Low Voltage Power and DC Circuit Breakers - GE Industrial Systems
Low Voltage Power and DC Circuit Breakers - GE Industrial Systems
Low Voltage Power and DC Circuit Breakers - GE Industrial Systems
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
<strong>Low</strong> <strong>Voltage</strong> <strong>Power</strong> <strong>and</strong> <strong>DC</strong> <strong>Circuit</strong> <strong>Breakers</strong><br />
EntelliGuard ® G <strong>Circuit</strong> Breaker<br />
EntelliGuard ® G <strong>Circuit</strong> Breaker Nomenclature<br />
Digit 6 Mounting<br />
Designation Mounting Poles Code<br />
3 1<br />
Drawout 4, right 2<br />
4, left 3<br />
OEM 3 4<br />
Stationary 4, right 5<br />
4, left 6<br />
<strong>GE</strong> Equipment<br />
Drawout 3 D<br />
Stationary 3 F<br />
NOTE: Right, Left indicates the location of the fourth pole, typically used to switch the Neutral.<br />
NOTE: 800A Envelope 2 (E, M Ratings) are not available in 4-pole design.<br />
NOTE: P frame available as 3-pole only<br />
Digit 7 Spring Charge Motor<br />
Spring Charge Motor Electrically Operated (EO) Code<br />
24/30Vdc A<br />
48Vdc B<br />
<strong>DC</strong> 60Vdc C<br />
72Vdc D<br />
110/130Vdc E<br />
250Vdc F<br />
48Vac G<br />
AC<br />
120Vac H<br />
240Vac J<br />
277Vac K<br />
Blank/None1 X<br />
1An "X" (Blank/None) denotes a Manually Operated device (MO)<br />
Spring Charge Contact, GSCC1, included with all Motor Operators.<br />
NOTE: When a Spring Charging Motor is selected, a Closing Device must be selected<br />
from Closing Devices for Digit 8, <strong>and</strong> a Shunt Trip Device must be selected from<br />
Shunt Trip 1 Devices for Digit 9.<br />
Shunt Trip 1 with a coil voltage different from the Spring Charge Motor may be userselected.<br />
When a Motor & Spring Charge Contact is selected, the Ready To Close (RTC) (Digit<br />
13) contact output options to the SD (Codes 1, 2, D, E, G, H, K, L) will be wired to<br />
the Spring Charge Contact location on the Secondary Disconnect Block.<br />
Digit 8 Closing Devices<br />
Closing Coil Type Code<br />
24Vdc A<br />
30Vdc B<br />
48Vac/dc C<br />
60-72Vdc D<br />
Closing Coil (CC) 2 110Vdc/130Vdc; 120Vac E<br />
208Vac F<br />
220Vdc; 240Vac G<br />
250Vdc; 277Vac H<br />
24Vdc M<br />
30Vdc N<br />
48Vac/dc P<br />
Comm<strong>and</strong> Operated 60-72 Vdc Q<br />
Closing Coil (CCC) 3 110Vdc/130Vdc; 120Vac R<br />
208Vac S<br />
220Vdc; 240Vac T<br />
Blank/None X<br />
2The Closing Coil (CC) permits either local or remote release of the spring charged<br />
closing mechanism by electrical operation.<br />
3The Comm<strong>and</strong> Operated Closing Coil (CCC) includes an additional anti-pumping<br />
safety feature to ensure that the electrical closing signal must be released<br />
before further closure is attempted, a shut off is initiated if the closing signal is<br />
maintained.<br />
NOTE: Manual button through breaker cover is included as st<strong>and</strong>ard assembly.<br />
NOTE: When a Spring Charging Motor is selected (Digit 7), a Closing Device must be<br />
selected from Closing Devices for Digit 8, <strong>and</strong> a Shunt Trip Device must be<br />
selected from Shunt Trip 1 Devices for Digit 9.<br />
SELECT ONE DEVICE ONLY.<br />
Rev. 9/12<br />
Prices <strong>and</strong> data subject<br />
to change without notice<br />
Digit 9 Shunt Trip<br />
Extended Range Shunt Trip (ANSI/UL) 4 Code<br />
24Vdc M<br />
48Vac/dc P<br />
70-72Vdc Q<br />
110/125Vdc; 120Vac R<br />
208Vac S<br />
220Vdc; 240Vac T<br />
250Vdc; 277Vac V<br />
Blank/none X<br />
Section 6<br />
4The Extended Range Shunt Trip is specifically intended <strong>and</strong> required for UL ANSI<br />
Ground Fault applications. The pick up range is 55-110% of the ST coil voltage.<br />
When a motor is selected from the Spring Charging Motor (Digit 7) a Shunt Trip must<br />
be selected.<br />
SELECT ONE DEVICE ONLY.<br />
Digit 10 Under <strong>Voltage</strong> Release (UVR)<br />
UVR with Fixed Time Delay5 Code<br />
24Vdc 1<br />
30Vdc 2<br />
48Vac/dc 3<br />
60-72Vdc 4<br />
110/130Vdc; 120Vac 5<br />
208Vac 6<br />
220Vdc; 240Vac 7<br />
250Vdc; 277Vac 8<br />
Blank/none X<br />
5The UVR Shunt Trip with Fixed Time Delay is specifically intended for applications<br />
where a delay period ('ride-through') is required due to potential voltage events.<br />
The design delays are 50msec when system voltage drops to 50% <strong>and</strong> 20 msec<br />
when system voltage drops below 50%.<br />
An optional External UVR Time Delay Module is available in a 1 - 3sec delay.<br />
SELECT ONE DEVICE ONLY.<br />
www.geindustrial.com BuyLog ® Catalog 6-7