Conditioning: <strong>pCO</strong> <strong>Standard</strong> chiller + heat pump User Guide ver. 2.9 02/11/99IMPORTANT:Set the 4-20 mA configuration by placing the jumper ofconnectors J14 (referring to B5) and J15 (referring to B6) asindicated in the figure on the left.3 2 1In case of errors in the reading of these probe check:- that analogue inputs accept 4 ÷ 20 mA signal (see figure)- that the limits of the set probes correspond to the actual probes- that the correct connection to hold pressureBy measuring voltage at terminals Bn and AVSS you can abtain the probe signal current sincethe impedance of the input is 50 Ohm. The pressure value can be determined as follows:⎛ V⎝ R⎞0.004⎠Fs− Fsmmax minPs= ⎜ − ⎟ ×+0.016P s pressure value (bar)V m voltage measure (V)R Input impedance (Ohm)Fs max , Fs min high and low probe limits (bar) (default <strong>McQuay</strong> = 0 – 30)FsminPag.15/61