ClorTec Onsite Hypochlorite Generation Systems - Ohiowater.org
ClorTec Onsite Hypochlorite Generation Systems - Ohiowater.org ClorTec Onsite Hypochlorite Generation Systems - Ohiowater.org
ClorTec Safety1. Active Ventilation / DilutionSystem designed to prevent buildup of hydrogen2. Maintain hydrogen concentrationat less than 25% of the 4% LEL or,1% by volume3. Seven tier safety interlocks on thegeneration plant4. Multiple redundant protectivedevices on electrolytic celloverpressurization5. Maintain a simple cost effectiveproduct86
The ClorTec DesignSeven tier safety interlocks on generation plant•Rupture Disk sensing•Inlet Pressure switch check•PRV flow switch check•Blower current sensing•Air Flow sensing•dP sensing•Plant H2 sensingSolution LineExhaust VentTo AtmospherePressureSwitchFlowSwitchBlower DuctBlower DuctBlowerTo Dosing PumpHypochloriteGeneratorHypochloriteStorage TankNOTE: In order for the unit to run all safety devices must be enabled, in the event ofa component failure or H 2 detection the system will shut down and alarm. Thesoftware will not allow the system to run if the sequence does not cascade in thedesignated order. Thereby identifying switch failure or an attempt to manually enablea primary safety device.87
- Page 36 and 37: RMS Benefits• Eliminates thermal
- Page 38 and 39: RMS Rover- Enhanced EngineeredDesig
- Page 40 and 41: RMS Rover Installation• Simple pr
- Page 42 and 43: RMS Rover Mixing• The RMS Rover b
- Page 44 and 45: RMS Rover Disinfection Options• D
- Page 46 and 47: RMS Rover Disinfection Injection-Ch
- Page 48 and 49: 48RMS Ancillary Equipment
- Page 50 and 51: LiquidChem Chiller Features• Dual
- Page 55 and 56: Liquid ChemChiller• 3” thick ur
- Page 57 and 58: Reservoir Management System (RMS)
- Page 59 and 60: Typical Water Softener Configuratio
- Page 61 and 62: 61The softened water is fed to a br
- Page 63 and 64: 63Saturated brine is fed & mixed wi
- Page 65 and 66: 65CT 450 and larger systems use eit
- Page 67 and 68: 67Clear cell casing provides indica
- Page 69 and 70: 69Plate design allows for self clea
- Page 71 and 72: ClorTec Today• Over 3500 installa
- Page 73 and 74: Introduction to ClorTecHistory• 1
- Page 75 and 76: 75Rectifiers ranging from 65 to 300
- Page 77 and 78: MCT Series Power Supply• Designed
- Page 79 and 80: 79HDPE and FRP tanks available
- Page 81 and 82: 81Multiple tanks are used for large
- Page 83 and 84: 83Hydrogen Dilution Air & Vent Syst
- Page 85: Recommended Venting• Vent Stack w
- Page 89 and 90: Electrolytic Cell Layers of Protect
- Page 91 and 92: Recommend skid mounted dosing pumps
- Page 93 and 94: Dosing Control Philosophy• Recent
- Page 95 and 96: Dosing Controller Options (cont’d
- Page 97 and 98: Dosing Controller Options (cont’d
- Page 99 and 100: Hydra-Cell Pumps•Wobble Plate Des
- Page 101 and 102: 101If an alarm is registered the po
- Page 103 and 104: 103Heaters & Chillers A range of op
- Page 105 and 106: 105RMS
- Page 107 and 108: 107500 gallon/5000 pound brine tank
- Page 109 and 110: 109Redundant 72 ton Brine makers
The <strong>ClorTec</strong> DesignSeven tier safety interlocks on generation plant•Rupture Disk sensing•Inlet Pressure switch check•PRV flow switch check•Blower current sensing•Air Flow sensing•dP sensing•Plant H2 sensingSolution LineExhaust VentTo AtmospherePressureSwitchFlowSwitchBlower DuctBlower DuctBlowerTo Dosing Pump<strong>Hypochlorite</strong>Generator<strong>Hypochlorite</strong>Storage TankNOTE: In order for the unit to run all safety devices must be enabled, in the event ofa component failure or H 2 detection the system will shut down and alarm. Thesoftware will not allow the system to run if the sequence does not cascade in thedesignated order. Thereby identifying switch failure or an attempt to manually enablea primary safety device.87