<strong>Low</strong> <strong>Voltage</strong> <strong>Power</strong> <strong>and</strong> <strong>DC</strong> <strong>Circuit</strong> <strong>Breakers</strong><br />
EntelliGuard ® G <strong>Circuit</strong> Breaker<br />
EntelliGuard ® G <strong>Circuit</strong> Breaker Nomenclature<br />
EntelliGuard ® G <strong>Circuit</strong> Breaker Product Number Structure<br />
G<br />
<strong>Circuit</strong><br />
Breaker Family<br />
G = EntelliGuard ® G<br />
Breaker/Switch<br />
Current Rating/Sensors<br />
16 = 1600A<br />
Short <strong>Circuit</strong> Withst<strong>and</strong> Rating<br />
Interrupting Rating Tier ANSI/UL 1066<br />
Mounting<br />
M = OEM, Drawout, 3 poles<br />
Shunt Trip<br />
R = 110/125Vdc; 120Vac<br />
Rev. 9/12<br />
Prices <strong>and</strong> data subject<br />
to change without notice<br />
6<br />
M<br />
Section 6<br />
A 1 1 H E R X R A X X L V<br />
Digit 1 2<br />
3, 4<br />
5 6 7 8 9 10 11 12 13 14 15 16, 17 18 19 20 Digit<br />
Breaker Switch Type<br />
A = ANSI/U 1066<br />
<strong>Circuit</strong> Breaker<br />
Spring Charge Motor<br />
1 = AC - 120Vac<br />
Closing Devices<br />
E = Closing Coil - 110Vdc/130Vdc; 120Vac<br />
Under <strong>Voltage</strong> Release (UVR)<br />
X = None<br />
Digit 1 <strong>Circuit</strong> Breaker Family<br />
Device Series Line Code<br />
EntelliGuard ® G Breaker/Switch G<br />
Digit 2 Breaker Switch Type<br />
Breaker/Switch Type, Envelope 1 Envelope 2 & 3<br />
Secondary Mounting Side Top Top<br />
ANSI/UL1066 <strong>Circuit</strong> Breaker A N A<br />
UL 489 <strong>Circuit</strong> Breaker B U B<br />
ANSI Non-auto CB<br />
C M C<br />
(ANSI Switch)<br />
UL489 Non-auto CB<br />
D S D<br />
(UL Switch)<br />
Top = Top Mounted Secondary Disconnects (TSD).<br />
Side = Side Mounted Secondary Disconnects (SSD). (Available on Envelope 1 only.)<br />
NOTE: N, U, M, S characters are for Envelope 1 only with top mounted secondary<br />
disconnects (TSD).<br />
When ordering codes A, B, C, D, Side Secondary Disconnects (SSD) are supplied as<br />
st<strong>and</strong>ard on Envelope 1.<br />
Codes N, U, M, S are not valid for Envelopes 2 <strong>and</strong> 3.<br />
Envelope 1 (Type N <strong>and</strong> H, 400A - 2000A).<br />
NOTE: <strong>DC</strong> Ratings; trip unit not included. <strong>DC</strong> Rated <strong>Circuit</strong> <strong>Breakers</strong> require external<br />
control devices (e.g., Type 37 or Type 76 <strong>DC</strong> Relays).<br />
NOTE: Side Secondary Disconnects are specifically intended for 5-High ("high<br />
density") equipment designs.<br />
With Side Mounted Disconnects (SSD), the following Aux. Switches are not valid (In<br />
Digit 12); Auxiliary Switch, 8NO+8NC (<strong>Power</strong> Rated) or Aux. Switch, 4NO/4NC<br />
(<strong>Power</strong> Rated) + 4NO/4NC (High Fidelity).<br />
5<br />
Bell Alarm, Mechanical Counter, Trip Annunciation<br />
Bell Alarm Contact with lockout<br />
Second Shunt Trip, Second UVR<br />
R = Second Entended Range Shunt Trip 110/125Vdc; 120Vac<br />
Rating Plug<br />
1900<br />
www.geindustrial.com BuyLog ® Catalog 6-5<br />
4<br />
Auxiliary Switch, Coil Signaling Contact<br />
CSC, Hi-Fi Via Trip Unit - 2nd ST or 2nd UVR<br />
X<br />
Key Interlock & Padlock Provisions<br />
None<br />
6<br />
Advanced Features <strong>and</strong><br />
Communications<br />
Monitoring + Data acq.,<br />
Modbus Protocol + RELT<br />
Zone Selective Interlocking (ZSI)<br />
None<br />
Overcurrent Protection Ground Fault<br />
LSIG<br />
Mechanical Interlock<br />
None DEFAULT<br />
Digits 3 <strong>and</strong> 4 Current Rating / Sensor<br />
Current Sensor <strong>Circuit</strong> Breaker Switches 1<br />
Rating (A)<br />
ANSI UL489 ANSI UL489<br />
400 04 04 – –<br />
600 – 06 – –<br />
800 08 08 08 08<br />
1000 – 10 – –<br />
1200 – 12 – 12<br />
1600 16 16 16 16<br />
2000 20 20 20 20<br />
2500 – 25 – 25<br />
3000 – 30 – 30<br />
3200 32 – 32 –<br />
4000 40 40 40 40<br />
5000 50 50 50 50<br />
6000 – 60 – 60<br />
1Switches (Digit 2 = M, S, C, D) do not have current Sensors or a trip unit