Low Voltage Power and DC Circuit Breakers - GE Industrial Systems
Low Voltage Power and DC Circuit Breakers - GE Industrial Systems
Low Voltage Power and DC Circuit Breakers - GE Industrial Systems
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
<strong>Low</strong> <strong>Voltage</strong> <strong>Power</strong> <strong>and</strong> <strong>DC</strong> <strong>Circuit</strong> <strong>Breakers</strong> Section 6<br />
WavePro <strong>Low</strong> <strong>Voltage</strong> <strong>Power</strong> <strong>Circuit</strong> <strong>Breakers</strong><br />
Step 9 Select Second Shunt Trip<br />
If you selected a shunt trip in Step 5 <strong>and</strong> require another, select<br />
your second shunt trip option. Transfer the product number digit<br />
to the box marked Step 9 in the Product Number Line <strong>and</strong> the<br />
price to the box marked Step 9 in the Price Column. Note: Second<br />
shunt trip requires the selection of a 7-stage auxiliary switch in<br />
Step 7.<br />
Step 10 Select Additional Options<br />
Select your combination of additional options. Transfer the product number digit to<br />
the box marked Step 10 in the Product Number Line <strong>and</strong> the price to the box marked<br />
Step 10 in the Price Column.<br />
6-38<br />
A-Disconnect 1<br />
“PM Ready”<br />
<strong>Voltage</strong> Product No. Digit<br />
None<br />
X<br />
120V, 60 Hz 1<br />
240V, 60 Hz 3<br />
24Vdc B<br />
110/125Vdc E<br />
250Vdc F<br />
Hidden Close<br />
Push Button 2<br />
BuyLog ® Catalog<br />
Operation<br />
Counter<br />
Remote Charge<br />
Indicator Product No. Digit<br />
X (none)<br />
A<br />
B<br />
C<br />
D<br />
E<br />
F<br />
G<br />
H<br />
J<br />
K<br />
L<br />
1The 36-point A-Disconnect is automatically supplied if any of the following options were selected in<br />
previous steps:<br />
—zone selective interlock<br />
—shunt trip<br />
—auxiliary switch<br />
—bell alarm<br />
—undervoltage trip<br />
—electrical lockout device<br />
—electric charge <strong>and</strong> close<br />
—MicroVersaTrip PM trip unit (”M” or “PM” option)<br />
Select the A-Disconnect here only if (1) none of these options were selected in previous steps <strong>and</strong><br />
4-wire ground fault is required or (2) none of these options were selected in previous steps <strong>and</strong> your<br />
WavePro breaker is to be “PM ready.” “PM ready” wiring includes inputs for 24V dc auxiliary power,<br />
communications, <strong>and</strong> 3 phase voltage.<br />
2Available only on breakers with electrical charge <strong>and</strong> close option.<br />
www.geindustrial.com<br />
Optional Hidden Close<br />
button feature shown<br />
Rev. 9/12<br />
Prices <strong>and</strong> data subject<br />
to change without notice