<strong>Low</strong> <strong>Voltage</strong> <strong>Power</strong> <strong>and</strong> <strong>DC</strong> <strong>Circuit</strong> <strong>Breakers</strong><br />
Trip Units<br />
EntelliGuard ® TU Trip Unit Features<br />
EntelliGuard ® TU Trip Unit<br />
New capabilities in the EntelliGuard ® TU Trip Unit provide ultimate<br />
system reliability <strong>and</strong> selectivity without sacrificing circuit protection.<br />
This superior addition enhances the <strong>Power</strong> Break ® II breaker<br />
with a Waveform Recognition Instantaneous Algorithm that<br />
eliminates costly downtime due to nuisance tripping. It enables<br />
harmonic analysis four cycles prior <strong>and</strong> after an event, <strong>and</strong><br />
discerns whether a downstream breaker/fuse is clearing the fault.<br />
The unit also includes Instantaneous Zone Selective Interlocking<br />
(I-ZSI) (can be used as a feeder <strong>and</strong> downstream device with a<br />
power circuit breaker upstream) which delivers simultaneous <strong>and</strong><br />
independent ZSI of Short Time, Ground Fault <strong>and</strong> Instantaneous<br />
protection, providing the ability to overlap the Instantaneous on<br />
the Main <strong>and</strong> Feeder breakers. Together, these innovative abilities<br />
achieve HRC2 with currents as high as 100kA with simultaneous<br />
flash protection <strong>and</strong> selectivity.<br />
The EntelliGuard ® TU Trip Unit offers optimum circuit safety<br />
<strong>and</strong> arc flash protection with the Reduced Energy Let-Through<br />
function, providing a faster instantaneous trip that may be<br />
used if faster <strong>and</strong> more sensitive protection is required<br />
temporarily. It is commonly referred to as an “Arc Flash Switch”<br />
or “Maintenance Switch”.<br />
The new <strong>and</strong> improved trip unit design delivers selectivity tools<br />
not previously available in <strong>GE</strong> circuit breakers:<br />
Exclusive EntelliGuard ® TU Trip Unit Features<br />
Designed for Flexibility<br />
—A wide range of continuous adjustment Long Time delays<br />
ensure the circuit breaker can be exactly adjusted in to your<br />
selectivity <strong>and</strong> protection needs.<br />
—Multiple Short Time diagonal b<strong>and</strong>s tune your protection to<br />
exactly where it needs to be.<br />
—Flexible time current settings <strong>and</strong> curves -St<strong>and</strong>ard Long Time<br />
characteristics exactly mimic the curve of a thermal magnetic<br />
circuit breaker.<br />
—Flexible Time Current Curves: 44 Long Time Shapes I2T <strong>and</strong><br />
I4T (fuse), 3 Short Time I2T slopes, Short Time adjustable in 55<br />
ms increments, a Selective Ground Fault curve<br />
Instantaneous Protection<br />
—Instantaneous pick-up is adjustable up to 15 times the plug<br />
rating on frames 800-2000A, 13 times on 3000A frames <strong>and</strong><br />
up to 9 times on 4000A frames.<br />
—A separately adjustable fast instantaneous trip- useful for<br />
when the circuit must provide the best possible protection<br />
<strong>and</strong> arc flash performance while sustaining normal load.<br />
—An override instantaneous - provides fast tripping for the<br />
largest bolted fault currents to minimize potential damage.<br />
—Up to 17 Short Time b<strong>and</strong>s allow you to set your circuit breaker<br />
to sustain load requirements without slowing protection.<br />
—Ground Fault Alarm via I/O or Modbus Communications<br />
—Ground fault protection with faster time b<strong>and</strong>s, multiple<br />
slopes <strong>and</strong> the ability to coordinate a 1200A ground fault<br />
with an 800A circuit breaker – a ratio four times better than in<br />
previous generation trip units<br />
Rev. 9/12<br />
Prices <strong>and</strong> data subject<br />
to change without notice<br />
Section 6<br />
Maintenance <strong>and</strong> Diagnostics<br />
—Universal trip plug fits any trip unit.<br />
—Flexible serial communication via Modbus RTU<br />
—Integrates directly into <strong>GE</strong>’s EnerVista ® <strong>Power</strong> Management<br />
System.<br />
—Large backlit LCD with detailed, easy-to-see descriptions.<br />
—Health status via breaker LED indicating normal operation,<br />
errors, pickup, <strong>and</strong> trips while providing non-volatile memory<br />
with a continuous self-testing microprocessor<br />
—Lithium battery to eliminate need for external power for<br />
set-up <strong>and</strong> review<br />
—10 event Log with Date/Time Stamp: Stores the last 10 events.<br />
Date/Time with 24Vdc <strong>Power</strong>.<br />
—Thermal Memory<br />
—WaveForm Capture: 40 Samples/Cycle, 4 cycles prior <strong>and</strong> 4<br />
cycles post event in COMTrade format.<br />
—Free set-up software<br />
To learn more about EntelliGuard ® TU Trip Unit<br />
features see brochure DEA-461C.<br />