<strong>Low</strong> <strong>Voltage</strong> <strong>Power</strong> <strong>and</strong> <strong>DC</strong> <strong>Circuit</strong> <strong>Breakers</strong> Section 6<br />

EntelliGuard ® G <strong>Low</strong> <strong>Voltage</strong> <strong>Power</strong> <strong>Circuit</strong> <strong>Breakers</strong><br />

EntelliGuard ® G Cassettes Nomenclature<br />

Digit 5—Cassette AIC Rating<br />

Interrupting Rating Tier ANSI/UL1066 Devices, LVPCB Envelope 1 Envelope 2 Envelope 3<br />

1/2S Override<br />

Code 254V 580V 635V Withst<strong>and</strong> HSIOC No. 1 Override WI Code 400-1200 400-2000 3200 400-3200 3200 4000-5000<br />

6-12<br />

S 65,000 65,000 50,000 50,000 50,000 49,000 53,500 S X<br />

N 65,000 65,000 65,000 65,000 None None None N X X<br />

H 85,000 85,000 65,000 65,000 65,000 63,700 69,500 H X<br />

P2 100,000 100,000 65,000 65,000 65,000 63,700 69,500 P X<br />

E 85,000 85,000 85,000 85,000 None None None E X<br />

M 100,000 100,000 100,000 85,000 85,000 83,800 90,950 M X X<br />

B 100,000 100,000 100,000 100,000 None None None B X X<br />

L 150,000 150,000 100,000 100,000 100,000 98,000 107,000 L X X<br />

Interrupting Rating Tier UL489 Devices ICCB Envelope 1 Envelope 2 Envelope 3<br />

1/2S Override<br />

Code 240V 480V 600V Withst<strong>and</strong> HSIOC No. 1 Override WI Code 400-1200 400-2000 2500-3000 400-3000 3000 4000-6000<br />

S 65,000 65,000 50,000 42,000 42,000 N/A 44,940 S X<br />

N 65,000 65,000 65,000 42,000 42,000 N/A 44,940 N X X<br />

H 85,000 85,000 65,000 50,000 50,000 N/A 53,500 H X X<br />

M 100,000 100,000 100,000 65,000 65,000 N/A 69,550 M X X<br />

L 150,000 150,000 100,000 85,000 85,000 N/A 90,950 L X X<br />

P2 100,000 100,000 65,000 50,000 50,000 N/A 50,000 P X<br />

ANSI Non-Automatic Switches 30 Cycle Withst<strong>and</strong> Ratings Envelope 1 Envelope 2 Envelope 3<br />

Code 254V 580V 635V Code 800-2000 800-3000 3000-6000<br />

N 42,000 42,000 42,000 Note: Non-automatic switches are provided<br />

N X<br />

M 65,000 65,000 65,000 with no internal sensing or tripping mechanism<br />

M X<br />

B 100,000 100,000 100,000 <strong>and</strong> cannot be applied above their respective<br />

withst<strong>and</strong> levels. If a non-automatic device is<br />

B X<br />

UL489 Non-Automatic Switches required at ratings above the available switches<br />

Envelope 1 Envelope 2 Envelope 3<br />

Code 240V 480V 600V is required, it is recommended that a circuit<br />

Code 800-2000 800-3000 3000-6000<br />

breaker set with maximum setting be employed<br />

N<br />

M<br />

B<br />

42,000<br />

65,000<br />

150,000<br />

42,000<br />

65,000<br />

150,000<br />

42,000<br />

65,000<br />

100,000<br />

using external control or protection as required<br />

by the application.<br />

N<br />

M<br />

B<br />

X<br />

X<br />

X<br />

Digit 6 Number of Poles<br />

Devices Series/ Line Code<br />

OEM Cassette - 3 Pole 2<br />

OEM Cassette - 4 Pole 5<br />

<strong>GE</strong> Equipment Cassette - 3 Pole1 7<br />

1<strong>GE</strong> Equipment cassette designed specifically for AKD20 Switchgear.<br />

These cassettes are NOT available for OEMs.<br />

2P frame available as 3-pole only<br />

Digit 7 Shutters<br />

Shutters with Locks Code<br />

Shutter <strong>and</strong> Shutter Lock - Factory Installed S<br />

None X<br />

Loose Cassette Parts- Field Installed Product Number<br />

Carriage Position Switch - 1NO/1NC GCPS1R<br />

Carriage Position Switch-2NO/12NC GCPS2R<br />

1 Kirk Key Interlock Cam for Cassette GCKRKR<br />

1 Ronis Key Interlock Cam for Cassette GCR0NR<br />

Secondary Disconnect Block B, 39 Pole-Top Mounted GSDWTR<br />

Secondary Disconnect Block B, 39 Pole-Side Mounted GSDWSR<br />

Secondary Disconnect Block B is required when:<br />

1. Any "ZONE SELECTIVE INTERLOCKING" options are selected in breaker/trip unit<br />

Catalog Digit 18.<br />

2. Any "ADVANCED FEATURES" are selected in breaker/trip unit Catalog Digit 19.<br />

3. A COIL SIGNALING CONTACT OPTION is selected, Digit 12.<br />

4. A READY TO CLOSE signal via the trip unit is selected, Digit 13.<br />

5. Any of the following OPTIONAL Aux. Contact Switches are selected in Digit 12:<br />

—8NO/NC POWER RATED<br />

—3NO/NC POWER RATED + 2NO/NC Hi-Fi<br />

—4NO/NC POWER RATED + 4NO/NC Hi-Fi<br />

BuyLog ® Catalog<br />

www.geindustrial.com<br />

Rev. 9/12<br />