LV generator protection - engineering site - Schneider Electric
LV generator protection - engineering site - Schneider Electric
LV generator protection - engineering site - Schneider Electric
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
3.2. Downstream <strong>LV</strong> network <strong>protection</strong>3.2.1. Priority circuit <strong>protection</strong>Choice of breaking capacityThis must be systematically checked with the characteristics of the main source(HV/<strong>LV</strong> transformer).Choice and setting of the Short Time Delay releasesb subdistribution boardsthe ratings of the <strong>protection</strong> devices for the subdistribution and final distributioncircuits are always lower than Generator Set rated current. Consequently, exceptin special cases, conditions are similar to supply by the transformer.b main <strong>LV</strong> switchboardv the sizing of the main feeder <strong>protection</strong> devices is normally similar to that of theGenerator Set. Setting of the STD must allow for the short-circuit characteristic ofthe Generator Set (see 3.1.2.).v discrimination of <strong>protection</strong> devices on the priority feeders must be provided in<strong>generator</strong> set operation (it can even be compulsory for safety feeders).It is necessary to check proper staggering of STD setting of the <strong>protection</strong>devices of the main feeders with that of the subdistribution <strong>protection</strong> devicesdownstream (normally set for distribution circuits at 10 ln).Note: when operating on the Generator Set, use of a low sensitivity RCDenables management of the insulation fault and ensures very simplediscrimination.3.2.2. Safety of peopleIn the IT (2 nd fault) and TN grounding systems, <strong>protection</strong> of people againstindirect contacts is provided by the STD <strong>protection</strong> of circuit-breakers. Theiroperation on a fault must be ensured, whether the installation is supplied by theMain source (Transformer) or by the Replacement source (Generator Set).Calculating the insulation fault currentZero-sequence reactance formulated as a % of Uo by the manufacturer x’o.The typical value is 8 %.The phase-to-neutral single-phase short-circuit current is given by:The insulation fault current in the TN system is slightly greater than the threephasefault current: for example, in event of an insulation fault on the system inthe previous example, the insulation fault current is equal to 3 kA.19