Trip Units<br />

Product Number Nomenclature System<br />

Digit 6 <strong>and</strong> 7 Overcurrent Protection Package<br />

Type Over Current (OC) Protection Package Code<br />

LSI (S, switchable) (I, switchable ANSI only) L3<br />

LSIG (S, switchable) (I, switchable ANSI only) L4<br />

St<strong>and</strong>ard Range<br />

Instantaneous<br />

LSIGA (S, switchable) (I, switchable ANSI only) (G, Alarm Only)<br />

LSIC (S, switchable) (I, switchable ANSI only)<br />

LSICA (S, switchable) (I, switchable ANSI only) (C, Alarm Only)<br />

L5<br />

L6<br />

L7<br />

LSIGDA1 (S, G, A switchable) (I, switchable ANSI only) L8<br />

EntelliGuard ® G ANSI/UL LSIGCDA1 (S, G, C, A all switchable) (I, switchable ANSI only) L9<br />

OC Protection LSH (S, switchable) (I, switchable ANSI only) LC<br />

LSHG (S, switchable) (I, switchable ANSI only) LD<br />

Extended Range<br />

Adjustable Instantaneous<br />

LSHGA (S, switchable) (I, switchable ANSI only) (G, Alarm Only)<br />

LSHC (S, switchable) (I, switchable ANSI only)<br />

LSHCA (S, switchable) (I, switchable ANSI only) (C, Alarm Only)<br />

LE<br />

LF<br />

LG<br />

LSHGDA1 (S, G, A switchable) (I, switchable ANSI only) LH<br />

LSHGCDA1 (S, G, C, A all switchable) (I, switchable ANSI only) LK<br />

1Function Combination is NOT UL Listed<br />

NOTES:<br />

L = Long Time (L, I2T) + Fuse Settings (I4T) (Fuse settings are now st<strong>and</strong>ard on all EntelliGuard ® Trip Units)<br />

S = Short Time (Switchable if Instantaneous (I) protection is enabled)<br />

I = St<strong>and</strong>ard Range Adjustable Instantaneous, (IOC, 2x-15x)<br />

H = Extended Range Adjustable Instantaneous, (IOC, 2x-30x), Only for ANSI EntelliGuard ® G<br />

G = Ground Fault Protection (GFP, 3-wire or 4-wire, internal summing) Trip <strong>and</strong> Alarm<br />

C = External CT for ground fault detection (AKD20 application: input from external summing CTs, used for multiple source ground fault dectection.<br />

OEM Application: Zero Sequence Input of 1A = 100%)<br />

D = Defeatable/Switchable Ground Fault, NOT UL Listed<br />

A = Ground Fault, External Ground Fault, Alarm only<br />

GA = Ground Fault Alarm Only<br />

CA = External Ground Fault Alarm Only<br />

GDA, GCDA = Ground Fault Trip <strong>and</strong> Ground Fault Alarm (all switchable, Not UL Listed)<br />

Digit 8 Zone Selective Interlocking (ZSI)<br />

Zone Selective Interlocking Code<br />

ZSI, Short time <strong>and</strong> GF; user seletable Z<br />

Z+IOC or HIOC ZSI; user selectable T<br />

Blank/none X<br />

ZSI selections require Secondary Disconnect Block B <strong>and</strong> 24Vdc control power.<br />

NOTE: Option X is the only valid item when a Switch is selected in Digit 2.<br />

Digit 9 Advanced Features <strong>and</strong> Communications<br />

Advanced Features <strong>and</strong> Communications Code<br />

Reduced Energy Let-Through (RELT) 1<br />

Modbus Protocol + RELT 2<br />

Profibus Protocol + RELT 3<br />

Monitoring + RELT, NO Communication 4<br />

Monitoring + Relay Package + RELT 5<br />

Monitoring + Data Acquisition, Modbus Protocol + RELT 6<br />

Monitoring + Data Acquisition, Profibus Protocol + RELT 7<br />

Monitoring + Data Acquisition + Relay Package, Modbus + RELT 8<br />

Monitoring + Data Acquisition + Relay Package, Profibus + RELT 9<br />

NONE<br />

NOTES:<br />

All Advanced Feature selections require Secondary Disconnect Block B <strong>and</strong><br />

24Vdc control power<br />

RELT = Reduced Energy Let Through<br />

Monitoring = Advanced Metering<br />

Data Acquisition = Waveform Capture <strong>and</strong> Harmonic Analysis<br />

X<br />

6-56<br />

BuyLog ® Catalog<br />

Digit 10 Manual/Auto Trip Reset<br />

www.geindustrial.com<br />

Section 6<br />

Manual/Auto Trip Reset Code<br />

Manual Lockout M<br />

Auto Reset/Reclose A<br />

Auto/Manual Lockout (Selectable) 2 S2 None (Defaults to Auto Reset/Reclose) X<br />

Note: When Bell Alarm with Lockout is selected on the EntelliGuard ® G <strong>Circuit</strong><br />

Breaker, then Code M must be selected<br />

X is only valid on <strong>GE</strong> Legacy <strong>Circuit</strong> <strong>Breakers</strong> <strong>and</strong> Conversion Kits<br />

M is valid on EntelliGuard ® G <strong>Breakers</strong> when a Bell Alarm is selected<br />

A is valid on EntelliGuard ® G <strong>Breakers</strong> when a Bell Alarm is not selected<br />

2S is IEC Only<br />

Digit 11 Factory or Field Installed<br />

Manual/Auto Trip Reset Code<br />

Factory Installed Trip Unit (Original) F<br />

Replacement Trip Unit (shipped loose) R<br />

Rev. 9/12<br />