<strong>Low</strong> <strong>Voltage</strong> <strong>Power</strong> <strong>and</strong> <strong>DC</strong> <strong>Circuit</strong> <strong>Breakers</strong><br />

EntelliGuard ® G <strong>Circuit</strong> Breaker<br />

EntelliGuard ® G <strong>Circuit</strong> Breaker Nomenclature<br />

Digit 6 Mounting<br />

Designation Mounting Poles Code<br />

3 1<br />

Drawout 4, right 2<br />

4, left 3<br />

OEM 3 4<br />

Stationary 4, right 5<br />

4, left 6<br />

<strong>GE</strong> Equipment<br />

Drawout 3 D<br />

Stationary 3 F<br />

NOTE: Right, Left indicates the location of the fourth pole, typically used to switch the Neutral.<br />

NOTE: 800A Envelope 2 (E, M Ratings) are not available in 4-pole design.<br />

NOTE: P frame available as 3-pole only<br />

Digit 7 Spring Charge Motor<br />

Spring Charge Motor Electrically Operated (EO) Code<br />

24/30Vdc A<br />

48Vdc B<br />

<strong>DC</strong> 60Vdc C<br />

72Vdc D<br />

110/130Vdc E<br />

250Vdc F<br />

48Vac G<br />

AC<br />

120Vac H<br />

240Vac J<br />

277Vac K<br />

Blank/None1 X<br />

1An "X" (Blank/None) denotes a Manually Operated device (MO)<br />

Spring Charge Contact, GSCC1, included with all Motor Operators.<br />

NOTE: When a Spring Charging Motor is selected, a Closing Device must be selected<br />

from Closing Devices for Digit 8, <strong>and</strong> a Shunt Trip Device must be selected from<br />

Shunt Trip 1 Devices for Digit 9.<br />

Shunt Trip 1 with a coil voltage different from the Spring Charge Motor may be userselected.<br />

When a Motor & Spring Charge Contact is selected, the Ready To Close (RTC) (Digit<br />

13) contact output options to the SD (Codes 1, 2, D, E, G, H, K, L) will be wired to<br />

the Spring Charge Contact location on the Secondary Disconnect Block.<br />

Digit 8 Closing Devices<br />

Closing Coil Type Code<br />

24Vdc A<br />

30Vdc B<br />

48Vac/dc C<br />

60-72Vdc D<br />

Closing Coil (CC) 2 110Vdc/130Vdc; 120Vac E<br />

208Vac F<br />

220Vdc; 240Vac G<br />

250Vdc; 277Vac H<br />

24Vdc M<br />

30Vdc N<br />

48Vac/dc P<br />

Comm<strong>and</strong> Operated 60-72 Vdc Q<br />

Closing Coil (CCC) 3 110Vdc/130Vdc; 120Vac R<br />

208Vac S<br />

220Vdc; 240Vac T<br />

Blank/None X<br />

2The Closing Coil (CC) permits either local or remote release of the spring charged<br />

closing mechanism by electrical operation.<br />

3The Comm<strong>and</strong> Operated Closing Coil (CCC) includes an additional anti-pumping<br />

safety feature to ensure that the electrical closing signal must be released<br />

before further closure is attempted, a shut off is initiated if the closing signal is<br />

maintained.<br />

NOTE: Manual button through breaker cover is included as st<strong>and</strong>ard assembly.<br />

NOTE: When a Spring Charging Motor is selected (Digit 7), a Closing Device must be<br />

selected from Closing Devices for Digit 8, <strong>and</strong> a Shunt Trip Device must be<br />

selected from Shunt Trip 1 Devices for Digit 9.<br />

SELECT ONE DEVICE ONLY.<br />

Rev. 9/12<br />

Prices <strong>and</strong> data subject<br />

to change without notice<br />

Digit 9 Shunt Trip<br />

Extended Range Shunt Trip (ANSI/UL) 4 Code<br />

24Vdc M<br />

48Vac/dc P<br />

70-72Vdc Q<br />

110/125Vdc; 120Vac R<br />

208Vac S<br />

220Vdc; 240Vac T<br />

250Vdc; 277Vac V<br />

Blank/none X<br />

Section 6<br />

4The Extended Range Shunt Trip is specifically intended <strong>and</strong> required for UL ANSI<br />

Ground Fault applications. The pick up range is 55-110% of the ST coil voltage.<br />

When a motor is selected from the Spring Charging Motor (Digit 7) a Shunt Trip must<br />

be selected.<br />

SELECT ONE DEVICE ONLY.<br />

Digit 10 Under <strong>Voltage</strong> Release (UVR)<br />

UVR with Fixed Time Delay5 Code<br />

24Vdc 1<br />

30Vdc 2<br />

48Vac/dc 3<br />

60-72Vdc 4<br />

110/130Vdc; 120Vac 5<br />

208Vac 6<br />

220Vdc; 240Vac 7<br />

250Vdc; 277Vac 8<br />

Blank/none X<br />

5The UVR Shunt Trip with Fixed Time Delay is specifically intended for applications<br />

where a delay period ('ride-through') is required due to potential voltage events.<br />

The design delays are 50msec when system voltage drops to 50% <strong>and</strong> 20 msec<br />

when system voltage drops below 50%.<br />

An optional External UVR Time Delay Module is available in a 1 - 3sec delay.<br />

SELECT ONE DEVICE ONLY.<br />

www.geindustrial.com BuyLog ® Catalog 6-7