<strong>Low</strong> <strong>Voltage</strong> <strong>Power</strong> <strong>and</strong> <strong>DC</strong> <strong>Circuit</strong> <strong>Breakers</strong> Section 6<br />

WavePro <strong>Low</strong> <strong>Voltage</strong> <strong>Power</strong> <strong>Circuit</strong> <strong>Breakers</strong><br />

EntelliGuard ® TU Trip Unit Characteristics<br />

Long Time Short Time<br />

Frame Max. Sensor Rating Current Setting (C) (Pick-Up) Delay (Seconds) 1 Pick-up (Multiple<br />

Envelope Size Ampere Rating (Amperes) (S) Multiple of Rating Plug Amperes (X) Fuse Type (F-B<strong>and</strong>s) Thermal Type (C-B<strong>and</strong>s) of Current Settings) (C) Delay (Seconds)<br />

0.025 0.20<br />

800 800 200, 400, 800 0.025 0.60<br />

0.025 1.21<br />

0.032 1.61 I2T in<br />

1600 1600 800, 1000, 1600<br />

0.044 2.41 0.401 0.059 3.21<br />

0.078 4.02<br />

0.10 4.82<br />

6-32<br />

2000 2000 2000<br />

BuyLog ® Catalog<br />

0.13 5.62<br />

0.17 6.43<br />

0.22 7.23<br />

0.27 8.04<br />

2500 1000, 2000, 2500 0.35 9.64<br />

3000 0.44 11.20<br />

3000 3000<br />

0.55 12.90 I2 0.69 14.50<br />

T out<br />

0.10, 0.21, 0.352 0.87 16.10<br />

4000 4000 4000 1.10 17.70<br />

19.30<br />

Trip Unit Characteristics (continued)<br />

Adjutable Instantaneous Adjustable Instantaneous High Range Instantaneous Ground Fault<br />

Pick-Up without ST (Multiple Pick-Up with ST (Multiple (Multiple of Frame Pick-Up (Multiple Delay with l 2 T Delay with l 2 T<br />

Envelope Size of Rating Plug Amperes) (X) of Rating Plug Amperes) (X) Short Time Rating) (H) of Sensor Ampere Rating) in seconds out seconds 3<br />

800<br />

1600<br />

2000<br />

3000<br />

4000<br />

0.5 thru 1.0 in<br />

Increments of 0.05<br />

1.5 thru 10.0 in 1.5 thru 15.0 in 2.0 thru 0.60 in<br />

0.5 increments 0.5 increments increments of 0.01<br />

1.5 thru 10.0 in 1.5 thru 15.0 in 2.0 thru 0.60 in<br />

0.5 increments 0.5 increments 1.0 increments of 0.01<br />

1.5 thru 10.0 in 1.5 thru 15.0 in 1.0<br />

2.0 thru 0.60 in<br />

0.5 increments 0.5 increments increments of 0.01<br />

1.5 thru 10.0 in 1.5 thru 13.0 in 2.0 thru 0.37 in<br />

0.5 increments 0.5 increments increments of 0.01<br />

1.5 thru 9.0 in 1.5 thru 9.0 in 2.0 thru 0.30 in<br />

0.5 increments 0.5 increments increments of 0.01<br />

1 Time delay shown at 600% of current setting at lower limit of b<strong>and</strong>.<br />

2 Time delay shown at lower limit of each b<strong>and</strong>. All pick-up tolerances are ±10%.<br />

3 Time delay shown at lower limit of each b<strong>and</strong>. Ground fault pick-up not to exceed 1200 amperes<br />

www.geindustrial.com<br />

1.5 thru 9.0 in<br />

Increments of 0.05<br />

.44 at 200% of<br />

pick-up at lower<br />

limit of b<strong>and</strong><br />

0.10, 0.21, 0.35<br />

0.10, 0.21, 0.35<br />

0.10, 0.21, 0.35<br />

0.10, 0.21, 0.35<br />

0.10, 0.21, 0.35<br />

Rev. 9/12<br />

Prices <strong>and</strong> data subject<br />

to change without notice