Conditioning: <strong>pCO</strong> <strong>Standard</strong> chiller + heat pump User Guide ver. 2.9 02/11/99This alarm message alerts operating personnel that the second compressor requiresmaintenance.AL_19AlarmClock Cardnot Installedor not WorkingClock card selected but disconnected or broken.AL_22AlarmEeprom Broken orAbsentCall AssistenceThe eeprom is damaged. Contact the nearest service centre.AL_25Circuit 1Pressure ProbeBroken AlarmThe pressure transducer of the 1st circuit detects out-of-range values.The probe may be broken.AL_26Circuit 2Pressure ProbeBroken AlarmThe pressure transducer of the 2nd circuit detects out-of-range values.The probe may be broken.AL_27Evap. Outlet WaterTemperature ProbeBroken or not Conn.AlarmThe water temperature probe at the evaporator outlet detects out-of-range values. The probemay be broken. This alarm forces the off status of the unit.M_NO_ALARMNo AlarmPendingNo active alarms.Pag.57/61