Conditioning: <strong>pCO</strong> <strong>Standard</strong> chiller + heat pump User Guide ver. 2.9 02/11/99The INFO masks display the date and version of the eeprom (first mask).In the second mask you can set the time of the test.USER PROGRAM loopM_USER_PASSEnter the UserPassword0003Right PasswordPARAMETERS_US1Winter TemperatureSetpoint LimitMinimum35.0°CMaximum 50.0°CPARAMETERS_US2Summer TemperatureSetpoint LimitMinimum05.0°CMaximum 20.0°CPARAMETERS_US3Temperature BandAdjustementWinter03.0°CSummer 03.0°CPARAMETERS_US4Dead Zone Adjust.Temperature00.0°CProbe Used forControl INPUTPARAMETERS_US5Defrost StartSetpoint -02.0°CDefrost EndSetpoint 14.0°CPARAMETERS_US6Pag.47/61