4.3.1.2. Source Ground Return (SGR)The “Source Ground Return” system directly measures the earth fault current bya specific external sensor.This <strong>protection</strong> detects faults upstream and downstream of the circuit-breaker.It is only possible at the supply end of the <strong>LV</strong> installation.E88019 E88018Figure 33.Note: the SGR CT is specific to this application.The Ground <strong>protection</strong> and Neutral <strong>protection</strong> are separate and thus can becombined.Setting the <strong>protection</strong> devicesGround <strong>protection</strong> can be set for its threshold (limited to 1200 A) by 9 bands andby its time delay (same as the Short Time Delay).To enhance discrimination with fuses or other circuit-breakers, part of the ground<strong>protection</strong> curve can be converted into a reverse curve by choosing the l 2 tONsetting.The SGR <strong>protection</strong> requires use of the MDGF module.4.3.2. Residual current device (RCD) <strong>protection</strong> or“zero sequence” systemRCD <strong>protection</strong> is stipulated by installation standards (IEC 60 364) for <strong>protection</strong>of people and equipment in the following cases:b TT type grounding systems, in which currents resulting from insulation faultsare smallb TN-S type networks with very long cables, in which the instantaneous thresholdis not sufficient to protect a short-circuit at the end of the lineb IT networks with very long cables.This <strong>protection</strong> is also used to provide additional fire <strong>protection</strong>.Its threshold from 500 mA to 30 A and time delay can be set to ensure residualcurrent discrimination.Figure 34.An external rectangular toroid sensor is compulsory.39

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!