<strong>Ductable</strong> <strong>water</strong> <strong>unit</strong>FWD 08 - 12 - 20 - 30 - 45UNT-PRC002-GB


© American Standard Inc. 2001 UNT-PRC002-GB


ContentsTechnical data 4Selection procedure 5Determining the total capacity 5Determining the sensible capacity 5FWD <strong>unit</strong>s 6Cooling capacities 6Heating capacities 7Water pressure losses 8Available static pressure 10Sound power levels 11Accessories 12Electric heater 12Hot <strong>water</strong> coil 14Plenums 19Filter boxes 22Intake and discharge grilles 24Diffusers/ducts/condensate pump 26Casing 30Fresh air damper 32Actuator 34Space plans 35Electrical diagrams 37Interconnection diagrams 39AquaStream system 40Psychrometric diagram 43UNT-PRC002-GB3


Technical DataFWD 08 12 20 30 45Power supply (V/Ph/Hz) 230/1/50CapacitiesCooling capacity on <strong>water</strong> (1) (kW) 5,2 8,3 15 18,8 30,1Heating capacity on <strong>water</strong> (2) (kW) 6,3 11,9 18,9 20,9 38,2Fan motor (type) 2 x direct drive centrifugalFan power input (3) (kW) 0,23 0,46 0,65 1,04 1,51Current amps (3) (A) 1,1 2,2 3,1 4,7 5,5Start-up amps (A) 3,2 5,5 9,3 14,1 16,5Air flowminimum (m 3 /h) 490 980 1400 1800 2700nominal (m 3 /h) 820 1650 2300 3000 4500maximum (m 3 /h) 980 1970 2600 3600 5400Main coilWater entering/leaving connections (type) ISO R7 rotating female(Dia) 3/4" 3/4" 1 1/2" 1 1/2" 1 1/2"Electric heater (accessory for blower only)Electric power supply (V/Ph/Hz) 230/1/50 230/1/50 or 400/3/50 400/3/50 400/3/50 400/3/50Heating capacity (kW) 2/4 8 10 12 12Hot <strong>water</strong> coil (accessory for blower only)Heating capacity (4) (kW) 6,3 12 17,4 22,4 34,5G2 filter (filter box accessory)Quantity 2 2 2 2 2Dimensions ( LxWxth) (mm) 386x221x8 486x271x8 586x321x8 586*421*8 586*621*8G4 filter (filter box accessory)Quantity - 2 2 2 2Dimensions ( LxWxth) (mm) - 486x264x48 586x314x48 586*414*48 586*614*48Condensate pump (accessory) (type) CentrifugalWater flow - lift height (l/h - mm) 24 - 500Not available for FWD30 and FWD45Sound level (L/M/H speed)Sound pressure level (5) (dB(A)) 36/40/43 38/41/44 46/50/53 47/52/57 47/52/58Sound power level (5) (dB(A)) 46/50/53 48/51/54 56/60/63 57/62/67 57/62/68Unit dimensionsWidth x Depth (mm) 890 x 600 1090 x 710 1290 x 820 1290 x 970 1290 x 1090Height (mm) 250 300 350 450 650Shipped <strong>unit</strong> dimensionsWidth x Depth (mm) 933 x 644 1133 x 754 1333 x 864 1333 x 1008 1333*1133Height (mm) 260 310 360 460 660Weight (kg) 32 46 61 76 118Colourgalvanised steelRecommended fuse sizeUnit alone (aM/gI) (A) 8/16 8/16 8/16 8/25 8/25Unit with electric heater (gI) (A) 16 (2kW),25 (4kW) 40 (230V),3*16 (400V) 3*20 3*25 3*25(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow(3) At high speed with nominal air flow.(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower <strong>unit</strong>.Heat exchanger operating limits:FWD:*<strong>water</strong> temperature: max 100° C*absolute service pressure: min 1 bar/max 11 barsAccessories - Hot <strong>water</strong> coil:*<strong>water</strong> temperature: min. +2° C/max. 100° C*absolute service pressure: min 1 bar/max 11 bars4 UNT-PRC002-GB


Selection procedureDetermining the totalcapacityUse the cooling and heatingcapacity tables and the air flowdata to choose the <strong>unit</strong>corresponding to your needs.Apply the following capacitycorrection factors, according to:- the temperature difference incooling mode, if it is not 5°C,- the air flow, if it is not thenominal air flow,- the % of ethylene-glycolcontained in the <strong>water</strong> circuit.Calculate the <strong>water</strong> flowaccording to the correctedcapacity data:Q =Corr. Capacity x 0.239temp. diff• The <strong>water</strong> pressure losses in theexchange coils and control valvesmust be determined using thegraphs on page 8.• The available static pressurevalues for the duct network at theFWD <strong>unit</strong> discharge are given bythe table on page 10.• The air pressure losses indicatedfor the different accessories are tobe taken into account todetermine the system's aerauliccharacteristics.Determining the sensiblecapacity• Use the TRANE pyschometricgraph on page 43 directly todetermine:1. The enthalpy of the air enteringthe HE coil (in kJ/kg of dry air) forthe relevant DB temperature anddegree of moisture.2. The specific volume V (in m 3 /kg ofdry air).3. The moisture content MC (in kg/kgof dry air).• Calculate the air mass M (in kg/s)entering the coilM = Q x (1 + MC)Vwhere Q = air flow in m 3 /s• Calculate the enthalpy of the airleaving HLHL = HE - PFMwhere PF = total cooling capacity.• On the graph, plot the enthalphyline HL, and then from the pointcorresponding to the DB/WBentering temperature on the coil,plot the line parallel to thestandard coil curves. Itsintersection with the enthalpy linedefines the DB/WB leavingtemperatures.• Calculate the difference betweenthe DB entering and leavingtemperatures: +ta (in °C)• Calculate the sensible capacity PsPs = +ta x 1.214 x QUNT-PRC002-GB5


FWD <strong>unit</strong>sCooling capacitiesUnit W.E.T. Cooling capacity (kW)(°C)Air inlet temperature DB/WB (°C)21/15 23/16 25/17 27/19 29/215 3.5 4.2 4.9 6.3 7.87 2.7 3.3 4 5.2 6.7FWD 08 9 2 2.6 3.2 4.2 5.6820 m 3 /h 11 1.4 2 2.7 3.4 4.513 0.9 1.4 2.1 2.7 3.515 0.5 0.9 1.4 2.1 2.75 5.2 6.5 7.8 10.1 12.87 3.7 5.1 6.3 8.3 10.9FWD 12 9 2.7 4 5.2 6.6 8.91650 m 3 /h 11 2.1 2.8 4.1 5.3 713 1.4 2.1 2.8 4.2 5.515 0.7 1.4 2 3 4.35 10.5 12.3 14.2 17.8 21.97 8.1 9.9 11.7 15 18.9FWD 20 9 6.2 7.8 9.5 12.3 15.82300 m 3 /h 11 4.4 6.3 7.9 9.8 12.913 2.9 4.5 6.4 8 10.215 1.5 3 4.7 6.4 8.15 13 15.4 17.8 22.4 27.77 9.9 12.3 14.6 18.8 23.8FWD 30 9 7.5 9.7 11.9 15.3 19.93000 m 3 /h 11 5.1 7.7 9.8 12.2 16.113 3.4 5.4 7.8 9.9 12.715 1.7 3.7 5.6 8 105 21 24.7 28.5 35.7 43.87 16. 19.8 23.4 30.1 37.9FWD 45 9 12.3 15.7 19 24.6 31.84500 m 3 /h 11 8.8 12.5 15.7 19.7 25.813 5.8 9.1 12.7 15.9 20.415 2.9 6.1 9.4 12.9 16.1W.E.T.: Water entering temperatureWater temp. delta: 5°CCapacities at indicated nominal air flowQW = 4186 x m 3 /s (l/s) x ∆t°C = kWCapacity correction factorsWater temp. delta (°C)3 5 7 91.22 1.0 0.71 0.54Air flow- 20% Nominal + 20%0.85 1 1.12Ethylene-glycol (%)15 20 30 350.82 0.70 0.63 0.616 UNT-PRC002-GB


Heating capacitiesUnit Water ent./leav. Heating capacity (kW)temp. (°C)Air inlet temperature DB (°C)(°C) 20 15 10 5 045/40 5.2 6.3 7.5 8.6 9.8FWD 08 50/45 6.3 7.5 8.6 9.8 10.9820 m 3 /h 70/50 9.2 10.4 11.6 12.7 13.990/70 14 15.2 16.4 17.5 18.745/40 9.6 11.8 14 16.2 18.4FWD 12 50/45 11.9 14.1 16.2 18.4 20.61650 m 3 /h 70/50 16.8 19.1 21.3 23.5 25.790/70 26.1 28.3 30.5 34 34.945/40 15.5 18.9 22.3 25.7 29.1FWD 20 50/45 18.9 22.3 25.7 29.1 32.52300 m 3 /h 70/50 27.9 31.4 34.9 38.4 41.890/70 42.2 45.6 49 52.5 55.945/40 17 20.8 24.6 28.5 32.3FWD 30 50/45 20.9 24.7 28.5 32.3 36.13000 m 3 /h 70/50 30.1 34 37.9 41.8 45.690/70 46 49.9 53.7 57.6 61.445/40 31.3 38.1 45 51.8 58.6FWD 45 50/45 38.2 45 51.9 58.7 65.54500 m 3 /h 70/50 56.8 63.9 70.9 77.8 84.890/70 85.5 92.4 99.3 106.1 113Capacities at indicated nominal air flowCapacity correction factorsAir flow- 20% Nominal + 20%0.84 1 1.14Ethylene-glycol (%)15 20 30 350.99 0.98 0.97 0.96UNT-PRC002-GB7


Water pressure losses on FWD 08 to 45Coil and headers08122010304510Pressure losses (kPa)0,1 11Water flow (l/s)Main coil volumeSize 08 12 20 30 45Volume (l) 1.6 2.5 3.6 4.9 7.9Pressure losses of 3-way valves for FWD 08-45Coil and headers08-20/bypass08-20/ouverte30-45/bypass30-45/ouverte10010Pressure losses (kPa)10,1 1 10Water flow (l/s)8 UNT-PRC002-GB


UNT-PRC002-GB9


Available static pressureDry coil without filterFWD08Available static pressure (Pa)Air flow (m 3 /h) 500 550 600 650 700 750 800 820 850 900 950 1000Fan 1 (PV) 45 33 18 3speed 2 (MV) 98 88 78 71 63 55 47 43 38 27 16 73 (GV) 116 109 100 92 83 74 68 67 63 56 49 41FWD12Available static pressure (Pa)Air flow (m 3 /h) 1000 1050 1100 1150 1200 1250 1300 1350 1400 1450 1500 1550 1600 1650 1700 1750 1800 1850 1900 1950 2000Fan 1 (PV) 42 23 6speed 2 (MV) 160 145 131 117 102 83 65 47 29 103 (GV) 208 203 197 192 187 181 176 171 165 160 155 149 144 138 130 123 114 104 93 82 72FWD20Available static pressure (Pa)Air flow (m 3 /h) 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 2600Fan 1 (PV) 99 77 44 18speed 2 (MV) 186 179 172 162 148 131 114 97 72 52 253 (GV) 204 199 195 190 186 181 176 171 163 157 144 128 113FWD30Available static pressure (Pa)Air flow (m 3 /h) 1800 1900 2000 2100 2200 2300 2400 2500 2600 2700 2800 2900 3000 3100 3200 3300 3400 3500 3600Fan 1 (PV) 180 160 141 122 101 80 63 50 37 20 2speed 2 (MV) 266 255 244 233 220 207 194 181 167 153 139 119 94 69 52 36 20 03 (GV) 338 329 320 311 302 293 284 276 267 258 249 240 231 222 210 198 187 175 160FWD45Available static pressure (Pa)Air flow (m 3 /h) 2700 2800 3000 3200 3400 3600 3800 4000 4200 4400 4500 4600 4800 5000 5200 5400Fan 1 (PV) 266 262 254 232 198 170 129 70 23speed 2 (MV) 276 274 268 262 256 250 239 227 215 203 192 174 129 73 103 (GV) 295 293 288 284 280 276 271 267 263 259 257 254 250 240 229 219At nominal air flowThe empty boxes correspond to flow-pressure ranges that cannot be used.10 UNT-PRC002-GB


Sound power levelsDischargeMeasurement conditions:Measurements taken in a room adjacent to the room containing the FWD, at the outlet of the rectangular duct (1.5 mlong) fixed to its discharge opening.Fan Power level in dB(A), per Hz frequency band Overall powerUnit speed 125 250 500 1000 2000 4000 8000 dB(A)1 55 50 42 37 37 31 30 46FWD 08 2 57 54 47 40 30 38 40 503 58 57 50 42 32 40 43 531 57 51 45 42 34 33 28 48FWD 10 2 58 54 48 45 38 39 35 513 60 58 50 48 40 42 39 541 57 51 45 42 34 33 28 48FWD 12 2 58 54 48 45 38 39 35 513 60 58 50 48 40 42 39 541 56 62 50 48 39 38 36 56FWD 14 2 61 66 55 53 47 46 45 603 63 69 58 56 50 50 49 631 57 63 51 49 40 39 37 57FWD 20 2 61 66 55 53 47 46 45 603 63 69 58 56 50 50 49 63IntakeMeasurement conditions:Measurements taken at the horizontal air intake.Fan Power level in dB(A), per Hz frequency band Overall powerUnit speed 125 250 500 1000 2000 4000 8000 dB(A)1 56 55 55 53 46 45 42 57FWD 08 2 63 62 60 60 53 53 53 643 66 65 63 62 56 55 57 671 62 58 55 58 51 48 44 61FWD 10 2 66 63 60 62 56 55 52 663 70 67 63 65 59 59 57 691 62 58 55 58 51 48 44 61FWD 12 2 66 63 60 62 56 55 52 663 70 67 63 65 59 59 57 691 66 65 65 65 57 50 46 68FWD 14 2 73 72 69 71 64 59 57 743 78 76 73 75 69 64 63 781 68 72 64 64 56 52 50 69FWD 20 2 76 76 68 71 65 61 61 753 78 79 71 74 69 66 66 78UNT-PRC002-GB11


AccessoriesElectric heaterTechnical dataFWD 08 12 20 30 45Elec. power supply (V/Ph/Hz) 230/1/50 230/1/50 ou 400/3/50 400/3/50 0 400/3/50Power (kW ) 2 ou 4 8 10 12 12Number of stages 1 1 1 1 1Nbr of components/Power 1 ou 2/2 kW 3/2.67 kW 3/3.33 kW 3/4 kW 3/4 kWThis accessory can only be used when the <strong>unit</strong> is blowing air.TAir pressure losses (Pa)UnitNominal-20% air flow +20%FWD 08 - 2kW 1 2 3FWD 08 - 4kW 3 4 5FWD 12 3 5 7FWD 20 3 4 5FWD 30 1 1 2FWD 45 1 112 UNT-PRC002-GB


Connexion diagramsUNT-PRC002-GB13


Hot <strong>water</strong> coilHeating capacitiesUnit Water ent./leav. Heating capacity (kW)temp.Air inlet temperature DB (°C)(°C) 20 15 10 5 060/40 2.3 3 3.7 4.3 4.9FWD08 70/50 3.8 4.4 5 5.6 6.2820m 3 /h 80/60 5.1 5.6 6.2 6.8 7.490/70 6.3 6.9 7.5 8.1 8.760/40 5.3 6.4 7.5 8.5 9.6FWD12 70/50 7.6 8.6 9.7 10.8 11.81650m 3 /h 80/60 9.8 10.9 11.9 13 14.190/70 12 13.1 14.2 15.3 16.460/40 8 9.5 11 12.5 14FWD20 70/50 11.1 12.6 14.4 15.6 17.22300m 3 /h 80/60 14.2 15.7 17.3 18.8 20.490/70 17.4 18.9 20.4 22 23.560/40 9.8 11.9 13.9 15.9 17.9FWD30 70/50 14.1 16.1 18.1 20.1 22.13000m 3 /h 80/60 18.3 20.2 22.3 24.3 26.490/70 22.4 24.5 26.5 28.5 30.660/40 15.8 18.9 21.9 24.9 27.8FWD45 70/50 22.1 25.1 28.1 31.1 34.14500m 3 /h 80/60 28.3 31.3 34.3 37.4 40.590/70 34.5 37.6 40.6 43.7 46.8Capacities at indicated nominal air flow, and atmospheric pressure of 101.3 kPaThis accessory can only be used when the <strong>unit</strong> is blowing air.Capacity correction factorsNominal- 20% air flow +20%0.87 1 1.10Air pressure losses (Pa)UnitNominal-20% air flow +20%FWD 08 6 8 11FWD 12 8 12 16FWD 20 8 11 14FWD 30 7 11 14FWD 45 7 11 1414 UNT-PRC002-GB


Pressure lossesCoilFWD20FWD12FWD08FWD45FWD3010010Pressure losses (kPa)0,1 Pressure losses (kPa)11Coil volumeSize 08 12 20 30 45Volume (l) 0.4 0.6 0.9 1.2 1.8Water pressure losses3-way valve10080Pressure losses (kPa)60504030201086543210.03 0.04 0.05 0.06 0.08 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1Pressure losses (kPa)UNT-PRC002-GB15


16 UNT-PRC002-GB


UNT-PRC002-GB17


18 UNT-PRC002-GB


Circular duct adapter plenumTechnical and dimensional dataThe plenum is made of galvanised unpainted sheet steelUnit Number Diameter of Dimensionsof connections connections (mm) LxPxH (mm)FWD 08 5 160 879x303x202FWD 12 5 200 1118x324x252FWD 20 5 250 1255x361x302FWD 30 5 315 1290x442x402FWD 45 5 3x315+2x400 1290x527x602Air pressure losses (Pa) (3 central connection pieces used)Unit -20% Nominal flow +20%FWD 08 7 10 14FWD 12 20 29 39FWD 20 24 31 37FWD 30 25 35 47FWD 45 25 35 47Vertical discharge and intake plenumTechnical and dimensional dataThe plenum is made of galvanised unpainted sheet steelUnitFWD 08FWD 12FWD 20FWD 30FWD 45DimensionsLxPxH (mm)750x239x253950x289x3031150x339x3531150x439x4531150x639x653Air pressure losses (Pa)Unit -20% Nominal flow +20%FWD 08 7 9 12FWD 12 10 12 15FWD 20 13 17 17FWD 30 9 12 16FWD 45 9 12 16UNT-PRC002-GB19


20 UNT-PRC002-GB


UNT-PRC002-GB21


G2 and G4 Filter boxesTechnical and dimensional dataThe plenum is made of galvanised unpainted sheet steelEU2 filter EU4 filter DimensionsUnit Quantity LxWxth.(mm) %arrestance Quantity LxWxth.(mm) %arrestance LxHxD (mm)FWD 08 2 386x221x8 81 x - - 796x236x108FWD 12 2 486x271x8 81 2 486x264x48 90 996x286x108FWD 20 2 486x321x8 81 2 586x314x48 90 1196x336x108FWD 30 2 586x421x8 81 2 586x414x48 90 1196x436x108FWD 45 2 586x621x8 81 2 586x614x48 90 1196x636x108Air pressure losses (Pa) with clean EU2 filterUnit -20% Nominal flow +20%FWD 08 14 18 23FWD 12 19 24 29FWD 20 20 25 26FWD 30 19 24 28FWD 45 19 24 28Air pressure losses (Pa) with clean EU4 filterUnit -20% Nominal flow +20%FWD 08 - - -FWD 12 30 44 60FWD 20 30 41 51FWD 30 28 38 49FWD 45 28 38 4922 UNT-PRC002-GB


Intake and discharge grillesIntake grille with EU2 filterTechnical and dimensional dataThe plenum is made of galvanised sheet steel painted with colour RAL 9010>EU2 filterDimensionsUnit Quantity LxWxth.(mm) %arrestance LxHxD (mm)FWD 08 1 710x163x7 73 761x214x47FWD 12 1 910x213x7 73 961x264x47FWD 20 1 1110x263x7 73 1161x314x47FWD 30 1 1110x363x7 73 1161x414x47FWD 45 1 1110x563x7 73 1161x614x47Air pressure losses (Pa) with clean EU2 filterUnit -20% Nominal flow +20%FWD 08 16 24 37FWD 12 21 35 60FWD 20 20 27 39FWD 30 38 52 68FWD 45 38 52 6824 UNT-PRC002-GB


Discharge grilleTechnical and dimensional dataThe plenum is made of galvanisedsteel painted with colour RAL 9010>UnitFWD 08FWD 12FWD 20FWD 30FWD 45DimensionsLxPxH (mm)761x214x34961x264x341161x314x341161x414x341161x614x34Air pressure losses PaUnit -20% Nominal flow +20%FWD 08 2 3 4FWD 12 4 7 10FWD 20 5 6 8FWD 30 1 1 2FWD 45 1 1 2UNT-PRC002-GB25


Diffusers/ducts/condensate pumpLinear diffusers and 600x600 cassetteTechnical and dimensional data: see dimensional drawingLinear discharge diffuser type VDL2MD,2 slots-2 directions, Ig 600, duct connection diam. = 200 mmLinear discharge diffuser type VRL2MD,2 slots-2 directions, Ig 600, duct connection diam.= 200 mmAir flowAir pressure loss(m 3 /h) (Pa)72 1108 6144 10180 15216 23252 30288 39Linear intake diffuser type VDL4MD,2 slots-2directions, Ig 1200, duct connection diam. = 200 mmLinear intake diffuser type VRL4MD,2 slots-2 directions, Ig 1200, duct connection diam.= 200 mmAir flowAir pressure loss(m 3 /h) (Pa)144 2180 5216 7252 9288 13360 18550 40Intake and diffusion 600 x 600 cassette, duct connection diam. = 200 mmAir flowAir pressure loss(m 3 /h) (Pa)200 7250 11300 14350 17400 22450 27500 32550 38Insulated flexible duct, diam. 200, Ig 6 m Pressure lossesAir flowAir pressure loss(m 3 /h) (Pa)200 2400 6600 12800 201000 301200 421400 561600 72Centrifugal condensate pumpLifting height= 500 mmMax. condensate flow= 24 l/hTo be used only for FWD 08 to 20.26 UNT-PRC002-GB


UNT-PRC002-GB27


UNT-PRC002-GB29


CasingThe casing is made from paintedgalvanised sheet steelCasing dimensionsUnit L x H x P ( mm )FWD08 894*571*258FWD12 1094*681*308FWD20 1294*791*358FWD30 1294*935*459FWD45 1294*1058*66330 UNT-PRC002-GB


UNT-PRC002-GB31


Fresh air damperThe casing is made from nonpaintedgalvanised sheet steel.Damper dimensionsUnit L x H x P ( mm )FWD08non existentFWD12 1078*272*270FWD20 1278*322*307FWD30 1278*422*382FWD45 1278*622*572Fresh air damper in open positionUnit - 20% Nominal air flow + 20%FWD12 3 6 8FWD20 4 5 7FWD30 4 5 7FWD45 4 5 7Fresh air damper in closed positionUnit - 20% Nominal air flow + 20%FWD12 10 16 23FWD20 10 15 19FWD30 10 14 19FWD45 10 14 1932 UNT-PRC002-GB


UNT-PRC002-GB33


ActuatorThis accessory is not supplied withthe fresh air damper.230V power supplyThe fresh air damper closes whenfresh air temperature drops below12°C.Actuator dimensions (L*H*D):165.5*85*65mmFresh air damper actuator230 V power supplyThe fresh air damper closes whenfresh air temperature drops below12°C.Actuator dimensions (LXPXH) =165X65X85 mm.34 UNT-PRC002-GB


Space requirement plansUNT-PRC002-GB35


36 UNT-PRC002-GB


Electrical diagramsUNT-PRC002-GB37


38 UNT-PRC002-GB


Interconnection diagramsUNT-PRC002-GB39


AquaStream Systeme40 UNT-PRC002-GB


UNT-PRC002-GB41


42 UNT-PRC002-GB


0,30QSQT0,350,400,45Psychrometric diagram0,500,550,600,650,700,750,800,850,900,951,00QT25QSSENSIBLE HEAT RATIO =ENTHALPY (kcal per kg of dry air and associated moisture)0,200,25200,750,760,929080706050 %40300,770,780,790,800,810,820,830,840,850,860,870,90-5051015202010253031908070603250 %40303320100,880,8910 5 0 5 10 15 20 25 30 35 40SENSIBLE HEAT RATIO =27262524WET BULB TEMPERATURE ( C)23HUMIDITY RATIO (or SPECIFIC HUMIDITY) (grams of moisture per kg of dry air)ENTHALPY (kJ per kg of dry air and associated moisture)2221201918171615SPECIFIC VOLUME (m 3 per kg of dry air)ENTHALPY (kJ per kg of dry air and associated moisture)ENTHALPY (kcal per kg of dry air and associated moisture)PSYCHROMETRIC CHART© 1960 THE TRANE COMPANY, LA CROSSE, USANOTE :Reproduction ProhibitedBarometric Pressure 101 kPa0,931 – The black lines indicate the airconditioning process when using Tranecooling coils.2 – The alignment circle is the reference pointfor the sensible to latent heat ratio lines.14131211100,9198WET BULB TEMPERATURE ( C)765PERCENT RELATIVE HUMIDITY (%)0-1010020305405010607015DRY BULB TEMPERATURE ( C)ENTHALPY (kJ per kg of dry air and associated moisture)80902043210 5ENTHALPY (kcal per kg of dry air and associated moisture)151010025110110100908070605040OSO 214 E - 0396- 100 10 20 30UNT-PRC002-GB43


The Trane CompanyAn American Standard Companywww.trane.comFor more information contactyour local sales office ore-mail us at comfort@trane.comLiterature Order NumberDate 0201SupersedesStocking LocationUNT-PRC002-GBN40SD010-GB_0399EuropeSince The Trane Company has a policy of continuous product improvement, it reserves the right to changedesign and specifications without notice.Société Trane – Société Anonyme au capital de 61 005 000 Euros – Siege Social: 1 rue des Amériques –88190 Golbey – France – Siret 306 050 188-00011 – RSC Epinal B 306 050 188Numéro d’identification taxe intracommunanutaire: FR 83 3060501888