13.07.2015 Views

LV generator protection - engineering site - Schneider Electric

LV generator protection - engineering site - Schneider Electric

LV generator protection - engineering site - Schneider Electric

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

3.2. Downstream <strong>LV</strong> network <strong>protection</strong>3.2.1. Priority circuit <strong>protection</strong>Choice of breaking capacityThis must be systematically checked with the characteristics of the main source(HV/<strong>LV</strong> transformer).Choice and setting of the Short Time Delay releasesb subdistribution boardsthe ratings of the <strong>protection</strong> devices for the subdistribution and final distributioncircuits are always lower than Generator Set rated current. Consequently, exceptin special cases, conditions are similar to supply by the transformer.b main <strong>LV</strong> switchboardv the sizing of the main feeder <strong>protection</strong> devices is normally similar to that of theGenerator Set. Setting of the STD must allow for the short-circuit characteristic ofthe Generator Set (see 3.1.2.).v discrimination of <strong>protection</strong> devices on the priority feeders must be provided in<strong>generator</strong> set operation (it can even be compulsory for safety feeders).It is necessary to check proper staggering of STD setting of the <strong>protection</strong>devices of the main feeders with that of the subdistribution <strong>protection</strong> devicesdownstream (normally set for distribution circuits at 10 ln).Note: when operating on the Generator Set, use of a low sensitivity RCDenables management of the insulation fault and ensures very simplediscrimination.3.2.2. Safety of peopleIn the IT (2 nd fault) and TN grounding systems, <strong>protection</strong> of people againstindirect contacts is provided by the STD <strong>protection</strong> of circuit-breakers. Theiroperation on a fault must be ensured, whether the installation is supplied by theMain source (Transformer) or by the Replacement source (Generator Set).Calculating the insulation fault currentZero-sequence reactance formulated as a % of Uo by the manufacturer x’o.The typical value is 8 %.The phase-to-neutral single-phase short-circuit current is given by:The insulation fault current in the TN system is slightly greater than the threephasefault current: for example, in event of an insulation fault on the system inthe previous example, the insulation fault current is equal to 3 kA.19

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!