedule.7. Indicating / Integrating Meters:All indicating instruments shall he of flush mounted industrial pattern conforming to the relevant latestamended IS. The instrument shall have non-reflecting bezels, clearly, divided and indelibly marked scales.And shall be provided with zero adjusting devices in the front. Integrating instruments shall be of flushmounted switchboard pattern complying with the requirements of relevant latest IS.8. Relays: Circuit breakers shall be provided with integrally mounted relays as specified in theschedule.The relay shall have a set of three phase characteristics, which shall be adjustable over a wide range, toprovide discrimination between multiplicities of devices. The relay shall be able to provide over currentand earth fault protection. Also UV and Shunt trip Relays are to be provided.9. Control switches/Selector switches: Control switches/Selector switches shall be of the heavy-duty rotarytype, with plates clearly marked to show the operating position. They shall be of semi-flush mounted typewith only the front plate and the operating handle projected.10. Contactors : Contactors shall be 3 pole /4 pole load break AC 23 duty with auxiliary contacts,fixed & moving contacts copper tinned, silver coated, interier type ,ounting base frame din rail channel.