LV generator protection - engineering site - Schneider Electric

LV generator protection - engineering site - Schneider Electric

LV generator protection - engineering site - Schneider Electric

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

The <strong>Schneider</strong><strong>protection</strong> solutionb reverse power setting:setting range setting step accuracyactivation 5 kW to 500 kW 5 kW ± 2.5 %thresholdactivation 0.2 to 20 s 0.1 s -20 % to 0 %time delayde-activation 5 kW of activation 5 kW ± 2.5 %threshold thresholdde-activation 1 to 360 s 0.1 s -20 % to 0 %time delay4.2.2.6. Over frequency and under frequencyb causesincorrect operation of <strong>generator</strong> / motor setfrequency reduction is possible when a <strong>generator</strong> is on overloadfrequency increase is possible should the <strong>generator</strong> begin racing after losing itsload.b application:over frequency and under frequency <strong>protection</strong> is used to:Check <strong>generator</strong> frequencyCheck frequency at motor terminalsPrevent saturation of transformers further to a frequency reduction.b principle:the function is activated when frequency exceeds the programmed threshold fora time longer than the time delay.Over frequency monitoringDe-activationtime delayOver Fde-activationzoneOver FactivationzoneActivationtime delayFigure 30: Operation for overfrequency.De-activationthresholdActivationthresholdFrequencyE88007EE88013EDe-activationtime delayUnder FactivationzoneUnder Fde-activationzoneActivationtime delayActivationthresholdDe-activationthresholdFrequencyFigure 31: Operation for underfrequency.36

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!