Conditioning: <strong>pCO</strong> <strong>Standard</strong> chiller + heat pump User Guide ver. 2.9 02/11/99Inputs and outputs connectionsConnecting NTC temperature probesAVSSBnThe two cables of the NTC probe have no polarity so connect them as you like.CODES "NTC" PROBES:code: NTC030W000 code: NTC060W000 code: NTC120W000The probe signal is an ohm value depending on temperature. The table shows differentresistance values at different temperatures. Disconnect the probe at the interface input andmeasure its resistance at its terminal so as to infer the corresponding temperature value fromthe table:°C: -20; -15; -10; -5; 0; 5; 10; 15; 20; 25; 30; 35KOhm: 67.71; 53.39; 42.25; 33.89; 27.28; 22.05; 17.96; 14.68; 12.09; 10.00; 8.31; 6.94Connecting pressure transducerIf your unit includes pressure probes, connect them to terminals B5 and B6 asshown in thediagram below.Transducer - interface connectionSeries 21 / 22Delivery side 0 : 30 bar ALCO PT1-30A 0712526(Alternative) 0 : 30 bar Code SPK30000000Connector J2J2-7 / B5J2-8 / AVSSJ2-9 / B6Connector J1J1-1 / B8J1-2 / +24VJ1-3 / B7WhiteWhiteBrownBrown = PowerWhite = SignalConnect the transducers directly to the interfacePag.14/61